SDC MD-31DB Motion Sensor Instruction Manual
- June 4, 2024
- SDC
Table of Contents
SDC MD-31DB Motion Sensor
Description
The SDC MD-31DB is a Request-To-Exit Passive Infared (PIR) sensor. Mounted near an exterior door inside a building with an access control system, the sensor provides free exit to individuals within the building without causing an alarm.
Mounting Location
NOTE: If the maximum range of 8.4ft. (2.6M) is desired, the mounting height must be at the maximum 15ft (4.57M).
Choosing a mounting location:
- Give the sensor a clear line-of-sight to every part of the detection area. Infraed energy cannot penetrate solid objects; if the PIR cannot detect movement, the sensor will not activate.
- Do not place sensor directly across from one or more windows.
- Is away from moving machinery, fluorescent lights and heating and cooling sources.
The mounting locations available for a request-to-exit sensor can be fairly limited. You may find that it is impossible to avoid a source of false detection within the sensors detection pattern. In that case, block the sensor’s view of that portion of the pattern by adjusting the shutters as described in section 7.
Mounting Procedure
To mount the sensor, do the following:
- Open the sensor housing by pressing on the latch with a screwdriver. This latch is located on the end of the sensor nearest the lens. Pull the cover up and away from the sensor’s base.
- Loosen rotation locking screw 2 turns (do not remove). Then, remove PCB assembly from the back plate of the sensor.
- Insert the wiring into one of the wire channels on the sensor’s back plate.
- Securely affix the sensor’s back plate to the wall or ceiling using 2 #6 x 3/4” (3.5 x 19mm) screws.
- Reinstall the PCB assembly and adjust for short or long range as described in Section 6. Then, tighten rotation locking screw.
Input/Output Description
The MD-31DB inputs and outputs are as follows:
V+ / V -: Connects to AC or DC power (12 to 28 volts).
Relays: Input/outputs for the unit’s dual single pole/double throw relay.
The relay may be used to control a magnetic lock or signal an access control
system. All relay connections (common, normally closed and normally open) for
both sets of contacts are available on the terminal block.
NOTE: Relay timer settings and the reset mode setting affect operation of
this relay (see switches 3, 4, 5 and 6 in DIP Switch Settings).
CAUTION: When using the MD-31DB to control a magnetic lock, we recommend
that an electric suppressor be used to provide transient protection for the
magnetic lock and relay contacts. Install the suppressor across the leads
connected to the lock as close as possible to the lock.
Any suggestions or comments to this instruction or product are welcome. Please contact us through our website or email engineer@sdcsecurity.com
MD-31DB Wiring
Wire the sensor as shown in the illustration
Long Range/Short Range Adjustments
The MD-31DB can be set to detect individuals at either a long range (several
steps from the door) or at a short range (immediately in front of the door).
If the building includes a lengthy approach to the exit doorway and no other
foot traffic in the area, choose the long range setting.
NOTE: If the maximum range of 8.4ft (2.6M) is desired, the mounting
height must be at the maximum 15ft (4.57M).
Choose between long and short range detection patterns
To set the range length:
-
Loosen the rotating locking screw.
-
Turn the PCB in it’s rotating base until the arrow on the base is aligned with the appropriate notch on the baseplate. If the sensor is ceiling mounted, choose between the notches with the “Ceiling” label. If the sensor is wall mounted, choose between the notches with the “Wall” label. The arrow on the mounting base (or back plate) needs to be aligned with the ceiling or wall arrows. The “L” designates long range and the “S” designates short range.
NOTE: Either long or short range must be selected. Attempting to use a “mid” range will result in undesirable operation. A mid range setting will not result in a mid range operation. It will only provide a long range with attenuated short range detection. -
Tighten the rotation locking screw.
Shutter Adjustment
The MD-31DB contains shutters behind the PIR cover. These shutters are used to adjust the field width. This may be necessary when the unit is installed where it may be tripped by non-exiting foot traffic or other erroneous sources at either or both edges of the detection area.
- To adjust the shutters, remove the lens cover from the PIR.
- Push the forward edge of the shutter(s) toward the middle of the opening until the area(s) to be blocked are outside the line-of-sight of the PIR. When making shutter adjustment, each shutter position has a detent and each detent masks off an entire detection zone. There are eight detection zones total and each shutter has the ability to mask off 7 of the eight zones. If the shutter is located between detents, the result will be an attenuation of a zone that is intended to be masked or attenuation of a detection zone resulting in improper operation.
- Replace the lens cover.
DIP Switch Settings
The MD-31DB DIP switch contains 6 switches for selecting operating options. The functions of these switches are as follows:
- Switch 1 – Sensor Mode (Sensitivity) Selector: OFF is the Request-to-Exit mode. ON is the Security Sensor mode. In the security sensor mode, the sensor is more immune to false alarms, but the extra time required to perform signal qualifications may make the unit unsuitable for most RTE applications. The unit is shipped in the Request-to-Exit mode.
- Switch 2 – LED Disable: This switch must be off to allow the LED to function. The unit is shipped with the LED enabled (switch OFF).
- Switch 3 – Relay Timer Mode: This switch selects the relay timer re-trigger or fixed modes.
With this switch OFF, the re-trigger mode is selected. In the re-trigger mode, the relay timer is restarted with the time programmed (switches 4, 5 & 6) whenever motion is detected. The relay will only deactivate when the time programmed expires without additional motion detected during the active period. With this switch ON, the fixed mode is selected and the relay will deactivate at the expiration of the relay time programmed (switches 4, 5 & 6) and additional motion detection during the active period has no effect. The unit is shipped with this switch OFF (re-trigger mode).
Switches 4, 5 & 6 – Relay Timer Settings: These switches Control the relay timing: To set the relay timing, refer to the following table:
Switch | Relay Time (Seconds) |
---|---|
4 | 5 |
OFF | OFF |
OFF | OFF |
OFF | ON |
OFF | ON |
ON | OFF |
ON | OFF |
ON | ON |
ON | ON |
Walk Testing
Walk into the motion detection field. Two to four normal steps into the field
should make the LED light.
NOTE: The MD-31DB has a warm up period of approximately 2 minutes.
Each time the LED goes on, wait for it to go off. Then wait 12 seconds before
continuing the walk-test. When there is no motion in the detection field, the
LED should be off.
IMPORTANT: The MD-31DB should be tested at least once a year.
Specifications
Range:
- Long:
- 8.4′ x 15.8′ (Adjustable)
- 2.6M x 4.8M (Adjustable)
- Short:
- 2′ x 5.5′ (Adjustable)
- 0.5M x 1.7M (Adjustable)
Relay (Dual): Form C
- Contact rating:
- 1A max. @
- 30VDC max
RFI Immunity:
- 30 V/m, 1 MHz – 1000MHz
White Light Immunity:
- 2000 Lux
Power Requirements:
12 to 28 VDC or VAC 3V peak-to-peak @ 12.5V <50mA current consumption
Operating Temperature:
- 32° to 122° F (0° to 50° C)
Size:
- 7″ x 2″ x 2″
- 17.8cm x 5.1cm x 5.1cm
Relative Humidity:
- <95% non-condensing
Part Numbers:
- MD-31DB = Black Housing
Regulatory Notices
The MD-31DB fully complies with the following regulations:
- FCC Part 15
- UL 294 – Access Control System Units, File BP6704
- C22.2 No. 205-M1983 – Signal Equipment
- CE
INSTALLATION INST\EXIT BARS KEY_EXITSWITCHES\INST-MD-31DB.vsd SECURITY DOOR
CONTROLS
WWW.SDCSECURITY.COM
[t] 800.413.8783
805.494.0622
E-mail: service@sdcsecurity.com
801 Avenida Acaso, Camarillo, CA 93012
PO Box 3670, Camarillo, CA 93011
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>