MEAN-WELL HDR-100 Series 85 100 Ultra Slim Step Shape W DIN Rail Owner’s Manual

June 13, 2024
MEAN WELL

85 ~ 100W Ultra Slim Step Shape DIN Rail
HDR-100 series

MEAN WELL HDR 100 Series 85 100 Ultra Slim Step Shape W DIN Rail - icon
1 MEAN WELL
HDR 100 Series 85 100 Ultra Slim Step Shape W DIN Rail - icon
2

MEAN WELL HDR 100 Series 85 100 Ultra Slim Step Shape W DIN Rail -
qr

https://www.meanwell.com/Upload/PDF/HDR%20DIN%20rail%20power%20supply.pdf

Features

  • Ultra slim design with 70mm(4SU) width
  • Universal input 85~264VAC(277VAC operational)
  • No load power consumption<0.3W
  • Isolation class
  • Pass LPS (Limited power source) for Blank type
  • DC output voltage adjustable
  • Protections : Short circuit / Overload / Over voltage
  • Cooling by free air convection (working temperature:-30~+70°C)
  • DIN rail TS-35/7.5 or 15 mountable
  • LED indicator for power on
  • 3 years warranty

Applications

  • Household control system
  • Building automation
  • Industrial control system
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

HDR-100 is one economical ultra slim 100W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 70mm(4SU) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC(277VAC operational) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. HDR-100 is designed with plastic housing that it can effectively prevent user from electric hazards. With working efficiency up to 90%, the entire series can operate at the ambient temperature between -30 and 70 under air convection. The complete protection functions and relevant certificates for home automations and industrial control apparatus (IEC62368-1,UL508, UL62368-1, BS EN/EN61558-2-16)make HDR-100 a very competitive power supply solution for household and industrial applications.

Model Encoding

MEAN WELL HDR 100 Series 85 100 Ultra Slim Step Shape W DIN Rail - Model
Encoding

Type Description Note
Blank 92W max, Pass LPS with a narrower output adjustable range In stock
N 100W max, Non-LPS with a wider output adjustable range In stock

SPECIFICATION

MODEL| HDR-100-12| HDR-100-12N| HDR-100-15| HDR-100.15N| HDR•100-24| HDR-100•24N| HDR-100-48| HDR-100-48N
---|---|---|---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 12V| 15V| 24V| 48V
RATED CURRENT| 7.1A| 7.5A| 6.13A| 6.5A| 3.83A| 4.2A| 1.92A| 2.1A
CURRENT RANGE| 0 – 7.1A| 0 – 7.5A| 0 – 6.13A| 0 – 6.5A| 0 – 3.83A| 0 – 4.2A| 0 -1.92A| 0 – 2.1A
RATED POWER| 85.2W| 90W| 92W| 97.5W| 92W| 100.8W| 92.2W| 100.8W
RIPPLE & NOISE (max.) Mole/| 120mVfrp| 120mVp-p| 150mVp-p| 240mVp-p
VOLTAGE ADJ. RANGE| Pass LPS| 12 – 13V| 15 – 17V| 24 – 25.W| 48 – 48W
Non LPS| 12- 13.8V| 13.5 -18V| 21.6 – 29V| 43.2 – 55.2V
VOLTAGE TOLERANCE Note.3| -±2.0%| ±1.0%| ±1.0%| ±1.0%
UNE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 60ms/230VAC 500ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)| 30ms/230VAC 12ms.1115VAC at full load
INPUT| VOLTAGE RANGE| 85 – 264VAC (277VAC operational ) 120 – 370VDC (390VDC operational )
FREQUENCY RANGE| 47 – 63Hz
EFFICIENCY (Typ.)| 88%| 189%| I90%| 190%
AC CURRENT (Typ.)| 3A1115VAC 1.6A230VAC
INRUSH CURRENT (Typ.)| COLD START 35A1115VAC 70A230VAC
PROTECTION| OVERLOAD| HDR-100 :102 -110% rated output power : HDR-100-xxN :105 – 150% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed
Constant current limiting within 50% -100% rated output voltage, recovers automatically after fault condition is removed
OVER VOLTAGE| 14.2 – 16.2V| 116.8 – 22.5V| I 30 – 36V| I 56.5 – Ray
Protection type : Shut down ofp voltage, re-power on to recover
ENVIRONMENT| WORKING TEMP.| -30 – +70°C (Refer to “Derating Curve’)
WORKING HUMIDITY| 20 – 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 – +85°C , 10 – 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/t (0 – 50t ) RH non-condensing
VIBRATION| 10 – 500Hz, 2G 10minJ1cycle. period for 60min each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters
OVER VOLTAGE CATEGORY| In ; According to EN61558, EN50178,EN60664-1, EN62477-1 ; altitude up to 2000 meters
SAFETY & EMC
(Note 5)| SAFETY STANDARDS| UL623613-1, UL508, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, IEC62368-1, EAC TP IC 004, BSMI CNS14336-1 approved; Design refer to TUV BS EN/EN62368-1
---|---|---
WITHSTAND VOLTAGE| I/P-01P:4KVAC
ISOLATION RESISTANCE| UP-011,:100M Ohms! 500VDC/25°C/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level! Note
Conducted| BS ENIEN55032(CISPR32), CNS13438| Class B
Radiated| BS EN/EN55032(CISPR32), CNS13438| Class B
Harmonic Current (Note 5)| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| —
EMC IMMUNITY| BS EN/EN55035, BS EN/EN61000 6-2. BS EN/EN61204-3
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3. 81W air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN!EN61000-4-3| Level 3, cdteria A
EFTIBurest| BS EN/EN61000-4-4| Level 3, criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, criteria A
Voltage Dips and interruptions| BS ENIEN61000-4-11| >95% dip 0. 5 periods, 30% dip 25 periods. >95% interruptions 250 periods
OTHERS| MTBF| 3271.9K hrs min. Tetcordia SR-332 (Bellcore) ; 856.5K hrs min. MIL-HDBK-217F (25t)
DIMENSION| 70’90’54.5mm (IVWD)
PACKING| 0.27Kg; 48pcs113.74Kg/0.96CUFT
NOTE| 1.All parameters NOT special y mentioned are measured at 230VAC input, rated load and 25t of ambient temperature.
2.Pia & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair- wire terminated with a 0.14 & 474 parallel capacitor.
3.Tolerance : includes set up tolerance, ine regulation and load regulation.
4.Harmonic current test at 90% bad for HDR-100-)ocN.
5.The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to park= these EMC tests, please refer to “EMI testing of component power suppies.”
(as available on http://www.meanwell.com)
6.The ambient temperature derating of 3.5C/1000m with fanless models and of 5t /1000m with fan models for operating altitude higher than 2000m(6500fI).
• Product Liability Disclaimer : For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

MEAN WELL HDR 100 Series 85 100 Ultra Slim Step Shape W DIN Rail - Block
Diagram 1

Derating Curve VS Ambient Temperature

MEAN WELL HDR 100 Series 85 100 Ultra Slim Step Shape W DIN Rail - Block
Diagram 2

Output Derating VS Input Voltage

MEAN WELL HDR 100 Series 85 100 Ultra Slim Step Shape W DIN Rail - Block
Diagram 3

Mechanical Specification

MEAN WELL HDR 100 Series 85 100 Ultra Slim Step Shape W DIN Rail -
Mechanical Specification 1 MEAN WELL HDR 100 Series 85 100 Ultra Slim Step Shape W
DIN Rail - Mechanical Specification 2

ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15

Terminal Pin No. Assignment

Pin No. Assignment Pin No. Assignment
1 AC/L 3,4 -V
2 AC/N 5,6 +V

Installation Manual

Please refer to : http://www.meanwell.com/manual.html

Downloaded from Arrow.com.
File Name:HDR- 0-SPEC 2023-04-14