VYNCO VMC151 51 Way Combined Meter Board Instruction Manual
- June 14, 2024
- VYNCO
Table of Contents
VYNCO VMC151 51 Way Combined Meter Board
Product Information
Specifications
- Rated Operational Voltage: 415V AC maximum, 50Hz
- Maximum Current: 100A
- Rated Insulation Voltage: 1000V
- Short Circuit Withstand: 10kA
Installation Procedure
- This product is designed to be installed inside a wall cavity with a minimum stud size of 90mm and a minimum plaster board/wall covering of 10mm.
- For surface mounting, use VMCC surface mount enclosure in conjunction with this board.
- The metal wall enclosure must be earthed. Fold out tags (x6) on the side walls of the enclosure can be folded out to set the correct height onto the studs.
- Door hinge pins are easily removable and the door can be reversed so that it swings either left or right. This product is designed to be used with New Zealand and Australia’s MEN system.
- DO NOT install a link between the neutral bars and earth bar on circuits dedicated to RCDs. Please ensure circuits and protective devices are adequately identified during installation.
Earth and Neutral Busbar Layout
- Earth Bar: Brass with steel screws (1 bar)
- Neutral Bar: Brass with steel screws (1 bar)
- RCD Neutral Bar: Brass with steel screws (8 bars)
- Double Screw Tunnels: 3
- Single Screw Tunnels: 40
Installation Instructions
- STEP 1
- STEP 2: Slide pin down to release door. There is no need to remove pin completely.
- STEP 3: Lift and remove door.
Fitting Diagram
To fit into wall cavity, fold out tabs to set height of enclosure onto studs.
FAQ
Q: What is the maximum current rating for this product?
A: The maximum current rating for this product is 100A.
Q: Can the door of this product be reversed?
A: Yes, the door can be easily reversed to swing either left or right.
Q: Can this product be used with RCDs?
A: Yes, this product can be used with RCDs. However, do not install a link between the neutral bars and earth bar on circuits dedicated to RCDs.
Q: Are there any user serviceable parts in this product?
A: No, this product does not contain any user serviceable parts.
SPECIFICATION
SPECIFICATIONS
Rated Operational Voltage| 415V AC maximum, 50Hz
Maximum Current| 100A
Rated Insulation Voltage| 1000V
Short Circuit Withstand| 10kA
DIMENSIONS
Cover Assembly| 800 x 402 x 35mm
Base Box Dimensions| 754 x 355 x 109mm
WARRANTY
This product is covered by a 1 Year Vynco Warranty – proof of purchase is
required. Please contact Vynco for details of returns procedure.
NOTE: This product contains NO user serviceable parts.
SAFETY
This product complies in full with AS/NZS 61439.3.
This product should be installed by a suitably qualified person in accordance
with Australian and New Zealand wiring rules.
INSTALLATION PROCEDURE
- This product is designed to be installed inside a wall cavity with a minimum stud size of 90mm and a minimum plaster board/wall covering of 10mm.
- For surface mounting use VMCC surface mount enclosure in conjunction with this board.
- The metal wall enclosure must be earthed. Fold out tags (x6) on the side walls of the enclosure can be folded out to set the correct height onto the studs.
- Door hinge pins are easily removable and the door can be reversed so that it swings either left or right. This product is designed to be used with New Zealand and Australia’s MEN system.
- DO NOT install a link between the neutral bars and earth bar on circuits dedicated to RCDs. Please ensure circuits and protective devices are adequately identified during installation.
EARTH AND NEUTRAL BUSBAR LAYOUT
EARTH AND NEUTRAL BUSBAR LAYOUT
| Material| Number of Bars| Double Screw
Tunnels| Single Screw Tunnels
Earth Bar| Brass with steel screws| 1| 3| 40
Neutral Bar| Brass with steel screws| 1| 4| 22
RCD Neutral Bar| Brass with steel screws| 8| 1| 3
REMOVING DOOR
-
STEP 1
Rotate top pin 90°. -
STEP 2
Slide pin down to release door. There is no need to remove pin completely. -
STEP 3
Lift and remove door.
FITTING DIAGRAM
To fit into wall cavity, fold out tabs to set height of enclosure onto studs.
VYNCO INDUSTRIES (NZ) LIMITED CHRISTCHURCH
388 Tuam Street, Phillipstown, Christchurch, 8011 PO Box 9022, Tower Junction,
Christchurch 8149 New Zealand
- P +64 3 379 9283
- E sales@vynco.co.nz
- VYNCO.CO.NZ
AUCKLAND
9 Levene Place, Mount Wellington
PO Box 12 249, Penrose, Auckland 1061 New Zealand
P +64 9 525 6051