BEA 10STRIKEREV34 Rim-Exit Electric Strike Instruction Manual
- June 4, 2024
- BEA
Table of Contents
- BEA 10STRIKEREV34 Rim-Exit Electric Strike
- TECHNICAL SPECIFICATIONS
- UL294 & UL1034 REQUIREMENTS
- GENERAL SAFETY
- MOUNTING & WIRING
- Connection Diagram
- Fail-safe / Fail-secure Reversible
- BEA, INC. INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BEA 10STRIKEREV34 Rim-Exit Electric Strike
Visit website for available languages of this document.
TECHNICAL SPECIFICATIONS
UL294 & UL1034 REQUIREMENTS
- ‰ Indoor use only.
- ‰ Wiring methods shall be in accordance with NFPA70.
- 10STRIKEREV is intended to be used with UL-listed, rim type, fire exit hardware, Von Duprin LLC, Model 99-F.
- 10STRIKEREV shall not installed in the fail-secure mode unless permitted by the local Authority Having Jurisdiction (AHJ), and shall not impair panic hardware operation.
- Remove the “Listed Fire Rated Hardware” label if the 10STRIKEREV is used in the fail-safe operation. Using these strikes in fail-safe operation negates the fire rating. 10STRIKEREV is fire rated in fail-secure operation only.
- 10STRIKEREV are access control unit accessories intended to be controlled by an access control system. The purpose of access control systems is to provide a means for controlling lock and unlocking external and internal doors of a premise.
GENERAL SAFETY
- ‰ Shut off all power going to electrical encolsure before attempting any wiring procedures.
- ‰ Maintain a clean and safe environment when working in public areas.
- Constantly be aware of pedestrian traffic around the door area.
- Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected reactions by the door.
- ESD (electrostatic discharge): Circuit boards are vulnerable to damage by electrostatic discharge. Before handling any board, ensure you dissipate your body’s ESD charge.
- Always check placement of all wiring before powering up to ensure that moving door parts will not catch any wires and cause damage to equipment.
- Ensure compliance with all applicable safety standards (i.e. ANSI A156.31) upon completion of installation.
- DO NOT attempt any internal repair of the components. All repairs and/or component replacements must be performed by BEA, Inc. Unauthorized disassembly or repair:
- May jeopardize personal safety and may expose one to the risk of electrical shock.
- May adversely affect the safe and reliable performance of the product resulting in a voided warranty.
MOUNTING & WIRING
Steps 1 – 3 only need to be performed if there was NOT an existing exit device at the installation site.
- Measure 39 13⁄16” (1011mm) from the finished floor and mark strike centerline on the door. Transfer centerline to frame.
- Align the strike on the centerline and mark two slotted holes. Drill holes and secure strike to frame.
- Align template on centerline and against strike.
- Measure the exit device latch position on the door.
- Close the door and mark the latch position on the frame. The latch position line will correspond with the inside of the strike keeper as shown.
- Position the strike on the frame according to the marks. Using the strike as a template, mark and drill a cable access hole and two mounting holes. Loosely mount the strike with Phillips flathead screws.
- Check latchbolt interaction and adjust the strike horizontally until the door latches properly, then tighten the two mounting screws and mark remaining screw holes.
- Remove the strike and drill marked holes. Wire accordingly. Insert the blind nuts into the holes and re-install the strike. If necessary, add spacers to adjust the gap between the strike and exit device. Secure the strike with the hex-socket, cap screws into the blind nuts.
Connection Diagram
12 VDC operation
24 VDC operation
Fail-safe / Fail-secure Reversible
Remove locking screw, loosen, slide and tighten sliding screw. Reinsert and tighten locking screw to the desired fail-safe or fail-secure setting.
BEA, INC. INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
- BEA, Inc., the sensor manufacturer, cannot be held responsible for incorrect installations or incorrect adjustments of the sensor/device; therefore, BEA, Inc. does not guarantee any use of the sensor/device outside of its intended purpose.
- BEA, Inc. strongly recommends that installation and service technicians be AAADM-certified for pedestrian doors, IDA-certified for doors/gates, and factory-trained for the type of door/gate system.
- Installers and service personnel are responsible for executing a risk assessment following each installation/service performed, ensuring that the sensor/device system performance is compliant with local, national, and international regulations, codes, and standards.
- Once installation or service work is complete, a safety inspection of the door/gate shall be performed per the door/gate manufacturer’s recommendations and/or per AAADM/ANSI/DASMA guidelines (where applicable) for best industry practices.
- Safety inspections must be performed during each service call – examples of these safety inspections can be found on an AAADM safety information label (e.g. ANSI/DASMA 102, ANSI/DASMA 107, UL294, UL325, and International Building Code).
- Verify that all appropriate industry signage, warning labels, and placards are in place.
Tech Support & Customer Service:
1-800-523-2462
General Tech Questions:
techservices-us@BEAsensors.com
Tech Docs:
www.BEAsensors.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>