TRITON AGIO Shower Electric Instruction Manual
- June 14, 2024
- TRITON
Table of Contents
AGIO Shower Electric
Product Information: AGIO Electric Shower
Specifications:
- Mains water pressure only
- Minimum inlet pressure: 100kPa (1 bar) for 10.5kW
- Maximum inlet pressure: 1000kPa (10 bar)
Important Safety Advice:
The shower unit MUST be switched off at the isolating switch
when not in use. This is a safety procedure recommended for all
electrical appliances.
The shower head and hose supplied with this product are a safety
critical part of your shower. Failure to use genuine Triton parts
may cause injury and invalidate your guarantee.
Installation and Operating Instructions:
Please read this book thoroughly and familiarize yourself with
all instructions before commencing installation and keep it for
future reference.
The shower installation MUST be carried out by a suitably
qualified person, following the sequence of this instruction
book.
General Guidance Notes:
-
Isolate the electrical and water supplies before removing the
cover. -
Read all of these instructions and retain them for later
use. -
DO NOT take risks with plumbing or electrical equipment.
-
Isolate electrical and water supplies before proceeding with
the installation. -
The unit must be mounted onto the finished wall surface (on top
of the tiles). DO NOT tile up to or seal around ANY PART of the
unit using silicone sealer after fixing to the wall. Special care
must be taken NOT TO BLOCK OR SEAL ANY PRD VENTS ON THE UNIT. -
Contact Customer Experience (see back page) if any of the
following occur:-
If it is intended to operate the shower at pressures above the
maximum or below the minimum stated. -
If the unit shows a distinct change in performance.
-
If the shower is frozen.
-
-
If it is intended to operate the shower in areas of hard water
(above 200 ppm temporary hardness), a scale inhibitor may have to
be fitted. For advice on the Scale Inhibitor, contact Customer
Experience. -
The shower head must be cleaned regularly with descaler to
remove scale and debris. Otherwise, restrictions to the flow on the
outlet of the unit will result in higher temperatures and could
also cause the Pressure Relief Device (PRD) in the unit to
operate. -
This product is not suitable for mounting into steam rooms or
steam cubicles.
Plumbing:
The plumbing installation must comply with Water Regulations,
Building Regulations, or any particular regulations as specified by
Local Water Company or Water Undertakers and should be in
accordance with BS EN 806.
FAQ:
Q: Can children use this shower?
A: Yes, this appliance can be used by children aged 3 years and
above and persons with reduced physical, sensory, or mental
capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning the use of the
appliance in a safe way and understand the hazards involved.
However, children should not play with the appliance, and cleaning
and user maintenance should not be made by children.
AGIO
electric shower
DRAW
FOR YOUR SERVICE REFERENCE
NOTE DOWN THE PRODUCT CODE BELOW
(FROM THE FRONT OR TOP OF THE BOX)
ALTERNATIVELY REGISTER BY TEL: 024 7637 8321
IMPORTANT SAFETY ADVICE
The shower unit MUST BE switched off at the isolating switch when not in use.
This is a safety procedure recommended for all electrical appliances.
The shower head and hose supplied with this product are a safety critical part
of your shower. Failure to use genuine Triton parts may cause injury and
invalidate your guarantee.
INSTALLATION AND OPERATING INSTRUCTIONS
Please read this book thoroughly and familiarise yourself with all
instructions before commencing installation and keep it for future reference.
The shower installation MUST be carried out by a suitably qualified person, in
the sequence of this instruction book.
2180843H – October 2022
INTRODUECleTcItOrNic – shPoLwEeArSE READ
PLEASE READ THIS IMPORTANT SAFETY INFORMATION
Products manufactured by Triton are safe and without risk provided they are
installed, used and maintained in good working order in accordance with our
instructions and recommendations. WARNING: DO NOT operate the appliance if
frozen, or suspected of being frozen. It must thaw out before using. DO NOT
operate the appliance if the shower head or spray hose becomes damaged. DO NOT
restrict flow out of the appliance by placing shower head in direct contact
with your body. DO NOT operate the appliance if water ceases to flow during
use or if water has entered inside the unit because of an incorrectly fitted
cover. WARNING: If restarting the appliance immediately after stopping, be
aware that a slug of hot water will be expelled for the first few seconds. The
shower head must be descaled regularly. Fit only shower heads recommended by
the manufacturer and never fit any additional device to restrict the water
outlet flow. The outlet must not be connected to any tap or fitting other than
those specified. This appliance is intended to be permanently connected to the
water mains and not connected by a hose set. A suitable double pole isolation
switch for supply disconnections must be incorporated in the fixed wiring
circuit in accordance with current wiring rules. See Electrical Installation
section for further details. The water inlet of this appliance shall not be
connected to inlet water obtained from any other water heating system.
Mains water pressure only. Minimum inlet pressure 100kPa (1 bar) 150kPa (1.5
bar) for 10.5kW Maximum inlet pressure 1000kPa (10 bar)
This book contains all the necessary fitting and operating instructions for
your electric shower. Care taken during the installation will provide a long,
trouble-free life from your shower.
WARNING
This appliance can be used by children aged from 3 years and
above and persons with reduced physical, sensory or mental capabilities or
lack of experience and knowledge if they have been given supervision or
instruction concerning use of the appliance in a safe way and understand the
hazards involved.
Children may not play with the appliance. Cleaning and user
maintenance shall not be made by children.
2
IMPORTANETle-ctrPiLcEAsShEowReEr AD THESE GENERAL GUIDANCE NOTES BEFORE PROCEEDING
1 GENERAL
1.1 Isolate the electrical and water supplies before removing the cover.
1.2 Read all of these instructions and retain them for later use.
1.3 DO NOT take risks with plumbing or electrical equipment.
1.4 Isolate electrical and water supplies before proceeding with the
installation.
1.5 The unit must be mounted onto the finished wall surface (on top of the
tiles). DO NOT tile up to or seal around ANY PART of the unit using silicone
sealer after fixing to the wall. Special care must be taken NOT TO BLOCK OR
SEAL ANY PRD VENTS ON THE UNIT.
1.6 Contact Customer Experience (see back page), if any of the following
occur:
a) If it is intended to operate the shower at pressures above the maximum or
below the minimum stated.
b) If the unit shows a distinct change in performance. c) If the shower is
frozen.
1.7 If it is intended to operate the shower in areas of hard water (above 200
ppm temporary hardness), a scale inhibitor may have to be fitted. For advice
on the Scale Inhibitor, contact Customer Experience.
1.8 The shower head must be cleaned regularly with descalent to remove scale
and debris, otherwise restrictions to the flow on the outlet of the unit will
result in higher temperatures and could also cause the (PRD) Pressure Relief
Device in the unit to operate.
1.9 This product is not suitable for mounting into steam rooms or steam
cubicles.
2 PLUMBING
2.1 The plumbing installation must comply with Water Regulations, Building
Regulations or any particular regulations as specified by Local Water Company
or Water Undertakers and should be in accordance with BS EN 806.
2.2 The supply pipe must be flushed to clear debris before connecting to the
shower unit.
2.3 DO NOT solder pipes or fittings within 300mm of the shower unit, as heat
can transfer along the pipework and damage components.
2.4 DO NOT fit any form of outlet flow control as the outlet acts as a vent
for the heater can.
2.5 DO NOT use excessive force when making connections to the flexible hose or
shower head, finger tight is sufficient.
2.6 All plumbing connections must be completed before making the electrical
connections.
2.7 This appliance MUST NOT be connected to the inlet supply by a hose-set.
3 ELECTRICAL
3.1 The installation must comply with BS 7671 Requirements for electrical installations’ (IEE wiring regulations), building regulations or any particular regulations as specified by the local Electrical Supply Company. 3.2 This appliance MUST be earthed. 3.3 In accordance with
The Plugs and
Sockets etc.
(Safety) Regulations 1994′, this appliance is intended to be permanently
connected to the fixed wiring of the electrical mains system. 3.4 Make sure
all electrical connections are tight to prevent overheating.
3.5 A 30mA residual current device (RCD) MUST be installed in all UK electric
and pumped shower circuits. This may be part of the consumer unit or a
separate unit.
3.6 Switch off immediately at isolating switch if water ceases to flow during
use.
3.7 Other electrical equipment i.e. extractor fans, pumps must not be
connected to the circuits within the unit.
3.8 Switch off at isolating switch when not in use. This is a safety procedure
recommended with all electrical appliances.
3.9 As with all electrical appliances it is recommended to have the shower and
installation checked at least every two years by a competent electrician to
ensure there is no deterioration due to age and usage.
3
Electric shower
INTRODUCTION
This book contains all the necessary fitting and operating instructions for
your electric shower. Please read them carefully.
The shower installation must be carried out by a suitably qualified person and
in the sequence of this instruction book.
Care taken during the installation will provide a long, trouble-free life from
your shower.
SPECIFICATIONS
Electrical Nominal power rating at 240V
8.5kW (40A MCB rating)
Nominal power rating at 230V
7.8kW (40A MCB rating)
Water
Inlet connection 15 mm diameter. Outlet connection ½” BSP male thread.
Entry Points Water Left: top, bottom back, bottom side.
Right: bottom side, bottom back, bottom.
Cable Left: top, bottom back, bottom side. Right: bottom side, bottom.
Materials Backplate, cover, controls, shower head ABS. Sprayplate Acetal.
Elements Minerally insulated corrosion resistant
metal sheathing.
Dimensions
Height 300 mm Width 208 mm Depth 110 mm
Standards and Approvals Waterproof rating IPX4.
Complies with the requirements of current British and European safety
standards for household and similar electrical appliances.
Complies with requirements of the British Electrotechnical Approvals Board
(BEAB).
Meets with Compliance with European Community Directives (CE) and UK Community Directives (UKCA).
ADVICE TO USERS
The following points will help you understand how the shower operates:
a. The electric heating elements operate at a constant rate at your chosen
power setting. It is the rate of the water passing through the heater unit
which determines the shower temperature at any given setting. The slower the
flow the hotter the water becomes and the faster the flow the cooler the
water.
b. During winter, mains water supply will be cooler than in summer. Therefore
the temperature of the shower will vary between seasons on any one setting of
the temperature control, e.g. if you have chosen setting number 6 as your
preferred shower temperature in the summer, you will have to increase that
number during winter by adjusting the temperature control clockwise (which in
effect slows the water flow).
c. The stabiliser valve minimises variations in shower temperature during
mains water pressure changes. If changes in shower temperature are experienced
during normal use, it will most likely be caused by the water pressure falling
near to or below the minimum level. The drop in pressure may be due to water
being drawn off at other points in the house whilst the shower is in use. If
pressure drops appreciably below the minimum, the heating elements will
automatically cut out.
If ever the water becomes too hot and you cannot obtain cooler water, first
check that the sprayplate in the shower head has not become blocked.
DO NOT place items such as soap or shampoo bottles on top of the unit. Liquid
could seep through the joint between the cover and backplate, and possibly
damage the sealing rubber.
4
Electric shower
CONTENTS
Page
INTRODUCTION IMPORTANT SAFETY INFORMATION & GENERAL GUIDANCE NOTES (please
read) SPECIFICATIONS GENERAL ADVICE TO USERS Main components
……………………………………………………………….. 6 Electrical requirements …………………………………………………………….
7 – 8 Water requirements……………………………………………………………… 9 Siting of the
shower……………………………………………………………. 10 Fitting the shower to the wall
……………………………………………..11 – 12 Plumbing connections ………………………………………………………… 13
Electrical connections …………………………………………………………. 14 Replacing the cover
……………………………………………………………. 15 Commissioning ………………………………………………………………… 16
Operating the shower………………………………………………………17 – 18 Operating functions
……………………………………………………………. 19 Instructions for installers and service engineers
only …………………………. 20
Water/Cable entry points diagram…………………………………………….. 20 Fault
finding………………………………………………………………..21 – 22 Spare parts
…………………………………………………………………….. 23 Guarantee, service policy, etc.
……………………………………………… rear cover
PRODUCT FICHE
Model
8.5kW
Load Profile
XS
Energy Efficiency Class
A
Energy Efficiency (%)
39
Annual Electricity Consumption (kwh)
482
Sound Power Level (db)
15
To check the product suitability for commercial and multiple installations,
please contact Triton’s specification advisory service before installation.
Telephone: 024 7637 2222 Email: technical@tritonshowers.co.uk
5
Electric shower
MAIN COMPONENTS
Fig.1
Inside unit (fig.1) 1. Power neon
11 13
13
12
2. Thermal safety cut-out – TCO 3. Power selector assembly
2
1
4. Can assembly
5. Stabilising valve
6. Solenoid valve
4
7. Outlet pipe 9
8. Pressure relief device (PRD)
9. Terminal block
3
255
mm
10
300 mm
5
10. Pressure switch assembly
11. Top cable/pipe entry 12. Wall screw fixings 13. Cover screw fixings 14. Earth connection 15. Water inlet (fig.2) 16. Cover assembly
6 14
12 15 7
58 mm
8 13
208 mm
NOTE: Not all wiring has been shown for reasons of clarity. T00311
Fig.2 16
6
Electric shower
ELECTRICAL REQUIREMENTS
WARNING! THIS APPLIANCE MUST BE EARTHED
The installation, supply cable and circuit protection must conform with BS
7671 (IEE wiring regulations) and be sufficient for the amperage required.
The following notes are for guidance only:
1 The shower must only be connected to a 230-240V ac supply. If you are
installing a shower with a kilowatt rating above 9kW, it is advisable to
contact the local electricity supply company.
1.1 The electrical rating of the shower is shown on the rating label (Fig.3)
within the unit.
2 Before making any sort of electrical connection within the installation,
make sure that no terminal is live. If in any doubt, switch off the whole
installation at the mains supply and remove the correct fuse.
3 The shower must be connected to its own independent electrical circuit. IT
MUST NOT be connected to a ring main, spur, socket outlet, lighting circuit or
cooker circuit.
3.1 The electrical supply must be adequate for the loading of the unit and
existing circuits.
4 Check your consumer unit (main fuse box) has a main switch rating of 80A or
above and that it has a spare fuse way which will take the fuse or Miniature
Circuit Breaker (MCB) necessary for the shower (Fig.4).
4.1 If your consumer unit has a rating below 80A or if there is no spare fuse
way, then the installation will not be straightforward and may require a new
consumer unit serving the house or just the shower.
4.2 You will need to contact the local electricity company. They will check
the supply and carry out what is necessary.
5 For close circuit protection DO NOT use a rewireable fuse. Instead use a
suitably rated Miniature Circuit Breaker (MCB) or cartridge fuse (see Table
A).
5.1 A 30mA residual current device (RCD) MUST be installed in all UK electric
and pumped shower circuits. This may be part of the consumer unit or a
separate unit.
Fig.3 – Illustrative purposes only
Triton Showers, Triton Road, Nuneaton, Warwickshire, CV11 4NR
xxxx
Fig.4 Schematic of installation circuit
Pull cord isolating switch
RCD
(can be part of consumer unit)
Shower unit
Fuse or MCB
Consumer unit Meter
80A or 100A main switch
Meter tails
Incoming supply fuse
Table A
CIRCUIT PROTECTION
unit rating
MCB
cartridge fuse
7.0kW
30/32A
30A
7.5kW
32A
35A
8.0kW
40A
35A
8.5kW
40A
45A
9.0kW
40A
45A
9.5kW
40/45A
45A
10.5kW
45A
45A
7
Electric shower
6 A 45 amp double pole isolating switch with a minimum contact gap of 3mm in both poles must be incorporated in the circuit.
6.1 It must have a mechanical indicator showing when the switch is in the OFF position, and the wiring must be connected to the switch without the use of a plug or socket outlet.
6.2 The switch must be accessible and clearly
able, but out of reach of a person
u
xed bath or shower, except for the
cord of a cord operated switch, and should
be placed so that it is not possible to touch
the switch body while standing in a bath or
shower cubicle. It should be readily accessible
to switch off after using the shower.
7 Where shower cubicles are located in any rooms other than bathrooms, all socket outlets in those rooms must be protected by a 30mA RCD.
8 The current carrying capacity of the cable must be at least that of the shower circuit protection (see Table B).
8.1 To obtain full advantage of the power provided by the shower, use the shortest cable route possible from the consumer unit to the shower.
8.2 It is also necessary to satisfy the disconnection time and thermal constraints which means that for any given combination of current demand, voltage drop and cable size, there is a maximum permissible circuit length.
9 The shower circuit should be separated from other circuits by at least twice the diameter of the cable or conduit.
9.1 The current rating will be reduced if the cabling is bunched with others, surrounded by thermal loft or wall insulation or placed in areas where the ambient temperature is above 30°C. Under these conditions, derating factors apply and it is necessary to select a larger cable size.
9.2 In the majority of installations (see Table B), the cable will unavoidably be placed in one or more of the above conditions. This being so, it is strongly recommended to use a minimum of 10mm cabling throughout the shower installation.
9.3 In any event, it is essential that individual site conditions are assessed
by a competent electrician in order to determine the correct cable size and
permissible circuit length.
Table B
Twin and earth PVC insulated cable Current carrying capacity
Installed in an insulated wall
In conduit trunking
Clipped direct or buried in a non-insulated
wall
6mm² 32A
10mm² 43A
16mm² 57A
6mm² 38A
10mm² 52A
16mm² 69A
6mm² 46A
10mm² 63A
16mm² 85A
Note: Cable selection is dependent on derating factors
*The method below may be used by installers to determine the approximate
size of the incoming cable.
6mm2
10mm2
16mm2
1. Measure the width of an individual strand, and half that measurment to
find (r), e.g: 1.34mm ÷ 2 = (r) 0.67mm
2. Multiply (r) x (r) x 3.14, e.g: (r) 0.67 x (r) 0.67 x 3.14 = 1.41mm2
3. Multiply this by the number of wire strands (usually 7), e.g: 1.41mm2 x 7
= 9.87mm2.
4. The number obtained would suggest 10mm2 wiring.
*PLEASE NOTE: If unsure, consult a qualified Electrician.
8
Electric shower
Mains electric supply (via double pole switch)
Isolating stopvalve
Double pole
isolating switch
Shower unit
Mains water supply
Separate permanently connected supply
from consumer unit
Fig.5 Diagrammatic view (not to scale)
WATER REQUIREMENTS
WARNING!
The shower must not be positioned where it will be subjected to freezing
conditions.
The installation must be in accordance with Water Regulations and Bylaws.
To guarantee activating the heating elements, the shower must be connected to
a mains water supply with a minimum running pressure of 100kPa (1.0 bar) at a
minimum flow rate of eight litres per minute for the 8.5kW rated model, and
nine litres per minute for the 9.5kW rated model.
For the 10.5kW rated shower, the minimum running pressure must be 150kPa (1.5
bar) at a minimum flow rate of eleven litres per minute.
For all models the maximum static pressure must not exceed 1000kPa (10 bar).
Note: If the stated flow rates are not available, it may not be possible to
achieve the best performance from the unit throughout the year.
During periods of high ambient temperatures it may be necessary to select a
low power setting to achieve your preferred shower temperature.
The water supply can be taken from a cold water storage cistern provided there
is a minimum head of ten metres above the shower head. It must be an
independent supply to the shower only.
If it is intended to operate the shower at pressures above the maximum or
below the minimum stated, contact Customer Service for advice.
Fig.5 shows a typical system layout.
DO NOT use jointing compounds on any pipe fittings for the installation.
9
Electric shower
SITING OF THE SHOWER
IMPORTANT: If installing onto a tiled wall always mount the unit on the
surface of the tiles. NEVER tile up to the unit.
Refer to fig.6 for correct siting of shower.
Position the unit where it will NOT be in direct contact with water from the
shower head. Position the shower unit vertically.
Leave enough room between the ceiling and the shower to allow access to the
cover top screws.
Note: Water Regulations require the shower head be `constrained by a fixed or
sliding attachment so that it can only discharge water at a point not less
than 25mm above the spill-over level of the relevant bath, shower tray or
other fixed appliance’. The use of the supplied retaining ring/gel hanger will
in most cases meet this requirement, but if the shower head can be placed
within a bath, basin or shower tray, then a double check valve, or similar,
must be fitted in the supply pipework to prevent back-flow.
Pressure relief safety device
A pressure relief device (PRD) is designed into the shower unit which complies
with European standards. The PRD provides a level of appliance protection
should an excessive build up of pressure occur within the shower.
DO NOT operate the shower with a damaged or kinked shower hose, or a blocked
shower head which can cause the PRD to operate.
When commissioning, the shower head must be removed from the flexible hose,
while at the same time the temperature control must be at the minimum flow
position. Failure to follow this procedure may also cause the PRD to operate.
Make sure the shower is positioned over a bath or shower tray because if the
PRD operates, then water will eject from the bottom of the unit.
Should this happen, turn off the electricity and water supplies to the shower
at the isolating switch and stopvalve. Contact Customer Service for advice on
replacing the PRD.
Shower unit can be mounted either
side of riser rail
Retaining ring
Height of shower head
and shower to suit user’s requirement
25 mm minimum
Outline of bath or shower tray
Shower unit must not be within an area 1 metre
from base
Fig.6 Diagrammatic view (not to scale)
10
Fig.7 Fig.8
20 mm
Electric shower FITTING THE SHOWER TO THE WALL
WARNING! Check there are no hidden cables or pipes before drilling holes for
wall
plugs. Use great care when using power tools near water. The use of
a residual current device (RCD) is recommended when using power tools.
Note: The control knobs are an integral part of the cover DO NOT attempt to
remove them.
Lift the cover from the backplate and remove the trimplate.
Entry positions for the mains water and electric cable are from the top,
bottom, either side or from the back.
Note: Deviations from the designated entry points will invalidate product
approvals.
If a bottom entry has been chosen, the pipe trim on the bottom of the cover
should be removed (fig.7).
If a top entry has been chosen, the pipe trim on the top of the backplate
should be removed (fig.8).
If a side entry is required, the trimplate side will have to be cut. With the
elbow compression fitted on the outlet, temporarily place the trimplate into
position, then mark the pipe entry on the side of the trimplate. Carefully
remove the appropriate area using a junior hacksaw.
Fig.9
Please note: NONE of the ‘cut outs’ are designed to ‘snap out’. DO NOT remove
using pliers as the backplate or lower trimplate could be damaged.
A junior hacksaw or suitable knife should be used and any rough edges removed.
Damage to the backplate or lower trimplate will invalidate product
specifications and warranty.
11
Electric shower
If installing a feed pipe from the back or bottom, the centre of the inlet
valve to the wall surface is 20mm (fig.9).
Note: If entry is from the back, the nut of the compression fitting will be
partially behind the surface of the wall. This area MUST be left clear when
plastering over the pipework in order to make the nut accessible for future
adjustments.
After choosing the site for the shower, use the backplate as a template and
mark the two fixing holes (fig.10).
Drill and plug the wall. An appropriate drill bit should be used. If the wall
is plasterboard or a soft building block, appropriate wall plugs should be
fitted.
Screw the top fixing screw into position leaving the base of the screw head
protruding 6mm out from the wall.
Hook the backplate over the bottom screw and fit the top fixing screw into
position.
DO NOT fully tighten the screws at this stage, as the fixing holes are
elongated to allow for out of square adjustment after the plumbing connections
have been completed.
Fig.10
12
Electric shower
WARNING!
The outlet of the shower acts as a vent and must not be connected to anything
other than the hose and
shower head supplied.
PLUMBING CONNECTIONS
Plumbing to be carried out before wiring DO NOT use jointing compounds on any
pipe fittings for the installation.
DO NOT solder fittings near the shower unit as heat can transfer along the
pipework and damage components.
Standard 15mm x 15mm brass compression fittings MUST be used to connect to the
inlet of the shower.
Note: An additional stopvalve (complying with Water Bylaws/Regulations) MUST
be fitted in the mains water supply to the shower as an independent means of
isolating the water in order to carry out maintenance or servicing. If this
isolator is fitted in a loft space, the loft must have a fixed access ladder
and be boarded, with appropriate lighting from the access point to the
isolator.
IMPORTANT: Before completing the connection of the water supply to the inlet
of the shower, and in compliance with Water Regulations, flush out the
pipework to remove all swarf and system debris. To do this, connect a hose to
the pipework and turn on the mains water supply long enough to clear the
debris to waste.
Procedure Turn off the water supply either at the mains stopvalve or the
isolating stopvalve. Connect the mains water supply to the inlet of the shower
via 15mm copper, stainless steel or plastic pipe using a 15mm x 15mm brass
compression fitting.
Note: The inlet fitting is designed to enter a compression fitting only. DO
NOT use push fit connectors as full engagement cannot be guaranteed. DO NOT
use excessive force when making these connections.
Make sure the backplate is square on the wall and tighten the two retaining
screws which hold it to the wall.
Turn on the mains water supply and check for leaks in the pipework connection
to the shower. IMPORTANT: Using a suitable sealant, always seal around the
incoming pipework to prevent water entering the wall.
Note: At this stage no water can flow through the unit.
13
Electric shower
ELECTRICAL CONNECTIONS
SWITCH OFF THE ELECTRICITY SUPPLY AT THE MAINS. Fig.11 shows a schematic
wiring diagram. The cable entry points are shown in fig.1. The cable can be
surface clipped, hidden or via 20mm conduit. Note: Conduit entry can only be
from rear. Route the cable into the shower unit and connect to the terminal
block (fig.12) as follows:
Earth cable to terminal marked E Neutral cable to terminal marked N Live cable
to terminal marked L
Fig.11
7 7
E L
N
1
2 8
4
5
IMPORTANT: Fully tighten the terminal block screws and make sure that no cable
insulation is trapped under the screws. Loose connections can result in cable
overheating.
Note: The supply cable earth conductor must be sleeved. The outer sheath of
the supply cable must be stripped back to the minimum.
The supply cable must be secured either by routing through conduit or in
trunking or by embedding in the wall, in accordance with current IEE
regulations.
The use of connections within the unit, or other points in the shower circuit,
to supply power to other equipment i.e. extractor fans, pumps etc. will
invalidate the guarantee.
DO NOT switch on the electricity supply until the cover has been fitted.
Note: The elements on UK models are to 240V specification and will give a
lower kW rating if the voltage supply is below 240V.
6
3
1. Terminal block 2. Thermal cut-out 3. Outlet 4. Microswitches 5. Start/stop microswitch
6. Solenoid valve 7. Elements 8. Neon
Fig.13
Terminal block
14
Fig.13
Selector spindle
Fig.14
Fig.15
Electric shower
REPLACING THE COVER
· Locate the trimplate into the backplate and secure with the two fixing
screws.
· The power selector spindle must be aligned as shown (fig.13).
· To make sure that the temperature control is correctly positioned on the
stabilising valve, temporarily place the cover in position so that the splines
engage and rotate the temperature control fully anti-clockwise.
· Remove the cover and position the temperature control knob so that it points
to the maximum flow position (fig.14).
· Position the power selector to the STOP
position (fig.15).
· Check to ensure that the wiring is not trapped and replace the cover
squarely to the backplate and guide into position so that the knobs locate
correctly into the splined spindles.
· Should any difficulty arise, recheck the points above.
· While applying slight pressure to the cover, secure in position with the
retaining screws.
WARNING COVER RETAINING SCREWS
ONLY the SUPPLIED SCREWS should be used. The use of non supplied screws WILL
invalidate product specifications & warranty.
15
Electric shower
COMMISSIONING
WARNING! Before normal operation of the shower, it is essential the following
commissioning
procedure is completed correctly.
The first operation of the shower is intended to flush out any remaining unit
debris and to make sure the heater unit contains water before the elements are
switched on. This operation must be carried out with the flexible hose screwed
to the outlet but without the shower head attached. Make sure the outlet of
the flexible hose is directed to waste. · Before turning on the electric and
mains
water supplies to the shower, make sure that the power selector is at the STOP
position (fig.16). · Select the minimum flow position (fig.17).
Note: Failure to turn the control to the minimum flow position may cause the
PRD to operate. · Turn on the mains water supply to the shower at the
isolating stopvalve and then turn on the electric supply to the shower at the
isolating switch. The power indicator will light. · Turn the power selector to
the COLD position (fig.18) and wait until water starts to flow from the
flexible hose. · Slowly rotate the temperature control fully anti-clockwise to
the maximum flow position (fig.19). It will take about thirty seconds for a
smooth flow of water to be obtained while air and any debris is flushed from
the shower. · When a smooth flow of water is obtained, rotate the temperature
control from minimum to maximum several times to release any trapped air
within the unit. · Once flushing out has been completed, stop the water flow
by turning the power selector to the STOP position. · Fit the shower head to
the flexible hose and place in the shower head holder.
The shower is now ready for normal operation.
16
Fig.16 Fig.17 Fig.18 Fig.19
Fig.20
Power selector
High Economy
Temperature control
00326
Electric shower
OPERATING THE SHOWER
WARNING!
Before normal operation of the shower, it is essential that the commissioning
procedure has been
completed correctly.
To start the shower
Turning the power selector to the red or blue
Cold
symbol positions will start water to flow.
To stop the shower
Switch the power selector to the STOP position and water will cease to flow.
WARNING!
If restarting immediately after stopping, be aware that a slug of hot water
will be
expelled for the first few seconds.
To use the power selector
The power selector has four positions – stop, cold, economy and high as shown
in fig.20. · Stop is to switch off the electric and water
supply at the shower – no flow or power used. · Blue symbol is for cold water
only. · Red single symbol is the economy setting
for using less power during warmer months. Temperature adjustment at this
setting is via the temperature control. · Red double symbol is the high
setting which allows the highest flow achievable for your preferred
temperature.
Adjustment of the temperature control on the COLD setting will only alter the
force of the water from the shower head. It will not alter the water
temperature.
Note: If the stated flow rate required for the unit cannot be met due to low
water pressure, it will be necessary to operate the unit on `economy’ setting
during the warmer months because of flow rate limitations entering the unit.
17
Electric shower
To adjust the shower temperature
Alter the water temperature by increasing or decreasing the flow rate of the
water through the shower via the temperature control (fig.21).
After obtaining your preferred showering temperature, the position can be
remembered and left as the normal setting and should only need to be altered
to compensate for seasonal changes in ambient water temperature. Note: The
preferred number on ECONOMY’ will give a different temperature to the same number position on
HIGH’.
To decrease the shower temperature
Turning the temperature control anti-clockwise (fig.21) will increase the flow
of water through the shower making it cooler.
To increase the shower temperature
Turning the temperature control clockwise (fig.22) will decrease the flow of
water through the shower making it warmer.
Note: It is advisable to be certain that the showering temperature is
satisfactory by testing with your hand before stepping under the shower head.
There will always be a time delay of a few seconds between selecting a flow
rate and the water reaching the stable temperature for that flow rate.
CAUTION: It is recommended that persons who may have difficulty understanding
or operating the shower controls should not be left unattended while
showering. Special consideration should be given to young children and the
less able bodied.
Fig.21 Fig.22
18
Electric shower
Fig.23 Power on indicator
327
Note: In normal use, it is in order to leave the water supply permanently on
to the shower unit, but as with most electrical appliances, the unit must be
switched off at the isolating switch when not in use.
OPERATING FUNCTIONS
Power on indicator (fig.23)
When the electricity supply to the shower is switched on at the isolating
switch, the POWER indicator will light.
Note: Should the safety cut-out device operate, the indicator will remain lit.
Low water pressure cut-out
If the water pressure falls below the minimum required for correct operation
of the shower, power will be switched off to the heating elements preventing
any maintained temperature rises (water will continue to flow). Power will
automatically be restored when adequate water pressure returns. TP
Temperature Protection
During normal operation if the temperature exceeds the showering safety limit
the power to the elements will be removed completely, although water will
continue to flow. When the temperature has cooled sufficiently, power to the
elements will be automatically restored to the settings at the time of
interruption.
Safety cut-out
The unit is fitted with a non-resettable thermal cut-out safety device. In the
event of abnormal operation which could cause unsafe temperatures within the
unit, the device will disconnect the heating elements. It will require a visit
from a qualified engineer to determine the nature of the fault and replace the
safety device once the unit has been repaired.
WARNING – CLEANING
Triton recommends that all products are cleaned using warm, soapy water.
Do not use abrasive or aggressive chemical cleaning products as this may
affect the product surface finish and
invalidate your guarantee.
19
Electric shower
INSTRUCTIONS FOR INSTALLERS AND SERVICE ENGINEERS ONLY
CLEANING THE INLET FILTER
It is recommended that the filter is periodically cleaned in order to maintain
the performance of the shower. It is essential that this operation is carried
out by a competent person.
IMPORTANT: Before servicing, switch off the electricity supply at the mains.
Switch off the water supply at the lsolator valve.
Remove the cover. The inlet filter is situated in the inlet pipe, which is
part of the solenoid valve (fig.24).
To access the filter, remove the trimplate then disconnect and remove the
compression fitting.
Also, depending on the incoming pipework arrangements, if there is not enough
slack in the pipework, it could mean the removing the unit from the wall.
When cleaning the filter, DO NOT use a sharp object as it will cause damage.
It is preferable to use an old toothbrush or similar.
Note: Full commissioning procedure will need to be performed after cleaning of
the filter (see page 16 for information on commissioning procedure).
Fig.24
Filter
ENTRY POINTS
Diagram Key:
Water Entry Points Cable Entry Points
20
Electric shower
FAULT FINDING
IMPORTANT: Switch OFF the electricity at the mains supply and remove the
circuit fuse before attempting any fault finding inside the unit.
Problem
Cause
Action
1 Shower inoperable, no water flow.
1.1 Interrupted power supply.
1.1.1 Blown fuse or circuit breaker. Check supply. Renew or reset fuse or circuit breaker. If it fails again, consult a qualified electrician.
2 Water too hot.
1.2 Unit malfunction.
2.1 Not enough water flowing through the shower.
1.2 Power cut. Check other appliances and if necessary, contact local
Electricity Supply Co.
1.2.1 Have unit checked. Contact Customer Experience.
2.1.1 Increase flow rate via temperature control. 2.1.2 Blocked shower head —
clean or replace
blocked sprayplate in shower head.
2.2 Blockage in supply.
2.2.1 Check if stop valves are fully open. Check if a blockage in the inlet filter.
2.3 Increase in ambient water temperature.
2.3.1 Readjust flow rate to give increased flow. 2.3.2 Select ECONOMY power.
3 Water temperature cycling hot/cool at intervals.
3.1 Heater cycling on temperature limiter.
3.1.1 See Water too hot causes 2.1, 2.2 and 2.3 and their appropriate action/cures. If it continues contact Customer Experience.
4 Water too cool or cold.
4.1 Too much flow.
4.1.1 Reduce flow rate via temperature control. 4.2.1 Is water supply mains or tank fed?
4.2 Water pressure below minimum required (see rating label).
4.2.2 If tank fed, replumb to mains water supply or see 4.2.4.
4.2.3 If mains fed, make sure that mains stopvalve is fully open and that
there are no other restrictions in the supply while shower is in use, or see
4.2.4.
4.2.4 Fit pump to give minimum pressure (see rating label). Contact Customer
Experience for advice.
4.3 Reduction in ambient 4.3.1 Readjust flow rate to give reduced flow. water temperature. 4.3.2 Select HIGH power.
21
Electric shower
FAULT FINDING
Problem/Symptom Cause
Action/Cure
4 Water too cool or cold. (continued)
4.4 Electrical malfunction.
4.4.1 Have unit checked by suitably qualified electrician or contact Triton Customer Experience.
4.5 Safety cut-out operated.
4.5.1 Thermal safety cut-out device has operated. Have the unit checked by a suitably qualified engineer or contact Customer Experience.
5 Shower varies from normal temperature to cold during use.
5.1 Water pressure has dropped below minimum required.
5.1.1 Wait until the water pressure resumes to normal.
6 Pressure relief device has operated (water ejected from PRD tube).
6.1 Blocked shower head. 6.1.1 Clean or replace blocked sprayplate in shower head and then fit new PRD.
6.2 Twisted/blocked flexible shower hose.
6.2.1 Check for free passage through hose. Replace the hose if necessary and fit new PRD.
6.3 Shower head not removed while commissioning.
6.3.1 Fit new PRD. Commission unit with shower head removed.
7 Shower fails to shut off.
7.1 Faulty power selector. 7.1.1 Replace power selector.
7.2 Debris in the solenoid.
7.2.1 Replace solenoid valve.
Note: Identify the cause of operation before fitting a new PRD unit. When
fitting a new PRD, follow the commissioning procedure.
It is advised all electrical maintenance/repairs to the shower should be
carried out by a suitably qualified person.
In the unlikely event of unit failure other than detailed in the fault finding
page, please contact Customer Experience for advice.
22
Electric shower
To purchase a genuine Triton spare part for your product, please visit
www.tritonshowers.co.uk/spares
for product codes and prices. Alternatively please call our Customer
Experience team on 024 7637 2222 to order direct. Please have your model name
available.
WEEE Directive Policy Statement
As a producer and a supplier of electric showers, Triton Showers is committed
to the protection of the environment via our own environmental policy and
compliance with the WEEE directive. Triton Showers is fully registered with
the Environment Agency under the following schemes:
Repic: Producer Takeback Scheme (PTS) registration number WEE/EJ3466QV Valpak:
Distributer Takeback Scheme (DTS) registration number DTS-501317-1 All our
electric products are labelled accordingly with the crossed out wheeled bin
symbol. This indicates, for disposal purposes at end of life, that these
products must be taken to recognised collection points, such as local
authority sites/local recycling centres; this will be free of any charges. Do
not return to Triton Showers.
23
UK SERVICE POLICY
In the event of a product fault or complaint occurring, the following
procedure should be followed:
DO NOT REMOVE THE PRODUCT
1. Telephone Customer Experience on 024 7637 2222 having available your
details including post code, the model number and power rating of the product,
together with the date of purchase and, where applicable, details of the
particular fault.
2. If required, the Customer Experience Advisor will arrange for a qualified
engineer to call.
3. All products attended to by a Triton service engineer must be installed in
full accordance with the Triton installation guide applicable to the product.
Every product pack contains an installation guide, however, they can also be
downloaded free at www.tritonshowers.co.uk.
4. Our engineer will require local parking and if a permit is required, this
must be available to the engineer on arrival at the call.
5. If loft access is required for isolation or to complete a repair, the loft
must have a fixed access ladder and be boarded, with appropriate lighting from
the access point to and around the repair area.
6. It is essential that you or an appointed representative, who must be over
18 years of age, is present for the duration of the service engineer’s visit.
If the product is in guarantee you must produce proof of purchase.
7. Where a call under the terms of guarantee has been booked and the failure
is not product related (i.e. scaling and furring, incorrect water pressure,
pressure relief device operation or electrical/plumbing installation fault) a
charge will be made. A charge will also be issued if nobody is at the property
when the service engineer calls or adequate parking/permit is not available.
8. If the product is no longer covered by the guarantee an up-front fixed fee
will be charged before the site visit.
9. Your receipt must be retained as proof of purchase. Should proof of
purchase not be available on an `in-guarantee’ call, or should the service
engineer find that the product is no longer under guarantee, the engineer will
charge the same fixed price and will request payment prior to departing. If
payment is not made on the day an administration charge will be added to the
fixed charge.
10. If a debt is outstanding from a previous visit, or from any other Triton
purchase, Triton reserves the right to withhold service until the debt has
been settled.
11. Triton takes the health, safety and wellbeing of its employees very
seriously and expects customers to treat all staff members with respect.
Should any employee feel threatened or receive abuse, either verbally or
physically, Triton reserves the right to withhold service.
Replacement Parts Policy
In line with AMDEA guidelines, Triton retains functional spares for as long as
there is a market for them and in most cases, well beyond. Due to the vast
array of product types, the life cycle of products can vary and therefore so
can the length of time parts can be supplied. Spare parts can be ordered via
our online spare parts store or by telephoning Triton Customer Experience team
on 024 7637 2222. Payment should be made by credit / debit card (excluding
American Express or Diners Card). Payment can also be made by pre-payment of a
pro-forma invoice, by cheque or postal order.
Telephone orders are based on information given during the call. Before
contacting Triton, please verify your requirements using the Triton website or
your professional installer. Triton cannot accept liability for incorrect part
identification.
TRITON UK STANDARD GUARANTEE
This guarantee applies only to products installed within the United Kingdom
and does not apply to products used commercially. This guarantee does not
affect your statutory rights.
With the exception of accessories, Triton guarantee the product against all
manufacturing defects for a period of 2 years (for domestic use only) from the
date of purchase, provided that it has been installed by a competent person in
full accordance with the fitting instructions.
All accessories such as shower heads, hoses and riser rails carry a 1 year
parts only guarantee against manufacturing defects.
Any part found to be defective during this guarantee period we undertake to
repair or replace at our option without charge, so long as it has been
properly maintained and operated in accordance with the operating instructions
and has not been subject to misuse or damage. This product must not be taken
apart, modified or repaired except by a person authorised by Triton.
What is not covered:
1. Breakdown due to: a) use other than domestic use by the property
occupants; b) wilful act or neglect; c) any malfunction resulting from the
incorrect use or quality of electricity, gas or water or incorrect setting of
controls; d) failure to install in accordance with this installation guide.
2. Claims for missing parts once the product has been installed.
3. Repair costs for damage caused by foreign objects or substances.
4. Total loss of the product due to non-availability of parts.
5. Compensation for loss of use of the product or consequential loss of any
kind.
6. Call out charges due to an abortive visit or where no fault has been found
with the appliance.
7. The cost of repair or replacement of isolating switches, electrical cable,
fuses and/or circuit breakers or any other accessories installed at the same
time. Replacement of the Pressure Relief Device that only activates when the
shower outlet is blocked is also excluded.
8. The cost of routine maintenance, adjustments, overhaul modifications or
loss or damage arising therefrom, including the cost of repairing damage,
breakdown, malfunction caused by corrosion, furring, frost or exposure to
freezing conditions.
9. Callout charges where the water supply cannot be isolated, this includes
consequential losses arising from unserviceable supply valves, or inaccessible
product or valves located in a loft space without suitable access.
For the latest Terms & Conditions please see:
www.tritonshowers.co.uk/terms
PLEASE NOTE PRODUCT REGISTRATION IS ONLY AVAILABLE TO UNITS PURCHASED &
INSTALLED IN THE UK
Triton Showers Triton Road Nuneaton Warwickshire, CV11 4NR
Triton is a division of Norcros Group (Holdings) Limited
Customer Experience: 024 7637 2222 Trade Installer Hotline: 024 7637 8344
www.tritonshowers.co.uk E-mail: serviceenquiries@tritonshowers.co.uk
E-mail: technical@tritonshowers.co.uk
Triton reserve the right to change product specification without prior notice. E&OE. © TRITON SHOWERS 2022
References
- Triton Showers | Bathroom Showers, Accessories & Spare Parts
- Triton Showers | Bathroom Showers, Accessories & Spare Parts
- Shower Spares | Shower Replacement Parts | Triton Showers
- Terms and Conditions
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>