TRANE A4AC4042D Central Air Conditioner and Gas Furnace Split System Instruction Manual

June 13, 2024
Trane

A4AC4042D Central Air Conditioner and Gas Furnace Split System

Submittal

Split System Air Conditioner

A4AC4042D1000A

Note: “Graphics in this document are for representation
only. Actual model may differ in appearance.”

AM-PRQ-A4AC4042D-1B-EN

Outline Drawing

Outline Drawing

Model

|

Base

|

A

|

B

|

C

|

D

---|---|---|---|---|---

A4AC4042D

|

4.4

|

930 (36–5/8)

|

870 (34–1/4)

|

19 (3/4)

|

43 (1–3/4)

SOUND POWER LEVEL


Model

|

A-Weighted Sound Power Level [dB(A)]

|

Full Octave Sound Power [dB]

63 Hz*

|

125 Hz

|

250 Hz

|

500 Hz

|

1000 Hz

|

2000 Hz

|

4000 Hz

|

8000 Hz

A4AC4042D

|

71

|

78

|

72

|

69

|

68

|

66

|

61

|

58

|

53

Note: Rated in accordance with AHRI Standard 270–2008 *For reference only.

2 AM-PRQ-A4AC4042D-1B-EN

Product Specifications

OUTDOOR UNIT (a) (b)

|

A4AC4042D1000A

---|---

POWER CONNS. — V/PH/HZ (c)

|

208/230/1/60

MIN. CIR. AMPACITY

|

20

MAX. OVERCURRENT PROTECTION

|

35

COMPRESSOR

|

SCROLL

NO. USED — NO. STAGES

|

1 — 1

VOLTS/PH/HZ

|

208/230/1/60

R.L. AMPS (d) — L.R. AMPS

|

15.4 — 92.1

FACTORY INSTALLED

|

YES/NO

START COMPONENTS (e)

|

NO (Uses BAYKSKT263)

INSULATION/SOUND BLANKET

|

NO

COMPRESSOR HEAT

|

NO

OUTDOOR FAN

|

PROPELLER

DIA. (IN.) — NO. USED

|

27.5

TYPE DRIVE — NO. SPEEDS

|

DIRECT — 1

CFM @ 0.0 IN. W.G. (f)

|

4513

NO. MOTORS — HP

|

1 — 1/5

MOTOR SPEED R.P.M.

|

850

VOLTS/PH/HZ

|

208/230/1/60

F.L. AMPS

|

1.05

OUTDOOR COIL — TYPE

|

All Aluminum

ROWS — F.P.I.

|

1 — 24

FACE AREA (SQ. FT.)

|

24.93

TUBE SIZE (IN.)

|

3/8

REFRIGERANT

|

LBS. — R-410A (O.D. UNIT) (g)

|

6 LBS., 6 OZ

FACTORY SUPPLIED

|

YES

LINE SIZE — IN. O.D. GAS (h) (i)

|

7/8

LINE SIZE — IN. O.D. LIQ.

|

3/8

CHARGING SPECIFICATIONS

|

SUBCOOLING

|

10°F

DIMENSIONS

|

H X W X D

CRATED (IN.)

|

39.7 x 35.5 x 35.5

WEIGHT

|

SHIPPING (LBS.)

|

246

NET (LBS.)

|

212

(a) Certified in accordance with the Air-Source Unitary Air-conditioner Equipment certification program, which is based on AHRI standard 210/240.

(b) Rated in accordance with AHRI standard 270.

(c) Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or fuses.

(d) This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selection current.

(e) No means no start components. Yes means quick start kit components. Optional authorized kits include KIT07689 for RunTru or BAYKSKT267.

(f) Standard Air — Dry Coil — Outdoor

(g) This value approximate. For more precise value see unit nameplate. (h) Reference the outdoor unit ship-with literature for refrigerant piping length and lift guidelines. Reference the refrigerant piping software pub # 32-3312-xx or refrigerant piping application guide SS APG006-xx for long line sets or specialty applications (xx denotes latest revision).

(i) The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, ten (10) feet of tested connecting line, and the smallest rated indoor evaporative coil match. Always verify proper system charge via subcooling (TXV/EEV) or superheat (fixed orifice) per the unit nameplate.

Mechanical Specification Options

General
The outdoor condensing units are factory charged with
the system charge required for the outdoor condensing
unit, ten (10) feet of tested connecting line, and the
smallest rated indoor evaporative coil match. This unit
is designed to operate at outdoor ambient
temperatures as high as 115°F. Cooling capacities are
matched with a wide selection of air handlers and
furnace coils that are AHRI certified. The unit is certified
to UL 1995. Exterior is designed for outdoor
application.

Casing
Unit casing is constructed of heavy gauge, galvanized
steel and painted with a weather-resistant powder
paint finish. The corner panels are prepainted. All
panels are subjected to our 1,000 hour salt spray test .

Refrigerant Controls
Refrigeration system controls include condenser fan,
compressor contactor and low and high pressure
switches.

Compressor
The compressor features internal over temperature and
pressure protection. Other features include: Centrifugal
oil pump and low vibration and noise.

Condenser Coil
The outdoor coil provides low airflow resistance and
efficient heat transfer. The coil is protected on all four
sides by louvered panels.

Low Ambient Cooling
As manufactured, this system has a cooling capacity to
55°F. The addition of an evaporator defrost control
permits operation to 40°F. The addition of an
evaporator defrost control with TXV permits low
ambient cooling to 30°F.

The addition of the BAYLOAM108 low ambient kit
permits ambient cooling to 20°F.

Thermostats— Cooling only and heat/cooling (manual
and automatic change over). Sub-base to match
thermostat and locking thermostat cover.

About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For
more information, please visit www.trane.com or www.americanstandardair.com.

The AHRI Certified mark indicates company participation in the AHRI Certification program. For verification of individual certified products, go to ahridirectory.org.

The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to
using environmentally conscious print practices.

AM-PRQ-A4AC4042D-1B-EN 22 Jul 2022
Supersedes AM-PRQ-A4AC4042D-1A-EN (March 2022)

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Trane User Manuals

Related Manuals