HILTI KB1 Wedge Anchor Instruction Manual
- June 8, 2024
- HILTI
Table of Contents
HILTI KB1 Wedge Anchor
OPERATOR INSTRUCTIONS
Symbol| Setting Information| Units| ⅜| ½| ⅝|
¾
---|---|---|---|---|---|---
HDB| Hollow Drill Bit| –| –| ✔| ✔| ✔
DRS
| Dust Removal Systems| –| ✔| ✔| ✔| ✔
AT-System
| Adaptive Torque System**| –| ✔| ✔| ✔| –
d0| Drill Bit Diameter| [inch]| ⅜| ½| ⅝| ¾
hef| Effective Embedment Depth| [inch]| 1½| 2| 2| 3¼| 2¾| 4| 3¼| 4¾
hnom| Nominal Embedment Depth| [inch]| 1⅞| 2⅜| 2⅜| 3⅝| 3¼| 4½| 4| 5½
h0| Minimum Hole Depth in Base Material| [inch]| 2⅛| 2¾| 2¾| 4¼| 3¾| 4¾| 4¼|
5¾
Tinst, concrete| Installation Torque Concrete| [ft-lb]| 20| 40| 60| 110
Tinst, grout filled CMU| Installation Torque Grout-Filled CMU| [ft-lb]| 15|
25| 35| 50
dh| Fixture Hole Diameter| [inch]| 7⁄16| 9⁄16| 11⁄16| 13⁄16
WS| Wrench Size| [inch]| 9⁄16| ¾| 15⁄16| 1⅛
- For steps 1a or 1b, make sure to drill deep enough to achieve h0, taking into account the depth of debris remaining in the hole.
** AT-System not applicable for grout-filled CMU and wood fastening applications.
For UL Listing, the ⅝” anchor is rated up to 10 NPS at a minimum of 3-¼” nominal embedment.