TRANE A4AH4E60B1C30A RunTru Central Air Conditioner Split System Owner’s Manual

June 13, 2024
Trane

TRANE logo Submittal
5.0 Ton
Convertible Air Handler
A4AH4E60B1C30A
September 2022
AA44AAHH44EE6600BB11CC-
-SSUUBB–11AA–EENN

Outline Drawing

TRANE A4AH4E60B1C30A RunTru Central Air Conditioner Split System -
Drawing

PRODUCT DIMENSIONS

Air Handler Model| A| B| C| D| E| F| H| Flow Control| Gas Line Braze
A4AH4E60B1C30A| 57.40| 23.50| 21.50| 21.75| 4.68| 9.66| 27.19| TXV| 7/8
All dimensions are in inches

Product Specifications

MODEL A4AH4E60B1C30A
RATED VOLTS/PH/HZ 208-230/1/60
RATINGS (a) See O.D. Specifications
INDOOR COIL — Type Plate Fin
Rows — F.P.I. 3 – 16
Face Area (sq. ft.) 7.9
Tube Size (in.) 3/8
Refrigerant Control TXV
Drain Conn. Size (in.)(b) 3/4 NPT
DUCT CONNECTIONS See Outline Drawing
INDOOR FAN — Type Centrifugal
Diameter-Width (In.) 11 X 11
No. Used 1
Drive – No. Speeds Direct – 5 (c)
CFM vs. in. w.g. See Fan Performance Table
No. Motors — H.P. 1 – 3/4
Motor Speed R.P.M. 1050
Volts/Ph/Hz 208-230/1/60
F.L. Amps 6.0
--- ---
FILTER
Filter Furnished? (d) No
REFRIGERANT R-410A
Ref. Line Connections Brazed
Coupling or Conn. Size — in. Gas 7/8
Coupling or Conn. Size — in. Liq. ****

3/8

DIMENSIONS| H x W x D
Crated (In.)| 57–1/8 x 27–1/2 x 25–1/2
Uncrated| 55-3/4 x 23-1/2 x 21-1/8
WEIGHT|
Shipping (Lbs.) / Net (Lbs.)| 185/174

(a) These Air Handlers are A.H.R.I certified with various Split System Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.
(b) 3/4” Male Plastic Pipe (Ref: ASTM 1785–76)
(c) ECM Motor
(d) Remote filter required.

Minimum Airflow CFM

A4AH4E60B1C30A

Heater| Minimum Heat Speed Tap
| With Heat Pump| Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG, BAYHTR1505BRK, BAYHTR1505LUG, BAYHTR1508BRK, BAYHTR1508LUG, BAYHTR1510BRK, BAYHTR1510LUG, BAYHTR3510LUG| Med-Low| Med-Low
BAYHTR1517BRK, BAYHTR3517LUG| Med| Med
BAYHTR1523BRK, BAYHTR1525BRK| Med-High| Med

Heater Pressure Drop Table


Airflow CFM

| Number of Racks| | Heater Racks
---|---|---|---
1| 2| 3| 4| Heater Model| No. of Racks
Air Pressure Drop — Inches W.G.| BAYHTR1504| 1
1800| 0.02| 0.04| 0.06| 0.14| BAYHTR1505| 1
1700| 0.02| 0.04| 0.06| 0.14| BAYHTR1508| 2
1600| 0.02| 0.04| 0.06| 0.13| BAYHTR1510| 2
1500| 0.02| 0.04| 0.06| 0.12| BAYHTR1517| 3
1400| 0.02| 0.04| 0.06| 0.12| BAYHTR3510| 3
1300| 0.02| 0.04| 0.05| 0.11| BAYHTR3517| 3
1200| 0.01| 0.04| 0.05| 0.10| BAYHTR3515| 3
1100| 0.01| 0.03| 0.05| 0.09| BAYHTR1523| 4
1000| 0.01| 0.03| 0.04| 0.09| BAYHTR1525| 4
900| 0.01| 0.03| 0.04| 0.08| |
800| 0.01| 0.03| | | |
700| 0.01| 0.02| | | |
600| 0.01| 0.02| | | |

Performance and Electrical Data

  1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
  2. Heater model numbers may have additional suffix digits.

Table 1. Air Flow Performance

A4AH4E60B1C30A

EXTERNAL STATIC

(in w.g)

| AIRFLOW
Speed Taps: 208 – 230 VOLTS
| High| Med-High| Med †| Med-Low| Low
0.1| 2040| 1874| 1658| 1512| 1373
0.2| 2008| 1846| 1622| 1476| 1333
0.3| 1975| 1816| 1585| 1438| 1289
0.4| 1942| 1785| 1546| 1395| 1240
0.5| 1909| 1751| 1506| 1349| 1187
0.6| 1875| 1716| 1463| 1300| 1129
0.7| 1841| 1678| 1418| 1246| 1067
1.      Values are with wet coil, no filter, and no heaters
2.      CFM Correction for dry coil = Add 3%
3.      † = Factory Setting
4.      In downflow applications, airflow must not exceed 1800 cfm due to condensate blowoff.
5.      Low = Tap 1, Med-Low = Tap 2, Med = Tap 3, Med-High= Tap 4, High = Tap 5

Table 2. Electrical Data

A4AH4E60B1C30A

**** Heater Model No.| **** No. of Circuits/ Phases| 240 Volt| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload Protec- tion| Capacity|

Heater Amps per Circuit

| Mini- mum Circuit Ampaci- ty| ****

Maximum Overload Protection


kW

| ****

BTUH

| ****

kW

| ****

BTUH

No Heater| | | | 6.0 | 8| 15| | | 6.0 | 8| 15
BAYHTR1504BRK BAYHTR1504LUG| 1/1| 3.8| 13100| 16.0| 28| 30| 2.9| 9800| 13.8| 25| 25
BAYHTR1505BRK BAYHTR1505LUG| 1/1| 4.8| 16400| 20.0| 33| 35| 3.6| 12300| 17.3| 29| 30
BAYHTR1508BRK BAYHTR1508LUG| 1/1| 7.7| 26200| 32.0| 48| 50| 5.8| 19700| 27.7| 42| 45
BAYHTR1510BRK BAYHTR1510LUG| 1/1| 9.6| 32800| 40.0| 58| 60| 7.2| 24600| 34.6| 51| 60
BAYHTR1517BRK-
Circuit 1 (a)| ****


2/1

| 9.6| 32800| 40.0| 58| 60| 7.2| 24600| 34.6| 51| 60
BAYHTR1517BRK-
Circuit 2| 4.8| 16400| 20.0| 25| 25| 3.6| 12300| 17.3| 22| 25
BAYHTR1523BRK-
Circuit 1| ****


2/1

| 9.6| 32800| 40.0| 58| 60| 7.2| 24600| 34.6| 51| 60
BAYHTR1523BRK-
Circuit 2| 9.6| 32800| 40.0| 50| 50| 7.2| 24600| 34.6| 43| 45
A4AH4E60B1C30A

BAYHTR1525BRK-

Circuit 1

| ****




4/1

| 6.0| 20500| 25.0| 39| 40| 4.5| 15400| 21.6| 35| 35
BAYHTR1525BRK-

Circuit 2

| 6.0| 20500| 25.0| 31| 35| 4.5| 15400| 21.6| 27| 30
BAYHTR1525BRK-

Circuit 3

| 6.0| 20500| 25.0| 31| 35| 4.5| 15400| 21.6| 27| 30
BAYHTR1525BRK-

Circuit 4

| 6.0| 20500| 25.0| 31| 35| 4.5| 15400| 21.6| 27| 30
BAYHTR3510LUG| 1/3| 9.6| 32800| 23.1| 36| 40| 7.2| 24600| 20.0| 32| 35
BAYHTR3517LUG| 1/3| 14.4| 49100| 34.6| 50| 50| 10.8| 36900| 30.0| 44| 45
BAYHTR1517BRK

with single circuit power source kit BAYSPEKT201A

| 1/1| 14.4| 49100| 60.0| 83| 90| 10.8| 36900| 51.9| 73| 80
BAYHTR1523BRK

with single circuit power source kit BAYSPEKT201A

| 1/1| 19.2| 65500| 80.0| 108| 110| 14.4| 49100| 69.2| 94| 100

  • = Motor Amps

(a)  MCA and MOP for circuit 1 contains the motor amps.

Features and Benefits

  • Galvanized metal cabinet with captured foil face insulation
  • 2% or less air leakage
  • R-4.2 Insulating Value
  • Multi-Position UP/Down Flow, Horizontal Left /Right
  • ALL Aluminum Coil
  • Electric Heaters with polarized plug connections (sold as accessory)
  • R-410A Thermal Expansion Valve
  • ECM Motor (( 33..00 –– 55 TToonn MMooddeellss ))
  • Low Voltage Pigtail Connections
  • Draw Through Design
  • Horizontal Drain pan
  • Single Color
  • Fused 24V Power
  • 5year warranty
  • Optional extended warranty available

Important :Condensate management kit is required for all 5 ton air handler models installed in downflow applications.

About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com.

The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

A4AH4E60B1C-SUB-1A-EN 06 Sep 2022
Supersedes (New)

References

Read User Manual Online (PDF format)