Blaze King AF30.2A Minimum Clearances Fireplace User Guide
- June 13, 2024
- Blaze King
Table of Contents
Blaze King AF30.2A Minimum Clearances Fireplace
USING INSTRUCTIONS
RESIDENTIAL INSTALLATION| A| B| C| D| E| F|
J
---|---|---|---|---|---|---|---
Roof exit; parallel and corner minimum clearances| 10.75”
273 mm
| 6”
153 mm
| 25.5” *
648 mm
| 16.375” *
416 mm
| 4”
102 mm
| 16.875” *
429 mm
| 37”
940 mm
Wall exit; parallel and corner minimum clearances| 10.75”
273 mm
| 6”
153 mm
| 25.5” *
648 mm
| 16.375” *
416 mm
| 4”
102 mm
| 16.875” *
429 mm
| 37”
940 mm
MOBILE HOME INSTALLATION|
Roof exit only; parallel and corner minimum clearances
*Fan Kit or Rear Shield Kit & Outside Air Kit required
| 10.75”
273 mm
| 6”
153 mm
| 25.5” *
648 mm
| 16.375” *
416 mm
| 4”
102 mm
| 16.875” *
429 mm
| 37”
940 mm
This appliance must be installed in compliance with all local codes and regulations
- Refer to local codes and pipe manufacturer specs for required minimum clearances.
- Flue pipe must be 6” diameter and 24 MSG steel construction. Do not use aluminum or galvanized steel.
- In Canada, a minimum 18” (457 mm) clearance from single wall pipe is required.
- Minimum clearances may only be reduced by means approved by the regulatory authority.
DIMENSIONS
G = 2 3/4” (70 mm) in USA
8” (203 mm) in Canada
| H = 16” (406 mm) in USA
18” (457 mm) in Canada
| I = 0” (0 mm) in USA
8” (203 mm) in Canada
| K = 18” (457 mm) for single wall pipe in Canada
---|---|---|---
- The Ember Protection Shield is not required to have an insulation value, but must be listed under UL 1618-
- 2009 (Type 1) and must have a minimum size of:
- USA: 35” x 42 1/8” (889 x 1070 mm) and Canada: 45 1/2” x 52 1/8” (1156 x 1324 mm)
- Alcove: min width = 51” (1295 mm), max depth = 48” (1219 mm), min height above stove top = 37” (940 mm)
FLOOR PROTECTION
- If the appliance is installed on a combustible floor, a non-combustible shield must be used underneath the appliance.
- In the USA, the non-combustible shield must extend 16” out from the front and 8” out from either side of the fuel-loading door.
- In Canada, the non-combustible shield must extend 8” out from the rear and either side ofthe appliance and 18” out from the front of the loading door.
- A non-combustible shield is also required underneath the chimney connector and extend at least 2” on either side of the chimney connector.
- This floor protection is required to prevent sparks from falling onto the combustible floor (see CSA B365-M87).
- This appliance does not require a thermal hearth pad protection.
- Blaze King does not recommend adhesive based vinyl flooring in front of appliances due to thermal expansion and warping which could be permanent.