BANNER BWA-9O2-C Area Monitoring Gateway with Cloud ID User Guide
- June 13, 2024
- BANNER
Table of Contents
Area Monitoring Gateway with Cloud ID Quick
Start Guide
Quick Start Guide Introduction
The Area Monitoring Gateway with Cloud ID™ from Banner Engineering provides
real-time insights about the operation and performance of the assets in your
facility. The gateway features a user-friendly, no-code setup and the ability
to automatically recognize an array of compatible sensors using the embedded
Cloud ID™ intelligence.
This Quick Start Guide describes the necessary steps to apply power, bind
sensors to the radio network of the gateway, and activate the gateway on your
Banner Cloud Data Services software account.
For a detailed description of the following steps, please scan this code to
consult the complete Area Monitoring Gateway with Cloud ID™ System Manual (pn
222401) or watch the tutorial videos on the product series page at
www.bannerengineering.com/AreaCloudID.
https://info.bannerengineering.com/cs/groups/public/documents/literature/222401.pdf
Configuration Instructions
Unpack and Supply Power to All Devices
-
Install the antenna.
a. Securely fasten the ISM radio antenna (BWA-902-C or BWA-202-C) to the Gateway’s SMA connection port R.
b. If you intend to use cellular communication, securely fasten the cellular antenna (BWA-CELLA-002) to the Gateway’s SMA connection port L. If you are not using cellular communication, leave this port capped with the protective cover. -
Apply power to the Area Monitoring Gateway:
a. Connect the power supply to the Gateway using the corresponding connection port.
b. Insert the wall plug of the power supply into a power outlet using the appropriate plug adapter for your region. -
Apply power to the compatible sensor Nodes:
a. For battery-powered devices, access the Node’s battery compartment or holder by unfastening the cover and installing the appropriate battery size and voltage using the proper orientation as indicated in the device’s datasheet.
b. For AC-powered devices, verify the device has been correctly wired and then connect to an appropriate power source as indicated in the device’s datasheet.
c. Keep the Node covers unfastened until after completing the binding process.
Bind the Sensor Nodes to the Wireless Network Banner offers an array of compatible Sensor Nodes that can measure vibration, differential pressure, temperature and humidity, tank level, and other data signals that are critical to monitor within an operation. Please visit the series page for the Area Monitoring Gateway with Cloud IDTM on our website to view the list of compatible nodes or consult the complete Area Monitoring Gateway with Cloud 10TM Kit System Manual (pn 222401).
-
On the Gateway: Enter binding mode:
a. Use the arrow keys to select the ISM Radio menu on the LCD and press ENTER.
b. Highlight the Binding menu and press ENTER. -
Use the arrow keys to select the Node ID address you intend to assign to the Sensor Node. You may only use Node IDs 1-40 with the Asset Monitoring Gateway. You must assign a unique Node ID for each Sensor Node in your network.
-
Press ENTER. The Gateway’s display indicates the device is in binding mode. 4. On the Sensor Node: Enter binding mode:
◦ For one-button Nodes, triple-click the button.
◦ For two-button Nodes, triple-click button 2.
The LEDs flash alternately and the Node searches for a Gateway in binding mode. After the Node binds, the LEDs stay solid momentarily, then they flash together four times. The Node automatically exits binding mode and reboots. -
On the Gateway: Press BACK to exit binding mode for that specific Node address. The Node LEDs continue to flash red until the Gateway exits binding mode with that Node address. The LED flashes green after the Node and Gateway have synced and are communicating properly. This may take a few moments. Please note: Some Node models also illuminate an amber LED after the device syncs with the Gateway. This indicates the Node is in fast-sampling mode. The Node automatically exits fast-sampling mode after 15 minutes, otherwise you can manually exit fast-sampling mode by clicking the button five times. Fast-sampling mode does not affect the sampling rate of a Cloud ID “A system and may be disregarded.
-
Repeat steps 2-5 for as many Sensor Nodes as are needed for your network. 7. On the Gateway: When you are finished binding, press BACK until you return to the main menu.
Connect to the Local Area Network
By default, the Area Monitoring Gateways are intended to push data to the Banner Cloud Data Services (BannerCDS) platform using a local area network. A specialized Ethernet cable is included with the Gateway to complete this connection.
- Connect the Ethernet cable to the corresponding port on the Gateway.
- Insert the RJ45 connector into a port on the local area network.
- Configure the Ethernet communication parameters, if necessary. By default, the Gateway is configured to communicate to a local network using the Dynamic Host Configuration Protocol (DHCP) setting and to act as a client on the network. This setting may work for most applications and no further configuration is needed. Contact your IT professional to ensure the device is not blocked from the local network. In some applications, your IT professional may prefer to attribute a Static IP Address to the Gateway. This may be done using the LCD menu on the Gateway. To set up a static IP address, follow these steps:
a. To set a static IP address: On the Gateway, use the arrows to highlight the System Config menu, then press ENTER.
b. Use the arrow keys to select the Ethernet menu, then press ENTER.
c. Highlight the DHCP selection, then press ENTER.
d. Set DHCP to OFF.
e. When the system requests a restart, press ENTER to confirm.
f. Navigate back to the Ethernet menu.
g. Use the arrow keys to select IP. then press ENTER. The octet of the IP address displays (for example, 192.168.10.1)
h. Use the arrow keys to scroll numerically to change the IP address as desired. Press ENTER to move to the next octet.
i. Press ENTER on the final octet to accept the changes.
j. Cycle power to the Gateway. The changes are saved on the Gateway and the new IP address is used.
k. Use the same procedures to set the subnet mask (SN) and default network gateway (GW) to match your network requirements. Your IT department can provide these settings if needed.
The Area Monitoring Gateway is intended to be deployed primarily using Ethernet communication. If it is necessary to use cellular communication to overcome complications with adding the device to the local area network, refer to the Area Monitoring Gateway with Cloud ID”‘ System Manual (pn 222401) to configure the system for cellular communication, or watch the tutorial videos on our website at www.bannerengineering.com/AreaCloudlD.
Activate the Banner Cloud Data Services
Follow these instructions to activate your Banner CDS account.
- Go to the bannercds.com website.
- Register your account by going to the Sign Up menu.
- Enter the requested information. The authorization code is on the Authorization Card included with your kit.
- Read and accept the Services Access and Use Agreement.
Create a New Gateway
Follow these steps to set up a new Gateway.
-
Log into the account and click New Gateway near the top right of the Overview screen.
-
Verify the Gateway Type is set to Cloud ID.
-
Name your Gateway.
-
Select the desired Company from the drop-down list.
-
Enter the serial number into the DXM Serial # field.
The serial number is on the Gateway’s label or is listed in the Gateway’s menu under System Info >» Controller » Serial. -
Click Save.
The Banner CDS software automatically creates dashboard layouts and data sets
for each sensor bound to the Area Monitoring Gateway.
The Banner CDS software application creates a site for the system and begins
searching for a data push from the Gateway.
These Area Monitoring Systems are designed to push data once every five
minutes with an Ethernet communication and once every ten minutes with
cellular communication. Therefore, the Gateway could take 5-10 minutes to
complete recognition by the Cloud application.
A push success will be indicated on the Gateway display with an $ followed by
a timestamp on the PUSH line and then refreshing the Banner CDS webpage with
Connected as the Status.
View Data and Dashboards
After the Banner CDS application has detected the Gateway, use the navigation
pane on the left side to view the Gateway.
Click Details next to the Gateway Name. The device Details page provides a
list of sensor objects for each Sensor Node bound to the system. The model
number, connection status, and relevant data registers for each sensor are
listed.
To edit the Sensor and Signal Names, click on the Edit button in the specific
row.
To view the dashboard for this system, click on Dashboards in the navigation pane and select the Gateway name from the list. Use the system dashboard to visually understand the status of your assets. Each icon represents a node within the system. The icon colors indicate:
- Green for those latest measurements that are within acceptable parameters;
- Yellow for measurements that have surpassed a Warning threshold; and
- Red for measurements that have surpassed a Critical threshold.
To view and adjust alarm thresholds:
- Edit these alarms as needed by clicking on the Edit button next to each alarm signal, or by navigating to the Alerts page and filtering the alert list to the appropriate gateway.
- Hover over and click the icons to view the default alarms currently established for each Sensor Node.
- On the Alert edit prompt, adjust the comparison operator and threshold values.
For more information about Alert settings and attributing Notifications to these alarms, please consult the complete Area Monitoring Gateway with Cloud ID™ System Manual (pn 222401) or watch the tutorial videos on www.bannerengineering.com/AreaCloudID.
Area Monitoring Gateway Specifications
Supply Voltage
12-30 V DC
Use only with a suitable Class 2 power supply (UL) or a
Limited Power Source (LPS) (CE) power supply
Construction
Polycarbonate
Environmental Rating
IP67
Operating Conditions
–20 °C to +60 °C (–4 °F to +140 °F)
Push to Cloud Rate
Once every 5 minutes (Ethernet connection) (default)
Once every 10 minutes (cellular connection)
Cellular Connectivity
4G LTE CATM1 (LTE-M/NB-IoT)
900 MHz Compliance (RM1809 Radio Module)
Radio module is indicated by the product label marking Contains FCC ID:
UE3RM1809: FCC Part 15, Subpart C,
15.247
Contains IC: 7044A-RM1809
IFT: RCPBARM13-2283
2.4 GHz Compliance (SX243 Radio Module)
Radio module is indicated by the product label marking Contains FCC ID:
UE3SX243: FCC Part 15, Subpart C, 15.247
Radio Equipment Directive (RED) 2014/53/EU ETSI/EN: EN 300 328 V2.2.2
(2019-07) [RED HarmStds] Contains IC: 7044A-SX243 ANATEL: 03737-22-04042
Certifications
**** Banner Engineering BV
Park Lane, Culliganlaan 2F bus 3
1831 Diegem, BELGIUM
**** Turck Banner LTD Blenheim House Blenheim Court Wickford, Essex SS11 8YT
GREAT BRITAIN
(CE/UKCA approval only applies to 2.4 GHz models)
(UL approval applies only to 900 MHz model)
FCC Part 15 Class A for Intentional Radiators
This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
Industry Canada Statement for Intentional Radiators
This device contains licence-exempt transmitters(s)/receiver(s) that comply
with Innovation, Science and Economic Development Canada’s licence-exempt
RSS(s). Operation is subject to the following two conditions:
1. This device must accept any interference, including interference that may
cause undesired operation of the device.
2. This device may not cause interference.
Dimensions
All measurements are listed in millimeters, unless noted otherwise.
Banner Engineering Corp Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in
material and workmanship for one year following the date of shipment. Banner
Engineering Corp. will repair or replace, free of charge, any product of its
manufacture which, at the time it is returned to the factory, is found to have
been defective during the warranty period. This warranty does not cover damage
or liability for misuse, abuse, or the improper application or installation of
the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER
EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING
UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of
Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING
CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS,
EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL
DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE
THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT
LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the
design of the product without assuming any obligations or liabilities relating
to any product previously manufactured by Banner Engineering Corp. Any misuse,
abuse, or improper application or installation of this product or use of the
product for personal protection applications when the product is identified as
not intended for such purposes will void the product warranty. Any
modifications to this product without prior express approval by Banner
Engineering Corp will void the product warranties. All specifications
published in this document are subject to change; Banner reserves the right to
modify product specifications or update documentation at any time.
Specifications and product information in English supersede that which is
provided in any other language. For the most recent version of any
documentation, refer to:
www.bannerengineering.com.
For patent information, see
www.bannerengineering.com/patents.
Contact Us
Banner Engineering Corp. headquarters is located at: 9714 Tenth Avenue North |
Minneapolis, MN 55441, USA | Phone: + 1 888 373 6767
For worldwide locations and local representatives, visit
www.bannerengineering.com.
Approved Antennas
BWA-9O2-C–Antena, Omni 902-928 MHz, 2 dBd, junta de caucho, RP-SMA Macho
BWA-9O5-C–Antena, Omni 902-928 MHz, 5 dBd, junta de caucho, RP-SMA Macho
BWA-9O6-A–Antena, Omni 902-928 MHz, 6 dBd, fibra de vidrio, 1800mm, N Hembra
BWA-9Y10-A–Antena, Yagi, 900 MHz, 10 dBd, N Hembra
Mexican Importer
Banner Engineering de Mèxico, S. de R.L. de C.V. | David Alfaro Siqueiros 103
Piso 2 Valle oriente | San Pedro Garza Garcia Nuevo Leòn,
C. P. 66269
81 8363.2714
© Banner Engineering Corp. All rights reserved.
August 03, 2023
p/n: 236146 Rev. A
References
- Banner CDS
- Asset Monitoring Gateway (AMG) with CLOUD ID
- Patents
- Asset Monitoring Gateway (AMG) with CLOUD ID
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>