Blaze King CK20.2 Wood Stove Repair Fireplace User Guide
- June 13, 2024
- Blaze King
Table of Contents
Blaze King CK20.2 Wood Stove Repair Fireplace
Product Information
- Product Name: CK20.2
- Installation Type: Residential and Mobile Home
- Minimum Clearances:
- Roof Exit – Parallel and Corner: 12.75″ (324 mm)
- Wall Exit – Parallel and Corner: 6.5″ (166 mm)
- Mobile Home Installation – A, B, C, D, E, F, J:
- A: 12.75″ (324 mm)
- B: 6.5″ (166 mm)
- C: 25.5″ (648 mm)
- D: 15.875″ (404 mm)
- E: 6″ (153 mm)
- F: 17.875″ (454 mm)
- J: 37″ (940 mm)
- Roof Exit Only – Parallel and Corner: 12.75″, 6.5″, 25.5″ x 15.875″ x 6″, 17.875″ x 37″
- Fan Kit or Rear Shield Kit & Outside Air Kit required
- Installation Compliance: Must comply with all local codes and regulations
- Flue Pipe Requirements: 6″ diameter, 24 MSG steel construction. Do not use aluminum or galvanized steel.
- Canada Clearance Requirement from Single Wall Pipe: Minimum 18″ (457 mm)
Product Usage Instructions
- Refer to local codes and pipe manufacturer specs for required minimum clearances.
- Ensure the flue pipe used is 6″ in diameter and made of 24 MSG steel construction. Do not use aluminum or galvanized steel.
- In Canada, maintain a minimum clearance of 18″ (457 mm) from single wall pipe.
- Minimum clearances may only be reduced by means approved by the regulatory authority.
- For residential installations, follow the minimum clearances specified for roof exit and wall exit, both parallel and corner configurations.
- For mobile home installations, follow the minimum clearances specified for A, B, C, D, E, F, and J parameters.
- For roof exit-only installations, follow the minimum clearances specified for parallel and corner configurations. Fan Kit or Rear Shield Kit and outside Air Kit are required.
- Ensure compliance with all local codes and regulations during installation.
- Use an ember protection shield listed under UL 1618-2009 (type 1) with a minimum size of 32″ x 40 1/8″ (813 mm x 1019 mm) in the USA and 41 3/8″ x 50 1/8″ (1051 mm x 1273 mm) in Canada.
- For alcove installations, ensure a minimum width of 50 7/8″ (1292 mm), a maximum depth of 48″ (1219 mm), and a minimum height above the stove of 37″ (940 mm).
- Avoid placing vinyl flooring directly in front of the appliance due to thermal expansion and the risk of permanent warping.
INSTALLATION
RESIDENTIAL INSTALLATION| A| B| C| D| E|
F| J
---|---|---|---|---|---|---|---
Roof exit; parallel and corner minimum clearances| 12.75”
324 mm
| 6.5”
166 mm
| 25.5” *
648 mm
| 15.875” *
404 mm
| 6”
153 mm
| 17.875” *
454 mm
| 37”
940 mm
Wall exit; parallel and corner minimum clearances| 12.75”
324 mm
| 6.5”
166 mm
| 25.5” *
648 mm
| 15.875” *
404 mm
| 6”
153 mm
| 17.875” *
454 mm
| 37”
940 mm
MOBILE HOME INSTALLATION|
Roof exit only; parallel and corner minimum clearances
*Fan Kit or Rear Shield Kit and outside Air Kit required
| 12.75”
324 mm
| 6.5”
166 mm
| 25.5” *
648 mm
| 15.875” *
404 mm
| 6”
153 mm
| 17.875” *
454 mm
| 37”
940 mm
This appliance must be installed in compliance with all local codes and regulations.
- Refer to local codes and pipe manufacturer specs for required minimum clearances.
- The flue pipe must be 6” diameter and 24 MSG steel construction. Do not use aluminum or galvanized steel. In Canada, a minimum 18” (457 mm) clearance from single wall pipe is required.
- Minimum clearances may only be reduced by means approved by the regulatory authority.
- 1= 4 58″ in Canada and 2 18″ in the USA 1 = 5 1/4” (127 mm) in Canada and 2 1/8″ (54 mm) in the USA.
- 2 = 58 34″ in Canada and 5634″ in USA2 = 58 1/8” (1476 mm) in Canada and 56 1/8” (1426 mm) in USA.
G = 2” (51 mm) in USA
8” (203 mm) in Canada
| H = 16” (406 mm) in USA
18” (456 mm) in Canada
| I = 0” (0 mm) in USA
8” (203 mm) in Canada
| K = 18” (456 mm) for single wall pipe in Canada
---|---|---|---
Ember protection shield (not required to have an insulation value) is to be listed under UL 1618-2009 (type 1) and must have a minimum size of:
- USA: 32 x 40 1/8” (813 mm x 1019 mm) and Canada: 41 3/8” x 50 1/8” (1051 mm x 1273 mm)
- Alcove: min-width = 50 7/8” (1292 mm), max depth = 48” (1219 mm), min-height above stove = 37” (940 mm)
FLOOR PROTECTION
If the appliance is installed on a combustible floor, a non-combustible shield must be used underneath the appliance. In the USA, the non-combustible shield must extend 16” out from the front and 8” out from either side of the fuel- loading door. In Canada, the non-combustible shield must extend 8” out from the rear and either side of the appliance and 18” out from the front of the loading door. A non-combustible shield is also required underneath the chimney connector and extend at least 2” on either side of the chimney connector. This floor protection is required to prevent sparks from falling onto the combustible floor (see CSA B365-M87). This appliance does not require thermal hearth pad protection. Blaze King does not recommend adhesive-based vinyl flooring in front of appliances due to thermal expansion and warping which could be permanent.