BEA 75.5390.03 Active Infrared Safety Sensor Instruction Manual
- June 13, 2024
- BEA
Table of Contents
- BEA 75.5390.03 Active Infrared Safety Sensor
- Product Information
- Product Usage Instructions
- DESCRIPTION
- TECHNICAL SPECIFICATIONS
- INSTALLATION
- ADDITIONAL DIP SWITCH ADJUSTMENTS
- TROUBLESHOOTING
- BEA, INC. INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BEA 75.5390.03 Active Infrared Safety Sensor
Product Information
The Smart Focus is an active infrared safety sensor designed for automatic doors. It features a range of components including LED, emitter, DIP switch, push button, setup adjustment screw, mounting screw, receiver, cable with connector, and face. The sensor is capable of detecting presence through distance measurement and has a response time of 64 ms. It operates on a supply voltage of 24 VAC or 24 VDC and has a maximum current consumption of 120mA (AC) or 80mA (DC). The sensor provides standard outputs through a relay with a maximum contact voltage of 42 VAC/VDC and a maximum contact current of 1A (resistive). It also includes a monitoring input with a maximum contact voltage of 30V and voltage thresholds for high state (>10V) and low state (<1V). The sensor has a hold time of 0.5s and requires a minimum reflectivity of 10% at an IR wavelength of 850nm. It is housed in an ABS material casing with an IP53 degree of protection and has dimensions of 5 3/4″ (L) x 1 3/5″ (H) x 2″ (D). The main cable length is 8′ and it conforms to relevant norms.
Product Usage Instructions
- Using the mounting template, cut an opening in the desired location for the sensor.
- Once inserted, secure the sensor in place using the provided mounting screws.
- Loosen the mounting screws and manually adjust the sensor angle as required. Ensure to tighten the screws after adjustment.
- Connect the cables according to the provided diagram and insert the sensor into the opening created in step 1.
- Remove the face of the sensor by inserting a screwdriver as shown.
- Press the push button to initiate an automatic setup. The LED will flash red/green.
- Once the LED stops flashing, the sensor is set up. Secure the face back in place and test for proper operation.
- If the LED continues to flash, refer to the next page for further adjustment instructions.
Additional Dip Switch Adjustments:
- DIP 1: Automatic Mode – Verify that the adjustment screw is positioned correctly and press the push button for automatic setup.
- DIP 2: Uncovered Zone – In manual mode, use the adjustment screw to increase or decrease the uncovered zone. Check the adjustment by moving a white paper vertically under the sensor.
- DIP 3: Frequency – Choose between Frequency 1 and Frequency 2. Relaunch a setup after changing DIP 3.
- DIP 4: Monitoring – Select between Active High or Active Low. Confirm DIP changes with a long push of the push button when finished.
Visit the website for available languages of this document.
DESCRIPTION
- LED
- emitter
- DIP switch
- push button
- setup adjustment screw
- mounting screw
- receiver
- cable with connector
- face
TECHNICAL SPECIFICATIONS
Technology | active infrared |
---|---|
Detection mode | presence detection by distance measurement |
Detection field | 1 2⁄5” × 2 3⁄4” (at 7’ mounting height) |
Response time | 64 ms |
Mounting height | 2 – 10’ |
Supply voltage | 12 – 24 VAC/VDC -5% / +10% |
Mains frequency | 50 – 60 Hz |
Max. current consumption | 120mA @ 24 VAC / 80mA @ 24 VDC |
Standard output:
max. contact voltage max. contact current max. switching power
| relay (free of potential contact) 42 VAC/VDC
1A (resistive)
30W (DC) / 42 VA (AC)
Monitoring input:
max. contact voltage voltage threshold
| 1 optocoupler (free of potential contact) 30 V
high state: > 10 V low state: < 1 V
Hold time| 0.5 s
Reflectivity| min. 10% at IR-wavelength of 850nm
Temperature range| -13 – 131 °F (-25 – 55 °C)
0 – 95% rel. humidity, non-condensing
Degree of protection| IP53
Dimensions| 5 3/4” (L) x 1 3/5” (H) x 2” (D)
Housing material| ABS (black)
Cable length (main cable)| 8’
Norm conformity| IEC 61000-6-2; IEC 61000-6-3; ISO 13849-1
Performance Level «c» CAT. 2
(under the condition that the door control system monitors the sensor at least once per door cycle)
Specifications are subject to change without prior notice. All values are measured in specific conditions.
INSTALLATION
- Avoid reflective backgrounds or objects in the detection field of the sensor.
- Avoid high-intensity lighting in the detection field.
- Do not cover the sensor.
- Do not touch the optical parts.
- Using the mounting template, cut an opening in the desired location for the sensor.
- Loosen the mounting screws and manually adjust the sensor angle. Be sure tighten the screws when finished.
- Connect the cables and insert the sensor in the opening from step 1.
- Once inserted, secure the 2 mounting screws.
- Wire the sensor according to the diagram.
- Remove the face by inserting a screwdriver as shown.
- Press the push button to launch an automatic setup. The LED will flash red/green.
- When the LED is no longer flashing, the sensor is set up. Now secure the face and test for proper operation.
- If the LED continues to flash, the sensor must be adjusted (see next page).
- The sensor can also be installed on the surface by using the surface mount accessory (sold separately).
ADDITIONAL DIP SWITCH ADJUSTMENTS
TROUBLESHOOTING
| The RED LED is ON sporadically or permanently.| Bad calibration.| Launch a
calibration.
---|---|---|---
| Bad adjustment of the uncovered zone.| Check if the DIP 4 is in correct
position. Launch a calibration.
| The sensor is disturbed by external light sources or another sensor.|
Select a different frequency for each module (DIP 2).
Launch a calibration.
| The sensor does not react, but a calibration can be launched.| The monitoring is activated, but the monitoring input is not powered.| Check wiring.
• Door control with monitoring : Connect purple and purple/yellow wires to monitoring output of door
control.
• Door control without monitoring : Set DIP switch 4 to OFF.
| The monitoring mode is incorrect.| Change position of DIP 4.
| The ORANGE LED is on permanently.| The sensor encounters a memory problem.|
Replace sensor.
| The ORANGE LED flashes quickly.| DIP switch setting awaiting confirmation.|
Confirm the DIP switch setting with a long push on the push button.
| The ORANGE LED flashes 1x every 3 seconds.| The sensor signals an internal fault.| Cycle power supply.
If the orange LED flashes again, replace the sensor.
| The ORANGE LED flashes 2x every 3 seconds.| The power supply is out of spec range (12 – 24 VAC/VDC -5% / +10%).| Check the power supply.
Reduce the cable length or change the cable.
| The ORANGE LED flashes 4x every 3 seconds.| The sensor does not receive enough IR energy.| Launch a new calibration. Step out of the detection field. Change the angle of spots.
Switch off the background (DIP 1: ON).
| The ORANGE LED flashes 5x every 3 seconds.| Calibration error.| Check mounting height.
Change position of setup adjustment screw.
Launch a new calibration.
Switch off the background (DIP 1: ON).
BEA, INC. INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
- BEA, Inc., the sensor manufacturer, cannot be held responsible for incorrect installations or incorrect adjustments of the sensor/device; therefore, BEA, Inc. does not guarantee any use of the sensor/device outside of its intended purpose.
- BEA, Inc. strongly recommends that installation and service technicians be AAADM-certified for pedestrian doors, IDA-certified for doors/gates, and factory-trained for the type of door/gate system.
- Installers and service personnel are responsible for executing a risk assessment following each installation/service performed, ensuring that the sensor/device system performance is compliant with local, national, and international regulations, codes, and standards.
- Once installation or service work is complete, a safety inspection of the door/gate shall be performed per the door/gate manufacturer’s recommendations and/or per ADM/ANSI/DASMA guidelines (where applicable) for best industry practices. Safety inspections must be performed during each service call – examples of these safety inspections can be found on an ADM safety information label (e.g. ANSI/DASMA 102, ANSI/DASMA 107, UL294, UL325, and International Building Code).
- Verify that all appropriate industry signage, warning labels, and placards are in place.
Tech Support & Customer Service:
1-800-523-2462
General Tech Questions : techservices-us@BEAsensors.com | Tech Docs:
www.BEAsensors.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>