TRITON AGIO Shower Electric Instruction Manual

June 14, 2024
TRITON

AGIO Shower Electric

Product Information: AGIO Electric Shower

Specifications:

  • Mains water pressure only
  • Minimum inlet pressure: 100kPa (1 bar) for 10.5kW
  • Maximum inlet pressure: 1000kPa (10 bar)

Important Safety Advice:

The shower unit MUST be switched off at the isolating switch
when not in use. This is a safety procedure recommended for all
electrical appliances.

The shower head and hose supplied with this product are a safety
critical part of your shower. Failure to use genuine Triton parts
may cause injury and invalidate your guarantee.

Installation and Operating Instructions:

Please read this book thoroughly and familiarize yourself with
all instructions before commencing installation and keep it for
future reference.

The shower installation MUST be carried out by a suitably
qualified person, following the sequence of this instruction
book.

General Guidance Notes:

  1. Isolate the electrical and water supplies before removing the
    cover.

  2. Read all of these instructions and retain them for later
    use.

  3. DO NOT take risks with plumbing or electrical equipment.

  4. Isolate electrical and water supplies before proceeding with
    the installation.

  5. The unit must be mounted onto the finished wall surface (on top
    of the tiles). DO NOT tile up to or seal around ANY PART of the
    unit using silicone sealer after fixing to the wall. Special care
    must be taken NOT TO BLOCK OR SEAL ANY PRD VENTS ON THE UNIT.

  6. Contact Customer Experience (see back page) if any of the
    following occur:

    • If it is intended to operate the shower at pressures above the
      maximum or below the minimum stated.

    • If the unit shows a distinct change in performance.

    • If the shower is frozen.

  7. If it is intended to operate the shower in areas of hard water
    (above 200 ppm temporary hardness), a scale inhibitor may have to
    be fitted. For advice on the Scale Inhibitor, contact Customer
    Experience.

  8. The shower head must be cleaned regularly with descaler to
    remove scale and debris. Otherwise, restrictions to the flow on the
    outlet of the unit will result in higher temperatures and could
    also cause the Pressure Relief Device (PRD) in the unit to
    operate.

  9. This product is not suitable for mounting into steam rooms or
    steam cubicles.

Plumbing:

The plumbing installation must comply with Water Regulations,
Building Regulations, or any particular regulations as specified by
Local Water Company or Water Undertakers and should be in
accordance with BS EN 806.

FAQ:

Q: Can children use this shower?

A: Yes, this appliance can be used by children aged 3 years and
above and persons with reduced physical, sensory, or mental
capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning the use of the
appliance in a safe way and understand the hazards involved.
However, children should not play with the appliance, and cleaning
and user maintenance should not be made by children.

AGIO
electric shower
DRAW

FOR YOUR SERVICE REFERENCE
NOTE DOWN THE PRODUCT CODE BELOW
(FROM THE FRONT OR TOP OF THE BOX)
ALTERNATIVELY REGISTER BY TEL: 024 7637 8321

IMPORTANT SAFETY ADVICE
The shower unit MUST BE switched off at the isolating switch when not in use. This is a safety procedure recommended for all electrical appliances.
The shower head and hose supplied with this product are a safety critical part of your shower. Failure to use genuine Triton parts may cause injury and invalidate your guarantee.

INSTALLATION AND OPERATING INSTRUCTIONS
Please read this book thoroughly and familiarise yourself with all instructions before commencing installation and keep it for future reference.
The shower installation MUST be carried out by a suitably qualified person, in the sequence of this instruction book.

2180843H – October 2022

INTRODUECleTcItOrNic – shPoLwEeArSE READ
PLEASE READ THIS IMPORTANT SAFETY INFORMATION
Products manufactured by Triton are safe and without risk provided they are installed, used and maintained in good working order in accordance with our instructions and recommendations. WARNING: DO NOT operate the appliance if frozen, or suspected of being frozen. It must thaw out before using. DO NOT operate the appliance if the shower head or spray hose becomes damaged. DO NOT restrict flow out of the appliance by placing shower head in direct contact with your body. DO NOT operate the appliance if water ceases to flow during use or if water has entered inside the unit because of an incorrectly fitted cover. WARNING: If restarting the appliance immediately after stopping, be aware that a slug of hot water will be expelled for the first few seconds. The shower head must be descaled regularly. Fit only shower heads recommended by the manufacturer and never fit any additional device to restrict the water outlet flow. The outlet must not be connected to any tap or fitting other than those specified. This appliance is intended to be permanently connected to the water mains and not connected by a hose set. A suitable double pole isolation switch for supply disconnections must be incorporated in the fixed wiring circuit in accordance with current wiring rules. See Electrical Installation section for further details. The water inlet of this appliance shall not be connected to inlet water obtained from any other water heating system.
Mains water pressure only. Minimum inlet pressure 100kPa (1 bar) 150kPa (1.5 bar) for 10.5kW Maximum inlet pressure 1000kPa (10 bar)
This book contains all the necessary fitting and operating instructions for your electric shower. Care taken during the installation will provide a long, trouble-free life from your shower.
WARNING
This appliance can be used by children aged from 3 years and
above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
Children may not play with the appliance. Cleaning and user
maintenance shall not be made by children.
2

IMPORTANETle-ctrPiLcEAsShEowReEr AD THESE GENERAL GUIDANCE NOTES BEFORE PROCEEDING

1 GENERAL
1.1 Isolate the electrical and water supplies before removing the cover.
1.2 Read all of these instructions and retain them for later use.
1.3 DO NOT take risks with plumbing or electrical equipment.
1.4 Isolate electrical and water supplies before proceeding with the installation.
1.5 The unit must be mounted onto the finished wall surface (on top of the tiles). DO NOT tile up to or seal around ANY PART of the unit using silicone sealer after fixing to the wall. Special care must be taken NOT TO BLOCK OR SEAL ANY PRD VENTS ON THE UNIT.
1.6 Contact Customer Experience (see back page), if any of the following occur:
a) If it is intended to operate the shower at pressures above the maximum or below the minimum stated.
b) If the unit shows a distinct change in performance. c) If the shower is frozen.
1.7 If it is intended to operate the shower in areas of hard water (above 200 ppm temporary hardness), a scale inhibitor may have to be fitted. For advice on the Scale Inhibitor, contact Customer Experience.
1.8 The shower head must be cleaned regularly with descalent to remove scale and debris, otherwise restrictions to the flow on the outlet of the unit will result in higher temperatures and could also cause the (PRD) Pressure Relief Device in the unit to operate.
1.9 This product is not suitable for mounting into steam rooms or steam cubicles.
2 PLUMBING
2.1 The plumbing installation must comply with Water Regulations, Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS EN 806.
2.2 The supply pipe must be flushed to clear debris before connecting to the shower unit.

2.3 DO NOT solder pipes or fittings within 300mm of the shower unit, as heat can transfer along the pipework and damage components.
2.4 DO NOT fit any form of outlet flow control as the outlet acts as a vent for the heater can.
2.5 DO NOT use excessive force when making connections to the flexible hose or shower head, finger tight is sufficient.
2.6 All plumbing connections must be completed before making the electrical connections.
2.7 This appliance MUST NOT be connected to the inlet supply by a hose-set.
3 ELECTRICAL
3.1 The installation must comply with BS 7671 Requirements for electrical installations’ (IEE wiring regulations), building regulations or any particular regulations as specified by the local Electrical Supply Company. 3.2 This appliance MUST be earthed. 3.3 In accordance withThe Plugs and Sockets etc.
(Safety) Regulations 1994′, this appliance is intended to be permanently connected to the fixed wiring of the electrical mains system. 3.4 Make sure all electrical connections are tight to prevent overheating.
3.5 A 30mA residual current device (RCD) MUST be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
3.6 Switch off immediately at isolating switch if water ceases to flow during use.
3.7 Other electrical equipment i.e. extractor fans, pumps must not be connected to the circuits within the unit.
3.8 Switch off at isolating switch when not in use. This is a safety procedure recommended with all electrical appliances.
3.9 As with all electrical appliances it is recommended to have the shower and installation checked at least every two years by a competent electrician to ensure there is no deterioration due to age and usage.

3

Electric shower

INTRODUCTION
This book contains all the necessary fitting and operating instructions for your electric shower. Please read them carefully.
The shower installation must be carried out by a suitably qualified person and in the sequence of this instruction book.
Care taken during the installation will provide a long, trouble-free life from your shower.

SPECIFICATIONS

Electrical Nominal power rating at 240V
8.5kW ­ (40A MCB rating)

Nominal power rating at 230V
7.8kW ­ (40A MCB rating)

Water
Inlet connection ­ 15 mm diameter. Outlet connection ­ ½” BSP male thread.

Entry Points Water ­ Left: top, bottom back, bottom side.
Right: bottom side, bottom back, bottom.
Cable ­ Left: top, bottom back, bottom side. Right: bottom side, bottom.

Materials Backplate, cover, controls, shower head ­ ABS. Sprayplate ­ Acetal. Elements ­ Minerally insulated corrosion resistant
metal sheathing.

Dimensions
Height ­ 300 mm Width ­ 208 mm Depth ­ 110 mm

Standards and Approvals Waterproof rating IPX4.
Complies with the requirements of current British and European safety standards for household and similar electrical appliances.
Complies with requirements of the British Electrotechnical Approvals Board (BEAB).

Meets with Compliance with European Community Directives (CE) and UK Community Directives (UKCA).

ADVICE TO USERS
The following points will help you understand how the shower operates:
a. The electric heating elements operate at a constant rate at your chosen power setting. It is the rate of the water passing through the heater unit which determines the shower temperature at any given setting. The slower the flow the hotter the water becomes and the faster the flow the cooler the water.
b. During winter, mains water supply will be cooler than in summer. Therefore the temperature of the shower will vary between seasons on any one setting of the temperature control, e.g. if you have chosen setting number 6 as your preferred shower temperature in the summer, you will have to increase that number during winter by adjusting the temperature control clockwise (which in effect slows the water flow).
c. The stabiliser valve minimises variations in shower temperature during mains water pressure changes. If changes in shower temperature are experienced during normal use, it will most likely be caused by the water pressure falling near to or below the minimum level. The drop in pressure may be due to water being drawn off at other points in the house whilst the shower is in use. If pressure drops appreciably below the minimum, the heating elements will automatically cut out.
If ever the water becomes too hot and you cannot obtain cooler water, first check that the sprayplate in the shower head has not become blocked.
DO NOT place items such as soap or shampoo bottles on top of the unit. Liquid could seep through the joint between the cover and backplate, and possibly damage the sealing rubber.

4

Electric shower

CONTENTS

Page

INTRODUCTION IMPORTANT SAFETY INFORMATION & GENERAL GUIDANCE NOTES (please read) SPECIFICATIONS GENERAL ADVICE TO USERS Main components ……………………………………………………………….. 6 Electrical requirements ……………………………………………………………. 7 – 8 Water requirements……………………………………………………………… 9 Siting of the shower……………………………………………………………. 10 Fitting the shower to the wall ……………………………………………..11 – 12 Plumbing connections ………………………………………………………… 13 Electrical connections …………………………………………………………. 14 Replacing the cover ……………………………………………………………. 15 Commissioning ………………………………………………………………… 16 Operating the shower………………………………………………………17 – 18 Operating functions ……………………………………………………………. 19 Instructions for installers and service engineers only …………………………. 20
Water/Cable entry points diagram…………………………………………….. 20 Fault finding………………………………………………………………..21 – 22 Spare parts …………………………………………………………………….. 23 Guarantee, service policy, etc. ……………………………………………… rear cover

PRODUCT FICHE

Model

8.5kW

Load Profile

XS

Energy Efficiency Class

A

Energy Efficiency (%)

39

Annual Electricity Consumption (kwh)

482

Sound Power Level (db)

15

To check the product suitability for commercial and multiple installations, please contact Triton’s specification advisory service before installation.
Telephone: 024 7637 2222 Email: technical@tritonshowers.co.uk
5

Electric shower

MAIN COMPONENTS

Fig.1

Inside unit (fig.1) 1. Power neon

11 13

13

12

2. Thermal safety cut-out – TCO 3. Power selector assembly

2

1

4. Can assembly

5. Stabilising valve

6. Solenoid valve

4

7. Outlet pipe 9
8. Pressure relief device (PRD)

9. Terminal block

3

255

mm

10

300 mm

5

10. Pressure switch assembly

11. Top cable/pipe entry 12. Wall screw fixings 13. Cover screw fixings 14. Earth connection 15. Water inlet (fig.2) 16. Cover assembly

6 14
12 15 7
58 mm
8 13
208 mm
NOTE: Not all wiring has been shown for reasons of clarity. T00311

Fig.2 16

6

Electric shower

ELECTRICAL REQUIREMENTS
WARNING! THIS APPLIANCE MUST BE EARTHED
The installation, supply cable and circuit protection must conform with BS 7671 (IEE wiring regulations) and be sufficient for the amperage required.
The following notes are for guidance only:
1 The shower must only be connected to a 230-240V ac supply. If you are installing a shower with a kilowatt rating above 9kW, it is advisable to contact the local electricity supply company.
1.1 The electrical rating of the shower is shown on the rating label (Fig.3) within the unit.
2 Before making any sort of electrical connection within the installation, make sure that no terminal is live. If in any doubt, switch off the whole installation at the mains supply and remove the correct fuse.
3 The shower must be connected to its own independent electrical circuit. IT MUST NOT be connected to a ring main, spur, socket outlet, lighting circuit or cooker circuit.
3.1 The electrical supply must be adequate for the loading of the unit and existing circuits.
4 Check your consumer unit (main fuse box) has a main switch rating of 80A or above and that it has a spare fuse way which will take the fuse or Miniature Circuit Breaker (MCB) necessary for the shower (Fig.4).
4.1 If your consumer unit has a rating below 80A or if there is no spare fuse way, then the installation will not be straightforward and may require a new consumer unit serving the house or just the shower.
4.2 You will need to contact the local electricity company. They will check the supply and carry out what is necessary.
5 For close circuit protection DO NOT use a rewireable fuse. Instead use a suitably rated Miniature Circuit Breaker (MCB) or cartridge fuse (see Table A).
5.1 A 30mA residual current device (RCD) MUST be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.

Fig.3 – Illustrative purposes only
Triton Showers, Triton Road, Nuneaton, Warwickshire, CV11 4NR
xxxx

Fig.4 Schematic of installation circuit
Pull cord isolating switch

RCD
(can be part of consumer unit)

Shower unit

Fuse or MCB

Consumer unit Meter

80A or 100A main switch

Meter tails

Incoming supply fuse

Table A

CIRCUIT PROTECTION

unit rating

MCB

cartridge fuse

7.0kW

30/32A

30A

7.5kW

32A

35A

8.0kW

40A

35A

8.5kW

40A

45A

9.0kW

40A

45A

9.5kW

40/45A

45A

10.5kW

45A

45A

7

Electric shower

6 A 45 amp double pole isolating switch with a minimum contact gap of 3mm in both poles must be incorporated in the circuit.

6.1 It must have a mechanical indicator showing when the switch is in the OFF position, and the wiring must be connected to the switch without the use of a plug or socket outlet.

6.2 The switch must be accessible and clearly

able, but out of reach of a person

u

xed bath or shower, except for the

cord of a cord operated switch, and should

be placed so that it is not possible to touch

the switch body while standing in a bath or

shower cubicle. It should be readily accessible

to switch off after using the shower.

7 Where shower cubicles are located in any rooms other than bathrooms, all socket outlets in those rooms must be protected by a 30mA RCD.

8 The current carrying capacity of the cable must be at least that of the shower circuit protection (see Table B).

8.1 To obtain full advantage of the power provided by the shower, use the shortest cable route possible from the consumer unit to the shower.

8.2 It is also necessary to satisfy the disconnection time and thermal constraints which means that for any given combination of current demand, voltage drop and cable size, there is a maximum permissible circuit length.

9 The shower circuit should be separated from other circuits by at least twice the diameter of the cable or conduit.

9.1 The current rating will be reduced if the cabling is bunched with others, surrounded by thermal loft or wall insulation or placed in areas where the ambient temperature is above 30°C. Under these conditions, derating factors apply and it is necessary to select a larger cable size.

9.2 In the majority of installations (see Table B), the cable will unavoidably be placed in one or more of the above conditions. This being so, it is strongly recommended to use a minimum of 10mm cabling throughout the shower installation.

9.3 In any event, it is essential that individual site conditions are assessed by a competent electrician in order to determine the correct cable size and permissible circuit length.
Table B

Twin and earth PVC insulated cable Current carrying capacity

Installed in an insulated wall

In conduit trunking

Clipped direct or buried in a non-insulated
wall

6mm² 32A
10mm² 43A
16mm² 57A

6mm² 38A
10mm² 52A
16mm² 69A

6mm² 46A
10mm² 63A
16mm² 85A

Note: Cable selection is dependent on derating factors

*The method below may be used by installers to determine the approximate
size of the incoming cable.

6mm2

10mm2

16mm2

1. Measure the width of an individual strand, and half that measurment to find (r), e.g: 1.34mm ÷ 2 = (r) 0.67mm
2. Multiply (r) x (r) x 3.14, e.g: (r) 0.67 x (r) 0.67 x 3.14 = 1.41mm2
3. Multiply this by the number of wire strands (usually 7), e.g: 1.41mm2 x 7 = 9.87mm2.
4. The number obtained would suggest 10mm2 wiring.
*PLEASE NOTE: If unsure, consult a qualified Electrician.

8

Electric shower

Mains electric supply (via double pole switch)

Isolating stopvalve

Double pole
isolating switch
Shower unit

Mains water supply

Separate permanently connected supply
from consumer unit
Fig.5 Diagrammatic view (not to scale)

WATER REQUIREMENTS
WARNING!
The shower must not be positioned where it will be subjected to freezing
conditions.
The installation must be in accordance with Water Regulations and Bylaws.
To guarantee activating the heating elements, the shower must be connected to a mains water supply with a minimum running pressure of 100kPa (1.0 bar) at a minimum flow rate of eight litres per minute for the 8.5kW rated model, and nine litres per minute for the 9.5kW rated model.
For the 10.5kW rated shower, the minimum running pressure must be 150kPa (1.5 bar) at a minimum flow rate of eleven litres per minute.
For all models the maximum static pressure must not exceed 1000kPa (10 bar).
Note: If the stated flow rates are not available, it may not be possible to achieve the best performance from the unit throughout the year.
During periods of high ambient temperatures it may be necessary to select a low power setting to achieve your preferred shower temperature.
The water supply can be taken from a cold water storage cistern provided there is a minimum head of ten metres above the shower head. It must be an independent supply to the shower only.
If it is intended to operate the shower at pressures above the maximum or below the minimum stated, contact Customer Service for advice.
Fig.5 shows a typical system layout.
DO NOT use jointing compounds on any pipe fittings for the installation.

9

Electric shower

SITING OF THE SHOWER
IMPORTANT: If installing onto a tiled wall always mount the unit on the surface of the tiles. NEVER tile up to the unit.
Refer to fig.6 for correct siting of shower.
Position the unit where it will NOT be in direct contact with water from the shower head. Position the shower unit vertically.
Leave enough room between the ceiling and the shower to allow access to the cover top screws.
Note: Water Regulations require the shower head be `constrained by a fixed or sliding attachment so that it can only discharge water at a point not less than 25mm above the spill-over level of the relevant bath, shower tray or other fixed appliance’. The use of the supplied retaining ring/gel hanger will in most cases meet this requirement, but if the shower head can be placed within a bath, basin or shower tray, then a double check valve, or similar, must be fitted in the supply pipework to prevent back-flow.
Pressure relief safety device
A pressure relief device (PRD) is designed into the shower unit which complies with European standards. The PRD provides a level of appliance protection should an excessive build up of pressure occur within the shower.
DO NOT operate the shower with a damaged or kinked shower hose, or a blocked shower head which can cause the PRD to operate.
When commissioning, the shower head must be removed from the flexible hose, while at the same time the temperature control must be at the minimum flow position. Failure to follow this procedure may also cause the PRD to operate.
Make sure the shower is positioned over a bath or shower tray because if the PRD operates, then water will eject from the bottom of the unit.
Should this happen, turn off the electricity and water supplies to the shower at the isolating switch and stopvalve. Contact Customer Service for advice on replacing the PRD.

Shower unit can be mounted either
side of riser rail

Retaining ring

Height of shower head
and shower to suit user’s requirement

25 mm minimum
Outline of bath or shower tray

Shower unit must not be within an area 1 metre
from base

Fig.6 Diagrammatic view (not to scale)

10

Fig.7 Fig.8

20 mm

Electric shower FITTING THE SHOWER TO THE WALL

WARNING! Check there are no hidden cables or pipes before drilling holes for wall
plugs. Use great care when using power tools near water. The use of
a residual current device (RCD) is recommended when using power tools.

Note: The control knobs are an integral part of the cover ­ DO NOT attempt to remove them.
Lift the cover from the backplate and remove the trimplate.
Entry positions for the mains water and electric cable are from the top, bottom, either side or from the back.
Note: Deviations from the designated entry points will invalidate product approvals.
If a bottom entry has been chosen, the pipe trim on the bottom of the cover should be removed (fig.7).
If a top entry has been chosen, the pipe trim on the top of the backplate should be removed (fig.8).
If a side entry is required, the trimplate side will have to be cut. With the elbow compression fitted on the outlet, temporarily place the trimplate into position, then mark the pipe entry on the side of the trimplate. Carefully remove the appropriate area using a junior hacksaw.

Fig.9

Please note: NONE of the ‘cut outs’ are designed to ‘snap out’. DO NOT remove
using pliers as the backplate or lower trimplate could be damaged.
A junior hacksaw or suitable knife should be used and any rough edges removed.
Damage to the backplate or lower trimplate will invalidate product
specifications and warranty.

11

Electric shower
If installing a feed pipe from the back or bottom, the centre of the inlet valve to the wall surface is 20mm (fig.9).
Note: If entry is from the back, the nut of the compression fitting will be partially behind the surface of the wall. This area MUST be left clear when plastering over the pipework in order to make the nut accessible for future adjustments.
After choosing the site for the shower, use the backplate as a template and mark the two fixing holes (fig.10).
Drill and plug the wall. An appropriate drill bit should be used. If the wall is plasterboard or a soft building block, appropriate wall plugs should be fitted.
Screw the top fixing screw into position leaving the base of the screw head protruding 6mm out from the wall.
Hook the backplate over the bottom screw and fit the top fixing screw into position.
DO NOT fully tighten the screws at this stage, as the fixing holes are elongated to allow for out of square adjustment after the plumbing connections have been completed.

Fig.10

12

Electric shower

WARNING!
The outlet of the shower acts as a vent and must not be connected to anything other than the hose and
shower head supplied.

PLUMBING CONNECTIONS
Plumbing to be carried out before wiring DO NOT use jointing compounds on any pipe fittings for the installation.
DO NOT solder fittings near the shower unit as heat can transfer along the pipework and damage components.
Standard 15mm x 15mm brass compression fittings MUST be used to connect to the inlet of the shower.
Note: An additional stopvalve (complying with Water Bylaws/Regulations) MUST be fitted in the mains water supply to the shower as an independent means of isolating the water in order to carry out maintenance or servicing. If this isolator is fitted in a loft space, the loft must have a fixed access ladder and be boarded, with appropriate lighting from the access point to the isolator.
IMPORTANT: Before completing the connection of the water supply to the inlet of the shower, and in compliance with Water Regulations, flush out the pipework to remove all swarf and system debris. To do this, connect a hose to the pipework and turn on the mains water supply long enough to clear the debris to waste.
Procedure Turn off the water supply either at the mains stopvalve or the isolating stopvalve. Connect the mains water supply to the inlet of the shower via 15mm copper, stainless steel or plastic pipe using a 15mm x 15mm brass compression fitting.
Note: The inlet fitting is designed to enter a compression fitting only. DO NOT use push fit connectors as full engagement cannot be guaranteed. DO NOT use excessive force when making these connections.
Make sure the backplate is square on the wall and tighten the two retaining screws which hold it to the wall.
Turn on the mains water supply and check for leaks in the pipework connection to the shower. IMPORTANT: Using a suitable sealant, always seal around the incoming pipework to prevent water entering the wall.
Note: At this stage no water can flow through the unit.
13

Electric shower

ELECTRICAL CONNECTIONS
SWITCH OFF THE ELECTRICITY SUPPLY AT THE MAINS. Fig.11 shows a schematic wiring diagram. The cable entry points are shown in fig.1. The cable can be surface clipped, hidden or via 20mm conduit. Note: Conduit entry can only be from rear. Route the cable into the shower unit and connect to the terminal block (fig.12) as follows:
Earth cable to terminal marked E Neutral cable to terminal marked N Live cable to terminal marked L

Fig.11
7 7

E L

N

1

2 8
4
5

IMPORTANT: Fully tighten the terminal block screws and make sure that no cable insulation is trapped under the screws. Loose connections can result in cable overheating.
Note: The supply cable earth conductor must be sleeved. The outer sheath of the supply cable must be stripped back to the minimum.
The supply cable must be secured either by routing through conduit or in trunking or by embedding in the wall, in accordance with current IEE regulations.
The use of connections within the unit, or other points in the shower circuit, to supply power to other equipment i.e. extractor fans, pumps etc. will invalidate the guarantee.
DO NOT switch on the electricity supply until the cover has been fitted.
Note: The elements on UK models are to 240V specification and will give a lower kW rating if the voltage supply is below 240V.

6

3

1. Terminal block 2. Thermal cut-out 3. Outlet 4. Microswitches 5. Start/stop microswitch

6. Solenoid valve 7. Elements 8. Neon

Fig.13

Terminal block

14

Fig.13
Selector spindle
Fig.14
Fig.15

Electric shower
REPLACING THE COVER
· Locate the trimplate into the backplate and secure with the two fixing screws.
· The power selector spindle must be aligned as shown (fig.13).
· To make sure that the temperature control is correctly positioned on the stabilising valve, temporarily place the cover in position so that the splines engage and rotate the temperature control fully anti-clockwise.
· Remove the cover and position the temperature control knob so that it points to the maximum flow position (fig.14).
· Position the power selector to the STOP position (fig.15).
· Check to ensure that the wiring is not trapped and replace the cover squarely to the backplate and guide into position so that the knobs locate correctly into the splined spindles.
· Should any difficulty arise, recheck the points above.
· While applying slight pressure to the cover, secure in position with the retaining screws.
WARNING COVER RETAINING SCREWS
ONLY the SUPPLIED SCREWS should be used. The use of non supplied screws WILL invalidate product specifications & warranty.

15

Electric shower
COMMISSIONING
WARNING! Before normal operation of the shower, it is essential the following commissioning
procedure is completed correctly.
The first operation of the shower is intended to flush out any remaining unit debris and to make sure the heater unit contains water before the elements are switched on. This operation must be carried out with the flexible hose screwed to the outlet but without the shower head attached. Make sure the outlet of the flexible hose is directed to waste. · Before turning on the electric and mains
water supplies to the shower, make sure that the power selector is at the STOP position (fig.16). · Select the minimum flow position (fig.17).
Note: Failure to turn the control to the minimum flow position may cause the PRD to operate. · Turn on the mains water supply to the shower at the isolating stopvalve and then turn on the electric supply to the shower at the isolating switch. The power indicator will light. · Turn the power selector to the COLD position (fig.18) and wait until water starts to flow from the flexible hose. · Slowly rotate the temperature control fully anti-clockwise to the maximum flow position (fig.19). It will take about thirty seconds for a smooth flow of water to be obtained while air and any debris is flushed from the shower. · When a smooth flow of water is obtained, rotate the temperature control from minimum to maximum several times to release any trapped air within the unit. · Once flushing out has been completed, stop the water flow by turning the power selector to the STOP position. · Fit the shower head to the flexible hose and place in the shower head holder.
The shower is now ready for normal operation.
16

Fig.16 Fig.17 Fig.18 Fig.19

Fig.20
Power selector
High Economy
Temperature control
00326

Electric shower

OPERATING THE SHOWER

WARNING!
Before normal operation of the shower, it is essential that the commissioning procedure has been
completed correctly.

To start the shower

Turning the power selector to the red or blue

Cold

symbol positions will start water to flow.

To stop the shower
Switch the power selector to the STOP position and water will cease to flow.

WARNING!
If restarting immediately after stopping, be aware that a slug of hot water will be
expelled for the first few seconds.

To use the power selector
The power selector has four positions – stop, cold, economy and high as shown in fig.20. · Stop is to switch off the electric and water
supply at the shower – no flow or power used. · Blue symbol is for cold water only. · Red single symbol is the economy setting
for using less power during warmer months. Temperature adjustment at this setting is via the temperature control. · Red double symbol is the high setting which allows the highest flow achievable for your preferred temperature.
Adjustment of the temperature control on the COLD setting will only alter the force of the water from the shower head. It will not alter the water temperature.
Note: If the stated flow rate required for the unit cannot be met due to low water pressure, it will be necessary to operate the unit on `economy’ setting during the warmer months because of flow rate limitations entering the unit.

17

Electric shower
To adjust the shower temperature
Alter the water temperature by increasing or decreasing the flow rate of the water through the shower via the temperature control (fig.21).
After obtaining your preferred showering temperature, the position can be remembered and left as the normal setting and should only need to be altered to compensate for seasonal changes in ambient water temperature. Note: The preferred number on ECONOMY’ will give a different temperature to the same number position onHIGH’.
To decrease the shower temperature
Turning the temperature control anti-clockwise (fig.21) will increase the flow of water through the shower making it cooler.
To increase the shower temperature
Turning the temperature control clockwise (fig.22) will decrease the flow of water through the shower making it warmer.
Note: It is advisable to be certain that the showering temperature is satisfactory by testing with your hand before stepping under the shower head. There will always be a time delay of a few seconds between selecting a flow rate and the water reaching the stable temperature for that flow rate.
CAUTION: It is recommended that persons who may have difficulty understanding or operating the shower controls should not be left unattended while showering. Special consideration should be given to young children and the less able bodied.

Fig.21 Fig.22

18

Electric shower

Fig.23 Power on indicator
327
Note: In normal use, it is in order to leave the water supply permanently on to the shower unit, but as with most electrical appliances, the unit must be switched off at the isolating switch when not in use.

OPERATING FUNCTIONS
Power on indicator (fig.23)
When the electricity supply to the shower is switched on at the isolating switch, the POWER indicator will light.
Note: Should the safety cut-out device operate, the indicator will remain lit.
Low water pressure cut-out
If the water pressure falls below the minimum required for correct operation of the shower, power will be switched off to the heating elements preventing any maintained temperature rises (water will continue to flow). Power will automatically be restored when adequate water pressure returns. TP ­ Temperature Protection
During normal operation if the temperature exceeds the showering safety limit the power to the elements will be removed completely, although water will continue to flow. When the temperature has cooled sufficiently, power to the elements will be automatically restored to the settings at the time of interruption.
Safety cut-out
The unit is fitted with a non-resettable thermal cut-out safety device. In the event of abnormal operation which could cause unsafe temperatures within the unit, the device will disconnect the heating elements. It will require a visit from a qualified engineer to determine the nature of the fault and replace the safety device once the unit has been repaired.

WARNING – CLEANING
Triton recommends that all products are cleaned using warm, soapy water.
Do not use abrasive or aggressive chemical cleaning products as this may affect the product surface finish and
invalidate your guarantee.

19

Electric shower

INSTRUCTIONS FOR INSTALLERS AND SERVICE ENGINEERS ONLY

CLEANING THE INLET FILTER
It is recommended that the filter is periodically cleaned in order to maintain the performance of the shower. It is essential that this operation is carried out by a competent person.
IMPORTANT: Before servicing, switch off the electricity supply at the mains.
Switch off the water supply at the lsolator valve.
Remove the cover. The inlet filter is situated in the inlet pipe, which is part of the solenoid valve (fig.24).
To access the filter, remove the trimplate then disconnect and remove the compression fitting.
Also, depending on the incoming pipework arrangements, if there is not enough slack in the pipework, it could mean the removing the unit from the wall.
When cleaning the filter, DO NOT use a sharp object as it will cause damage. It is preferable to use an old toothbrush or similar.
Note: Full commissioning procedure will need to be performed after cleaning of the filter (see page 16 for information on commissioning procedure).

Fig.24
Filter

ENTRY POINTS

Diagram Key:
Water Entry Points Cable Entry Points

20

Electric shower

FAULT FINDING
IMPORTANT: Switch OFF the electricity at the mains supply and remove the circuit fuse before attempting any fault finding inside the unit.

Problem

Cause

Action

1 Shower inoperable, no water flow.

1.1 Interrupted power supply.

1.1.1 Blown fuse or circuit breaker. Check supply. Renew or reset fuse or circuit breaker. If it fails again, consult a qualified electrician.

2 Water too hot.

1.2 Unit malfunction.
2.1 Not enough water flowing through the shower.

1.2 Power cut. Check other appliances and if necessary, contact local Electricity Supply Co.
1.2.1 Have unit checked. Contact Customer Experience.
2.1.1 Increase flow rate via temperature control. 2.1.2 Blocked shower head — clean or replace
blocked sprayplate in shower head.

2.2 Blockage in supply.

2.2.1 Check if stop valves are fully open. Check if a blockage in the inlet filter.

2.3 Increase in ambient water temperature.

2.3.1 Readjust flow rate to give increased flow. 2.3.2 Select ECONOMY power.

3 Water temperature cycling hot/cool at intervals.

3.1 Heater cycling on temperature limiter.

3.1.1 See Water too hot causes 2.1, 2.2 and 2.3 and their appropriate action/cures. If it continues contact Customer Experience.

4 Water too cool or cold.

4.1 Too much flow.

4.1.1 Reduce flow rate via temperature control. 4.2.1 Is water supply mains or tank fed?

4.2 Water pressure below minimum required (see rating label).

4.2.2 If tank fed, replumb to mains water supply or see 4.2.4.
4.2.3 If mains fed, make sure that mains stopvalve is fully open and that there are no other restrictions in the supply while shower is in use, or see 4.2.4.
4.2.4 Fit pump to give minimum pressure (see rating label). Contact Customer Experience for advice.

4.3 Reduction in ambient 4.3.1 Readjust flow rate to give reduced flow. water temperature. 4.3.2 Select HIGH power.

21

Electric shower

FAULT FINDING

Problem/Symptom Cause

Action/Cure

4 Water too cool or cold. (continued)

4.4 Electrical malfunction.

4.4.1 Have unit checked by suitably qualified electrician or contact Triton Customer Experience.

4.5 Safety cut-out operated.

4.5.1 Thermal safety cut-out device has operated. Have the unit checked by a suitably qualified engineer or contact Customer Experience.

5 Shower varies from normal temperature to cold during use.

5.1 Water pressure has dropped below minimum required.

5.1.1 Wait until the water pressure resumes to normal.

6 Pressure relief device has operated (water ejected from PRD tube).

6.1 Blocked shower head. 6.1.1 Clean or replace blocked sprayplate in shower head and then fit new PRD.

6.2 Twisted/blocked flexible shower hose.

6.2.1 Check for free passage through hose. Replace the hose if necessary and fit new PRD.

6.3 Shower head not removed while commissioning.

6.3.1 Fit new PRD. Commission unit with shower head removed.

7 Shower fails to shut off.

7.1 Faulty power selector. 7.1.1 Replace power selector.

7.2 Debris in the solenoid.

7.2.1 Replace solenoid valve.

Note: Identify the cause of operation before fitting a new PRD unit. When fitting a new PRD, follow the commissioning procedure.
It is advised all electrical maintenance/repairs to the shower should be carried out by a suitably qualified person.

In the unlikely event of unit failure other than detailed in the fault finding page, please contact Customer Experience for advice.
22

Electric shower
To purchase a genuine Triton spare part for your product, please visit www.tritonshowers.co.uk/spares
for product codes and prices. Alternatively please call our Customer Experience team on 024 7637 2222 to order direct. Please have your model name available.
WEEE Directive ­ Policy Statement
As a producer and a supplier of electric showers, Triton Showers is committed to the protection of the environment via our own environmental policy and compliance with the WEEE directive. Triton Showers is fully registered with the Environment Agency under the following schemes:
Repic: Producer Takeback Scheme (PTS) registration number WEE/EJ3466QV Valpak: Distributer Takeback Scheme (DTS) registration number DTS-501317-1 All our electric products are labelled accordingly with the crossed out wheeled bin symbol. This indicates, for disposal purposes at end of life, that these products must be taken to recognised collection points, such as local authority sites/local recycling centres; this will be free of any charges. Do not return to Triton Showers.
23

UK SERVICE POLICY
In the event of a product fault or complaint occurring, the following procedure should be followed:
DO NOT REMOVE THE PRODUCT
1. Telephone Customer Experience on 024 7637 2222 having available your details including post code, the model number and power rating of the product, together with the date of purchase and, where applicable, details of the particular fault.
2. If required, the Customer Experience Advisor will arrange for a qualified engineer to call.
3. All products attended to by a Triton service engineer must be installed in full accordance with the Triton installation guide applicable to the product. Every product pack contains an installation guide, however, they can also be downloaded free at www.tritonshowers.co.uk.
4. Our engineer will require local parking and if a permit is required, this must be available to the engineer on arrival at the call.
5. If loft access is required for isolation or to complete a repair, the loft must have a fixed access ladder and be boarded, with appropriate lighting from the access point to and around the repair area.
6. It is essential that you or an appointed representative, who must be over 18 years of age, is present for the duration of the service engineer’s visit. If the product is in guarantee you must produce proof of purchase.
7. Where a call under the terms of guarantee has been booked and the failure is not product related (i.e. scaling and furring, incorrect water pressure, pressure relief device operation or electrical/plumbing installation fault) a charge will be made. A charge will also be issued if nobody is at the property when the service engineer calls or adequate parking/permit is not available.
8. If the product is no longer covered by the guarantee an up-front fixed fee will be charged before the site visit.
9. Your receipt must be retained as proof of purchase. Should proof of purchase not be available on an `in-guarantee’ call, or should the service engineer find that the product is no longer under guarantee, the engineer will charge the same fixed price and will request payment prior to departing. If payment is not made on the day an administration charge will be added to the fixed charge.
10. If a debt is outstanding from a previous visit, or from any other Triton purchase, Triton reserves the right to withhold service until the debt has been settled.
11. Triton takes the health, safety and wellbeing of its employees very seriously and expects customers to treat all staff members with respect. Should any employee feel threatened or receive abuse, either verbally or physically, Triton reserves the right to withhold service.
Replacement Parts Policy
In line with AMDEA guidelines, Triton retains functional spares for as long as there is a market for them and in most cases, well beyond. Due to the vast array of product types, the life cycle of products can vary and therefore so can the length of time parts can be supplied. Spare parts can be ordered via our online spare parts store or by telephoning Triton Customer Experience team on 024 7637 2222. Payment should be made by credit / debit card (excluding American Express or Diners Card). Payment can also be made by pre-payment of a pro-forma invoice, by cheque or postal order.
Telephone orders are based on information given during the call. Before contacting Triton, please verify your requirements using the Triton website or your professional installer. Triton cannot accept liability for incorrect part identification.

TRITON UK STANDARD GUARANTEE
This guarantee applies only to products installed within the United Kingdom and does not apply to products used commercially. This guarantee does not affect your statutory rights.
With the exception of accessories, Triton guarantee the product against all manufacturing defects for a period of 2 years (for domestic use only) from the date of purchase, provided that it has been installed by a competent person in full accordance with the fitting instructions.
All accessories such as shower heads, hoses and riser rails carry a 1 year parts only guarantee against manufacturing defects.
Any part found to be defective during this guarantee period we undertake to repair or replace at our option without charge, so long as it has been properly maintained and operated in accordance with the operating instructions and has not been subject to misuse or damage. This product must not be taken apart, modified or repaired except by a person authorised by Triton.
What is not covered:
1. Breakdown due to: a) use other than domestic use by the property occupants; b) wilful act or neglect; c) any malfunction resulting from the incorrect use or quality of electricity, gas or water or incorrect setting of controls; d) failure to install in accordance with this installation guide.
2. Claims for missing parts once the product has been installed.
3. Repair costs for damage caused by foreign objects or substances.
4. Total loss of the product due to non-availability of parts.
5. Compensation for loss of use of the product or consequential loss of any kind.
6. Call out charges due to an abortive visit or where no fault has been found with the appliance.
7. The cost of repair or replacement of isolating switches, electrical cable, fuses and/or circuit breakers or any other accessories installed at the same time. Replacement of the Pressure Relief Device that only activates when the shower outlet is blocked is also excluded.
8. The cost of routine maintenance, adjustments, overhaul modifications or loss or damage arising therefrom, including the cost of repairing damage, breakdown, malfunction caused by corrosion, furring, frost or exposure to freezing conditions.
9. Callout charges where the water supply cannot be isolated, this includes consequential losses arising from unserviceable supply valves, or inaccessible product or valves located in a loft space without suitable access.
For the latest Terms & Conditions please see:
www.tritonshowers.co.uk/terms
PLEASE NOTE PRODUCT REGISTRATION IS ONLY AVAILABLE TO UNITS PURCHASED & INSTALLED IN THE UK

Triton Showers Triton Road Nuneaton Warwickshire, CV11 4NR
Triton is a division of Norcros Group (Holdings) Limited

Customer Experience: 024 7637 2222 Trade Installer Hotline: 024 7637 8344
www.tritonshowers.co.uk E-mail: serviceenquiries@tritonshowers.co.uk
E-mail: technical@tritonshowers.co.uk

Triton reserve the right to change product specification without prior notice. E&OE. © TRITON SHOWERS 2022

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals