Blaze King BX24.1 Wood Stove Instructions
- June 13, 2024
- Blaze King
Table of Contents
Blaze King BX24.1 Wood Stove Instructions
BX24.1 MINIMUM CLEARANCES
RESIDENTIAL INSTALLATION| A| B| C| D| E|
F| J
---|---|---|---|---|---|---|---
Roof exit; parallel and corner minimum clearances| 10”
254 mm
| 10”
254 mm
| 25.125” *
639 mm
| 15.125” *
385 mm
| 2.75”
70 mm
| 16.375” *
416 mm
| 49”
1245 mm
Wall exit; parallel and corner minimum clearances| 10”
254 mm
| 14”
365 mm
| 25.125” *
639 mm
| 15.125” *
385 mm
| 2.75”
70 mm
| 16.375” *
416 mm
| 49”
1245 mm
This appliance must be installed in compliance with all local codes and regulations.
Refer to local codes and pipe manufacturer specs for required minimum
clearances.
Flue pipe must be 6” diameter and 24 MSG steel construction. Do not use
aluminum or galvanized steel.
In Canada, a minimum 18” (457 mm) clearance from single wall pipe is required.
Minimum clearances may only be reduced by means approved by the regulatory
authority.
G = 2” (51 mm) in USA
8” (203 mm) in Canada
| H = 16” (406 mm) in USA
18” (456 mm) in Canada
| I = 0” (0 mm) in USA
8” (203 mm) in Canada
| K = 18” (456 mm) for single wall pipe in Canada
---|---|---|---
Ember protection shield (not required to have an insulation value) is to be
listed under UL 1618-2009 (type 1) and must have a minimum size of:
USA: 41 3/4” x 36 3/4” (1061 mm x 934 mm) and Canada: 46 1/4” x 46 3/4” (1175
mm x 1188 mm) Alcove: min width = 50 1/8” (1273 mm), max depth = 48” (1219
mm), min height above stove = 49” (1245 mm)
FLOOR PROTECTION
If the appliance is installed on a combustible floor, a non-combustible shield must be used underneath the appliance. In the USA, the non-combustible shield must extend 16” out from the front and 8” out from either side of the fuel- loading door. In Canada, the non-combustible shield must extend 8” out from the rear and either side ofthe appliance and 18” out from the front of the loading door. A non-combustible shield is also required underneath the chimney connector and extend at least 2” on either side of the chimney connector. This floor protection is required to prevent sparks from falling onto the combustible floor (see CSA B365-M87). This appliance does not require a thermal hearth pad protection. Blaze King does not recommend adhesive based vinyl flooring in front of appliances due to thermal expansion and warping which could be permanent