MEAN WELL DUPS40 DIN Rail Type Uninterruptible DC-UPS Module Owner’s Manual
- June 13, 2024
- MEAN WELL
Table of Contents
MEAN WELL DUPS40 DIN Rail Type Uninterruptible DC-UPS Module
Product Information
Product Name: 24V/40A DIN Rail Type Uninterruptible DC-UPS Module
Model: DUPS40
- Specification
- DC UPS INPUT:
- Normal Input Voltage: 24Vdc
- Input Voltage Range: 24 ~ 29Vdc
- Rated Current: 40A
- Voltage Range: 21 ~ 29Vdc
- Discharge Current Range: 0 ~ 40A
- Charging Current: 2A
- Normal Battery Voltage: 24Vdc (2 x 12Vdc in series or 1 x 24Vdc)
- Battery Type: Lead-acid battery
- External Battery Capacities: 4AH ~ 135AH
- Battery Polarity: Protected by internal detection, No Damage, recovers automatically after fault conduction is removed. This protection only works when batteries are not connected, No Damage. External fuse is recommended when batteries are connected.
- PROTECTION:
- Short Circuit Protection: Protected by internal detection, No Damage, recovers automatically after fault conduction is removed.
- Over Discharge Current: 42~46A, After 3 sec., unit will cut-off battery discharging by relay.
- Battery Deep Discharge: Cut-off battery discharging by relay.
- RELAY CONTACT RATINGS (max.):
- DC BUS OK: LED (Red) – Battery over-discharge warning or battery broken: light; Battery OK: dark
- BATTERY DISCHARGE: Relay contact – Short when battery in discharge condition, relay contacts LED (Yellow) – light: Battery discharging; dark: Battery is not discharging or discharging current < 2.0A
- COOLING:
- Working Temperature: -30 ~ +70°C (Refer to Derating Curve)
- Working Humidity: 5 ~ 95% RH non-condensing
- ENVIRONMENT:
- Storage Temperature: -40 ~ +85°C
- Temperature Coefficient: Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
- Operating Altitude: 2000 meters/OVC II
- Safety Standards: EAC TP TC 004 approved
- Withstand Voltage: IP/OP – Chassis: 0.5KVac; IP/OP- Relay: 0.5KVac; Relay – Chassis: 0.5KVac
- Isolation Resistance: IP/OP – Chassis, IP/OP- Relay, Relay – Chassis: >100M Ohms / 500Vdc / 25/ 70% RH
- EMC EMISSION:
- Conducted: BS EN/EN55032(CISPR32) Class B
- EMC IMMUNITY:
- ESD: BS EN/EN61000-4-2 Level 3, 8KV air; Level 2, 4KV contact; criteria B
- Radiated: BS EN/EN61000-4-3 Level 3, 10V/m; criteria A
- EFT / Burst: BS EN/EN61000-4-4 Level 3, 2KV; criteria A
- Surge: BS EN/EN61000-4-5 Level 3, 0.5KV (DC input ports)
- Conducted: BS EN/EN61000-4-6 Level 3, 10V; criteria A
- Magnetic Field: BS EN/EN61000-4-8 Level 4, 30A/m; criteria A
- MTBF: 1376.5K hrs min. Telcordia SR-332 (Bellcore); 499.5K hrs min. MIL-HDBK-217F (25)
- DIMENSION PACKING: 63125.2113.5mm (WHD); 0.42Kg; 20pcs/9.4Kg/1.57CUFT
Product Usage Instructions
To use the 24V/40A DIN Rail Type Uninterruptible DC-UPS Module (DUPS40), follow these instructions:
- Connect the DC UPS input to a power supply with a normal input voltage of 24Vdc.
- Ensure that the input voltage range is within 24 ~ 29Vdc.
- Connect the DC UPS output to the load that requires uninterrupted power.
- Connect the battery to the module. The battery should have a normal voltage of 24Vdc (can be achieved by connecting 2 x 12Vdc batteries in series or using a single 24Vdc battery).
- Make sure the battery type is a lead-acid battery with capacities ranging from 4AH to 135AH.
- For protection against short circuits, it is recommended to use an external fuse when batteries are connected.
- Ensure that the working temperature is within the range of -30~ +70°C. Refer to the provided derating curve for temperature-dependent adjustments.
- Avoid operating the module in extreme humidity conditions (5 ~ 95% RH non-condensing).
- The module can be stored in temperatures ranging from -40 ~ +85°C.
- To test the battery, check the LED display status. A green LED indicates a successful battery test, a red LED indicates battery over-discharge warning or battery broken, and a yellow LED indicates battery discharging.
Features
- Uninterruptible DC-UPS controller
- Parallel connection to DC BUS
- (Power supply + DC-UPS Module + Batteries + Load)
- Suitable for 24V system, up to 40A
- 2A Battery charging current
- Allows 4AH~135AH lead-acid various battery capacities
- Complete diagnostic and monitoring for DC BUS OK, battery discharge, battery fail
- LED indicator for signal status
- Protections: Battery reverse polarity protection & Short circuit(By internal detection) / Battery discharge / Over discharge current
- Cooling by free air convection
- 3 years warranty
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
GTIN CODE
- MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
The DUPS40 is a 40A DIN rail type DC-UPS module, and it is paired with a power supply and an external battery to achieve the backup function. When the AC mains fails or is interrupted, the load will be immediately connected to the battery pack to avoid interruption and to ensure the continuous operation of the entire system (the operating time depends on the capacity of the battery pack). The main features of DUPS40 include: fast installation, suitability for 24V battery packs and various capacities of 4AH~135AH, 2A battery charging current, low voltage disconnect for battery protection and more. The product is suitable for use in data centers, security systems, emergency lighting, wireless communication UPS, central monitoring systems, etc.
Model Encoding
SPECIFICATION
MODEL | DUPS40 |
---|
DC UPS INPUT
| NORMAL INPUT VOLTAGE| 24Vdc
INPUT VOLTAGE RANGE| 24 ~ 29Vdc
RATED CURRENT| 40A
DC UPS OUTPUT| VOLTAGE RANGE| 21 ~ 29Vdc
DISCHARGE CURRENT RANGE| 0 ~ 40A
CHARGING CURRENT| 2A
BATTERY
| NORMAL BATTERY VOLTAGE| 24Vdc ( 2 x 12Vdc in series or 1 x 24Vdc)
BATTERY TYPE| Lead-acid battery
EXTERNAL BATTERY CAPACITIES| 4AH ~ 135AH
PROTECTION
| BATTERY POLARITY| Protected by internal detection, No Damage, recovers
automatically after fault conduction is removed
SHORT CIRCUIT| This protection only works when batteries are not
connected, No Damage. External fuse is recommended when batteries are
connected.
OVER DISCHARGE CURRENT| 42~46A,After 3 sec., unit will cut-off battery
discharging by relay
BATTERY DEEP DISCHARGE| Cut-off battery discharging by relay
FUNCTION
| RELAY CONTACT RATINGS (max.)| 30VDC/1A resistive load
DC BUS OK| Relay contact : Short when DC voltage between 21~29V(±2%),
relay contacts
LED(Green) : DC BUS OK : light ; DC BUS fail : dark
BATTERY FAIL Note.2| Short when battery voltage falls below 22V(±2%)
or battery failure is observed through the battery test function, relay
contacts
LED(Red) : Battery over-discharge warning or battery broken : light ; Battery
OK : dark
BATTERY DISCHARGE| Relay contact : Short when battery in discharge
condition, relay contacts
LED(Yellow) : light : Battery discharging ; dark : Battery is not discharging
or discharging current < 2.0A
ENVIRONMENT
| COOLING| Free air convection
WORKING TEMP. Note.3| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 5 ~ 95% RH non-condensing
STORAGE TEMP.| -40 ~ +85℃
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 60℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,
Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE Note.4| 2000 meters/OVC II
SAFETY & EMC
(Note.5)
| SAFETY STANDARDS| EAC TP TC 004 approved
WITHSTAND VOLTAGE| IP/OP – Chassis : 0.5KVac ; IP/OP- Relay : 0.5KVac ;
Relay – Chassis : 0.5KVac
ISOLATION RESISTANCE| IP/OP – Chassis, IP/OP- Relay, Relay –
Chassis:>100M Ohms / 500Vdc / 25℃/ 70% RH
EMC EMISSION
| Parameter| Standard| Test Level / Note
Conducted| —–| —–
Radiated| BS EN/EN55032(CISPR32)| Class B
Voltage Flicker| —–| —–
Harmonic Current| —–| —–
EMC IMMUNITY
| BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact; criteria B
Level 2, 4KV air ; Level 1, 2KV contact; criteria A
Radiated| BS EN/EN61000-4-3| Level 3, 10V/m ; criteria A
EFT / Burst| BS EN/EN61000-4-4| Level 3, 2KV ; criteria A
Surge| BS EN/EN61000-4-5| Level 3, 0.5KV(DC input ports)
Conducted| BS EN/EN61000-4-6| Level 3, 10V ; criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m ; criteria A
OTHERS
| MTBF| 1376.5K hrs min. Telcordia SR-332 (Bellcore) ;
499.5K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 63125.2113.5mm (WHD)
PACKING| 0.42Kg; 20pcs/9.4Kg/1.57CUFT
NOTE
|
- All parameters NOT specially mentioned are measured at normal input(24V), rated load and 25 C of ambient temperature.
- Every 30 seconds, unit will test the battery.If the testing result is faulty, unit will turn on “Battery Fail” relay contact and “Red LED” indicator.
- Derating may be needed over high ambient temperature. Please check the derating curve for more details.
- The ambient temperature derating of 3.5°C/1000m with fanless models and of 5°C/1000m with fan models for operating altitude higher than 2000m(6500ft).
- The unit is considered a component which will be installed into a final equipment. All the MC tests are been executed by mounting the unit on a 360*720mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets MC directives. For guidance on how to perform these MC tests,please refer to “EMI testing of component power supplies.”(as available on http://www.meanwell.com)
Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve
Buffering Time
Discharge Current | Buffering Time(Reference) |
---|---|
7.5AH | 12AH |
2.5A | 6500s |
5A | 3000s |
10A | 1200s |
20A | 400s |
30A | 120s |
40A | 25s |
Mechanical Specification
- Case No.: 979F
- Unit: mm
Terminal Pin No. Assianment (TB1)
Pin No. | Assignment |
---|---|
1 | BAT INPUT + |
2 | BAT INPUT – |
3 | DC INPUT – |
4 | DC INPUT + |
Terminal Pin No. Assignment (TB2)
Pin No. | Assignment | LED |
---|---|---|
1 | BAT Discharge | YELLOW |
2
3| BAT Fail| RED
4
5| DC OK| GREEN
6
Installation Instruction
ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)
- This series fits DIN rail TS35/7.5 or TS35/15.
- For installation details, please refer to the Instruction manual.
Suggested Application
Back up connection for AC interruption
Combine redundancy module DRDN20 or DRDN40) to back up AC interruption or failure of PSU
Installation Manual
- Please refer to: http://www.meanwell.com/manual.html
SCAN
Documents / Resources
| MEAN
WELL DUPS40 DIN Rail Type Uninterruptible DC-UPS
Module
[pdf] Owner's Manual
DUPS40 DIN Rail Type Uninterruptible DC-UPS Module, DUPS40, DIN Rail Type
Uninterruptible DC-UPS Module, Rail Type Uninterruptible DC-UPS Module, Type
Uninterruptible DC-UPS Module, Uninterruptible DC-UPS Module, DC-UPS Module,
Module
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>