MURPHY DLA100 TANKTEND Level Monitoring System
Product Information: DLA100 TANKTENDTM Level Monitoring System
The DLA100 TANKTENDTM Level Monitoring System is a device used to monitor the
level of flammable and combustible liquids in tanks. It is designed for use in
non-hazardous locations and operates on an operating voltage of 120 VAC, 50/60
Hz (standard) or 220 VAC, 50/60 Hz (optional, not UL listed).
The system includes adjustable high and low level contacts that operate alarm
lights on the front of the DLA100. It also has a SPDT dry contact to operate a
remote low level alarm. This system can be used as both a tank filling alarm
and a low fuel supply alarm. The level is indicated in linear measurement, and
a chart can be obtained from your tank supplier to convert height measurement
to gallons, liters, etc.
The DLA100 comes with a UTKN tank plug kit for installation on underground or
above ground tanks. The kit includes a 12 ft. (3.66 m) x 1/4 in. (6 mm)
diameter stainless steel tube and fittings for below ground tank
installations. The tank plug is available in 2 NPT or 4 NPT.
A two-year limited warranty on materials and workmanship is provided with the
DLA100 TANKTENDTM Level Monitoring System.
Product Usage Instructions: DLA100 TANKTENDTM Level Monitoring System
Before beginning the installation of this Murphy product, please ensure
that all electrical power to the machine is disconnected and that the machine
cannot operate during installation. Follow all safety warnings of the machine
manufacturer and read and follow all installation instructions.
Mounting the DLA100
- Obtain customer-supplied mounting hardware.
- Choose a mounting location that provides an unobstructed view of the gage and unobstructed access.
- Refer to the mounting dimensions provided on page 1 for proper positioning.
- Mount the DLA100 using the customer-supplied mounting hardware.
Note: It is recommended to route the sensor tubing and AC power line through rigid conduit during installation.
Installing the Tank Plug Kit (UTKN)
- Locate the tank service cover.
- Install the UTKN tank plug included in the DLA100 package.
Note: The tank plug kit includes a 12 ft. (3.6 m) x 1/4 in. (6 mm) dia. stainless steel tube and all necessary fittings. Choose either a 2 NPT or 4 NPT tank plug based on your tank’s requirements.
DLA100 TANKTENDTM Level Monitoring System
Installation and Operation Instructions
Please read the following information before installing. A visual inspection
of this product for damage during shipping is recommended before mounting. It
is your responsibility to have a qualified person install
this unit and make sure it conforms NFPA 70 (National Electrical Code) and 30A
(Automotive and Marine Service Station Code) and any other applicable local
codes.
GENERAL INFORMATION
Specifications
- Enclosure : 14 gauge steel, NEMA 3R.
- Power Input (Operating Voltage ): 120 VAC, 50/60 Hz (Standard);
- 220 VAC, 50/60 Hz (Optional, not UL listed).
- Laboratory Listing : Listed for use in non-hazardous locations to gage flammable and combustible liquids.
OPLHA SWICHGAGE®
- Accuracy : ± 2% for the first and last quarters of the scale, the middle half of scale is ±1%.
- Geared Movement : 302 and 304 stainless steel.
- Overrange : Do not exceed 30% above full range.
- Sensing Element : Bellows.
- Dial : 4-1/2 in. (114 mm), white on black background.
Description
The DLA100 Monitoring System continuously monitors the level in a fuel storage
tank and displays this level on an easy to read 4-1/2 in. (114 mm) dial gage.
Level is measured by the highly reliable bubbler method using a built-in air
pump (120 VAC, 50/60 Hz; optional 220 VAC) and our OPL-HAC level SWICHGAGE®.
The DLA100 system is housed in a weather-proofed enclosure (NEMA 3R) with
provision for pad locking.
Adjustable high and low level contacts operate alarm lights on the front of
the DLA100. A SPDT dry contact is provided to operate a remote low level
alarm.
Because it has both high and low level switches, the DLA100 can be used as a
tank filling alarm and a low fuel supply alarm. Level is indicated in linear
measurement. Your tank supplier can provide you with a chart converting height
measurement to gallons, liters, etc.
A UTKN tank plug kit is provided with the DLA100 and can be installed on an
underground or above ground tank. This kit includes 12 ft. (3.66 m) x 1/4 in.
(6 mm) diameter stainless steel tube and fittings for below ground tank
installations. The tank plug is available in 2 NPT or 4 NPT.
The UTKN tank plug and the DLA100 must be interconnected by a length of copper
tubing (1/4 in. 6 mm dia.) routed through conduit (1 in. 25 mm dia.). Copper
tubing and conduit are supplied by the customer. The copper tubing allows tank
static head pressure changes to be monitored on the OPLHAC SWICHGAGE®.
Warranty
A two year limited warranty on materials and workmanship is provided with this Murphy product. Details are available on request and are packed with each unit.
DLA100 Mounting Dimensions
INSTALLATION
WARNING: Installation of the DLA100 Series MUST BE made by a qualified
installer. Hazardous conditions exist with flammable and corrosive products.
Extinguish all smoking materials. Risk of explosion, fire and burning can
cause serious or fatal injury.
Mounting the DLA100
For Mounting Dimensions see page 1.
Mounting hardware is customer supplied. The mounting location for the DLA100
should provide unobstructed view of the gage and unobstructed access. Before
mounting the DLA100, determine the routing of the sensor tubing and AC power
line (routing through rigid conduit is recommended).
Installing the Tank Plug Kit (UTKN)
- The DLA100 includes a UTKN tank plug. Tank plug kit includes 12 ft.
- (3.6 m) x 1/4 in. (6 mm) dia. stainless steel tube and all necessary fittings.
The tank plug is available in 2 or 4 NPT.
-
Locate the tank service cover and install the UTKN tank plug.
-
From tank top to the DLA100 location, route a 1/4 in. (6 mm) dia. copper tube within a 1 in. (25 mm) dia. conduit. The customer is to supply the copper tube and the conduit. Caution must be exercised when routing copper tubing through conduit to avoid damaging the tube. Refer to Fig. 1 and Fig. 2.
-
Before inserting the 1/4 in. (6 mm) dia. stainless steel tubing (probe) through tank plug fitting, make sure tubing can reach bottom and also will allow extra tubing for adjustments.
Now lower the tubing until it touches bot- tom of the tank, do this as follows -
Loosen the compression nut and the ferrule (see Detail A).
- Insert the tubing through the compression nut, ferrule and fitting until it touches bottom of tank.
- Mark tubing at top of fitting–raise the tubing exactly 3 in. (76 mm) off bottom and securely tighten ferrule and compression nut.
- Cut excess stainless steel tubing allowing 1/2 in. (13 mm) extension above the compression nut.
-
The copper tubing carries static head pressure from the stainless steel sensor tube within the tank to the DLA100. Connect the copper tubing to the stainless steel tank probe as shown (see Detail B). The copper tubing should be continuous length— without splices.
-
Securely tighten all fittings, all connections must be air tight.
Fig. 1 Typical Installation for Below Ground Tank
- Manwell
- Driveway Surface
- UTKN Tank Plug
- Coupling
- Stand-Pipe
- Tank Plug Opening 1/4 in. (6 mm) dia.
- Stainless Steel Tube
Fig. 2 Typical Installation for
Connecting Copper Tubing to DLA100
The DLA100 includes a CKBO check valve, connected directly below the gage,
within the DLA100 enclosure. This check valve is designed to pre-vent product
from backing up into the gage. Connect the tubing line com-ing from the UTKN
plug to the CKBO valve as follows
CAUTION: Tubing line MUST NOT exceed 150 feet (45.7 m) from the tank for the DLA100 gage to read correctly. Contact Murphy for distances greater than 150 ft. (45.7 m).
-
Locate the CKBO check valve. It is connected to the OPLHAC SWICHGAGE®. Refer to Fig. 3, at right.
-
Completely detach the compression nut located at the end of the CKBO check valve (see Detail C).
-
Insert the copper tubing line through the com-pression nut and ferrule.
-
Route the copper tubing, the ferrule and the compression nut through the conduit fitting located directly below the check valve, at the bottom of the DLA100 enclosure.
-
Attach the copper tubing to the CKBO check valve fitting as shown.
-
Now, tighten the compression nut. Connection must be air tight.
Fig. 3 DLA100 Connections
ELECTRICAL CONNECTIONS
WARNING: Turn power “OFF” before wiring. Make sure voltage/current requirements are within the DLA100 ratings.
Connecting AC Power to the DLA100
IMPORTANT: All connections must be made using appropriate wire size and
wire termination hardware.
- Locate the user terminal block within the DLA100 enclosure.
- Route the wiring from the 120 or 220 VAC power source to the terminal block. Routing the power leads through conduit is recommended.
- Connect the “L” power lead to DLA100 terminal #1, see Fig. 4, and Detail D.
- Connect the “N” power lead to DLA100 terminal #2.
- When connecting the DLA100 to a remote low level alarm, connect the remote alarm “N.O.” lead to DLA100 terminal #3. Connect the “COMMON” lead to terminal #4. Connect “N.C.” lead to terminal #5. Activation of external low level alarm is controlled by energizing/de-energizing of relay K1, see the Typical Wiring Diagram, Fig. 4.
Fig. 4 Typical Wiring Diagram
ADJUSTING LIMIT CONTACTS AND GAGE POINTER
Adjusting High and Low Limit Contacts
The OPLHAC SWICHGAGE® instrument features adjustable limit contacts. The
OPLHAC is within the DLA100 enclosure. Facing the OPLHAC dial, the left knob
is for adjusting the “Low Limit” contact. The “High Limit” contact knob is
located on right.
- Open the DLA100 enclosure door to access the gage. Determine “Low” product level where alarm activation is to occur. Gently turn the “Low Limit” contact knob to desired point on the scale.
- Determine the “High” product level where alarm activation is to occur. Repeat the above procedure for the knob controlling the “High Limit” contact. Close enclosure door and latch.
Limit Contacts Wiping Feature
The force of the pointer causes the flexible contact arm (A) to tilt resulting
in a wiping action (D). This clears away film and corrosion formed on the
contact surface, refer to Detail E.
- A. Contact arm-flex
- B. Contact arm
- C. Pointer Contact
- D. Initial point of contact
- E. Limit contact knob
Resetting the SWICHGAGE® Pointer
After the DLA100 has been connected, reset the pointer for proper level
indication, proceed as follows. Allow the DLA100 system to complete 2 to 3
purge cycles before performing the following calibration steps
WARNING: Turn power OFF before resetting the gage pointer.
- Determine actual product level by a reliable means and record this value.
- Use caution to remove the SWICHGAGE® snap ring and lens (place your hand on top of ring to protect against its spring action).
- Carefully hold the pointer, as shown at Detail F, making sure not to bend it.
- With a small screwdriver, turn the set- ting screw to corresponding reading value recorded in step 1. Clockwise to raise the pointer– counterclockwise to lower the pointer.
- Replace the lens and snap ring.
- Turn AC power ON. Check pointer position reading to be certain it agrees with calibrated setting after tank purging.
NOTE: Span adjustments and recalibration must be performed by authorized mechanic or return the unit to Frank W. Murphy Mfr.
CIRCUIT OPERATION AND TEST
Perform the following circuit operation and test after the DLA100 system is
completely installed and wired appropriately.
Important: The relay timers TD1 and TD2 must be set to your specifications
before attempting this operation test. To set the relay timers, refer to the
instructions provided by the relay manufacturer (included in your DLA100
system information package).
Circuit Operation
A typical application for indication only of high and low level alarms for
storage or supply tank, is achieved with the use of DLA100.
The TD1 relay timer controls the purge pump cycle “ON” and “OFF” times. The
TD2 relay timer locks out the alarm contacts during the purge cycle. Relay TD2
stops any type of false alarm in a purge cycle.
The alarm indication will only be activated during the period when the
indicating pointer is making contact with the low or high OPLHAC adjustable
contact.
Testing the DLA100
- Apply power to the DLA100.
- The purge pump will begin pumping. if the purge pump does not start, connect a voltmeter across terminals #1 and #2 to verify the correct AC voltage is being applied. Refer to “Electrical Connections” section on page 3. Check purge relay time settings or recycle time delay. Also check the fuse.
- The SWICHGAGE® pointer will travel clockwise. Adjust the limit contacts to desired set points (see above section).
- If override is necessary it must be done externally.
- To test the limit contacts, turn the limit contact knob to be tested until the contact touches the pointer. That will trip the control circuit. Reset limit contact.
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
Frank W. Murphy Manufacturer
P.O. Box 470248; Tulsa, Oklahoma 74147; USA tel.
918-627-3550 fax
918-664-6146
e-mail fwmurphy@ionet.net
Frank W. Murphy Southern Division
P.O. Box 1819; Rosenberg, Texas 77471; USA
tel. 281-342-0297
fax 281-341-6006
e-mail murphysd@intertex.net
Printed in U.S.A.
Frank W. Murphy, Ltd.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K.
tel. +44 1722 410055
fax +44 1722 410088 tlx 477088
e-mail sales@fwmurphy.co.uk
Frank W. Murphy Pte., Ltd.
26 Siglap Drive; Republic of Singapore 456153
tel. +65 241-3166 fax +65 241-8382
e-mail fwmsales@fwmurphy.com.sg
Murphek Pty., Ltd.
1620 Hume Highway; Campbellfield, Vic 3061;
Australia tel. +61 3 9358-5555
fax +61 3 9358-5558
Murphy de México, S.A. de C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje San Luis Potosí, S.L.P.;
México 78384
tel. +52-48-206264
fax +52-48-206336
e-mail
murmexsl@sanluis.podernet.com.mx
Murphy Switch of California
P.O. Box 900788; Palmdale, California 93590; USA
tel. 805-272-4700
fax 805-947-7570
e-mail sales@murphyswitch.com
Frank W. Murphy France
tel. +33 1 30 762626
fax +33 1 30 763989