FW MURPHY MDTM89 Production Controls Instruction Manual

June 4, 2024
FW MURPHY

FW MURPHY MDTM89 Production Controls


All trademarks and service marks used in this document are the property of their respective owners.

Installation and Operations

Please read the following instructions and warnings before installation. Visually inspect the product for any damage that may have occurred during shipping.

WARNINGS

**WARNINGS**

| Before installation of this product:

  • Disconnect all electrical power to the machine
  • It is your responsibility to ensure that qualified mechanical and electrical technicians install this product
  • Make sure the machine cannot operate during installation
  • Follow all safety warnings of the machine manufacturer
  • Read and follow all installation instructions
  • Please contact FW Murphy Production Controls immediately if you have any questions

---|---

MDTN89 Interface Capabilities


Model| Power Source| Rating
LCDT| CD Ign., 120 VAC, 12/24 VDC| Cl.I, Div.1, Gr.D, Haz. Areas1
S1501| 120 VAC or 12/24 VDC| Cl.I, Div.1, Gr.D, Haz. Areas
MARK TTD| CD Ign., 12/24 VDC| Cl.I, Div.2, Gr.D, Haz. Areas2
TATTLETALE®| CD Ign., 120 VAC, 12/24 VDC| Non-Hazardous Areas
PLCs, various non-FW Murphy annunciators – contact FW Murphy

  1. An isolation barrier is needed between the MDTM89 and an Annunciator rated for Class I, Division 1, Group D, Hazardous Areas.
  2. When used with approved ignition. Contact FW Murphy for details.

FW Murphy’s model MDTM89 is an electronic, dual-temperature monitor. It monitors two thermocouples, displays the temperature of the thermocouple selected and has adjustable trip points for each input. A toggle switch provides for selection of the thermocouple to be displayed and/or the temperature trip point to be checked/adjusted. If either trip point is reached, the associated output turns ON and can be used as a control signal or to initiate alarms and/or shutdown.

Mounting the Gauge

Mount the MDTM89 temperature gauge in a place where it will be protected from rain and splashing water. A minimum distance of 12 in. (305 mm) from any ignition coils or coil leads should be maintained. The MDTM89 flush mount case is intended for mounting in a flat panel .032 in. (1 mm) to .125 in. (3 mm) thick.

  1. Cut a 4-3/4 in. (121 mm) diameter hole.
  2. Drill three 1/4 in. (6 mm) diameter fastening holes as shown below.
  3. Insert the gauge from the back side of the panel.
  4. Using the three 10-24 screws, included with the gauge, secure gauge to the panel.

Wiring and Adjustment

CAUTION

| Perform the wiring operation with the power source OFF. Make sure the voltage and current requirements are within the gauge ratings. Keep all high voltage wiring, such as spark plug wires, away from THERMOCOUPLES AND EXTENSION WIRING. Before wiring, determine the voltage and polarity for the application.
---|---

One Thermocouple Only

Even though the MDTM89 is a dual-temperature monitor, it will monitor and display one temperature with equal results.

» When monitoring one temperature, always jumper the unused thermocouple terminals on the back of the MDTM89 with a short length of wire. The unused channel will display approximate ambient temperature.

Open Thermocouple Input

An open thermocouple input forces the monitor into upscale overrange. The monitor indicates an overrange by displaying the numeral 1 in the left most digit of the display. An overrange will turn on the trip point output for the respective thermocouple.

Table 1. Thermocouple Extension Wire Color Code

Thermocouple Type| Thermocouple Extension Wire| Color Code/Material
Positive Lead| Negative Lead
J| J| White /Iron| Red/Constantan
K| K| Yellow/Chromel| Red/Alumel
Table 2. Thermocouple Extension Wire Loop Resistance in Ohms per Foot at 68° F

Size AWG No.| Type J| Type K
14| .07| .146
16| .137| .230
18| .222| .374
20| .357| .586
24| .878| 1.490

MDTM89 Wiring and Adjustment Instructions

Facing the dial, left side knob is Low limit contact. Right side is High limit contact.
To set limit contact, turn the knob to the desired point on the scale.

Using Thermocouple Extension Wire

  1. After thermocouple installation, connect the thermocouple leads to the MDTM89 according to the instructions.
  2. If the thermocouple leads are not long enough, you will need to use shielded thermocouple extension wire. The thermocouple extension wires, from your thermocouple lead wires to the terminals of the MDTM89, must be of the same material as the thermocouple lead wires. See Table 1.
  3. When connecting the thermocouple extension wire to your thermocouple leads, twist the wire connections, then install wire nuts, such as ceramic type, which have no metal insert. DO NOT SOLDER.
    a. To prevent problems of interference from electrical noise, DO NOT route thermocouple wires in the same conduit or
    within 12 inches (304 mm) of ignition wires or alternating current conductors.
    b. Metallic-overbraided thermocouple wire is recommended. It provides electrical shielding as well as protection against wear and abrasion.

Connecting Thermocouple Wires (Ungrounded Thermocouple)

  1. Remove factory-installed jumpers or shunts from TC1 and TC2 terminals before connecting thermocouple(s).

  2. Connect the thermocouple leads to the thermocouples. Observe lead polarity. See Table 1 for thermocouple extension lead color code and thermocouple polarity.
    NOTE: Before continuing to the next step, decide which thermocouple is to be identified as TC1 and which is to be identified as TC2. A wire marker should be installed on each end of the thermocouple lead to identify TC1 and TC2.

  3. Connect the positive lead of thermocouple TC1 to the positive (+) terminal of terminal strip TC1.

  4. Connect the negative lead of thermocouple TC1 to the negative (-) terminal of terminal strip TC1.

  5. Connect the positive lead of thermocouple TC2 to the positive (+) terminal of terminal strip TC2.

  6. Connect the negative lead of thermocouple TC2 to the negative (-) terminal of terminal strip TC2.

Connecting Output Wires

  1. Wire the gauge trip point outputs as shown in the Typical Wiring Diagrams section.
  2. Connect the Power Wires as detailed below.
    a. Determine the voltage and the polarity of the input power before attempting to connect the power leads to the MDTM89.
    b. On CD ignitions, connect the shut-down lead to the MDTM89 ignition input as shown in the Typical Wiring Diagrams section.
Typical Wiring Diagram




Operation Test

Perform the Operation Test after the MDTM89 is installed and wired appropriately.

  1. Rotate the trip point potentiometers TC1 and TC2 clockwise until an audible click is heard or detente is felt. These are 12- turn potentiometers.
    a. Start the engine or power up the monitor.

  2. Set the display selector switch to the TC1 position to display the TC1 temperature. Note temperature reading for step 2b.
    a. Depress and hold the Push to Read trip point push button to display the TP1 setting.
    b. Rotate the TC1 trip point potentiometer counterclockwise until the display reading is equal to the temperature reading observed in step 2.
    c. Trip point TP1 will turn on and trip the shutdown device or alarm; verify by observation.
    d. Rotate the trip point potentiometer TC1 clockwise several turns to turn off TP1.
    e. Reset alarm or shut down device.

  3. Set the display selector switch to the TC2 position to display the TC2 temperature. Note temperature reading for step 3b.
    a. Depress and hold the Push to Read trip point push button to display the TP2 setting.
    b. Rotate the TC2 trip point potentiometer counterclockwise until the display reading is equal to the temperature reading observed in step 3.
    c. Trip point TP2 will turn on and trip the shutdown device or alarm; verify by observation.
    d. Rotate trip point potentiometer TC2 clockwise several turns to turn off TP2.
    e. Reset alarm or shut down device.

Trip Point Adjustments
  1. Power up the temperature monitor by turning on power or by starting engine.
  2. Set the display toggle switch to the TC1 position.
  3. Press the button and read the trip point in display.
  4. Rotate the trip point potentiometer TC1 until the display indicates the desired trip point temperature for TC1.
  5. Set the display selector switch to TC2 position.
  6. Press the button and read the trip point in display.
  7. Rotate the trip point potentiometer TC2 until the display indicates the desired trip point temperature for TC2

Specifications

Dial: White on black, dual scale, °F and °C standard, 4-1/2 in. (114 mm) diameter
Power Requirements (Operating Voltages):
_ MDTM89-A: 100 to 350* VDC, CD ignition, negative ground (FET outputs)
MDTM89-E: 100 to 350* VDC, CD ignition, negative grounds (FET outputs)
MDTM89-B: 100 to 350* VDC, CD ignition, negative or positive ground (SCR outputs)
MDTM89-C: 12 to 24 VDC, negative ground, 15 milliwatts (FET outputs)
MDTM89-D: 120 VAC (MDTM89-C with 120 V isolation module #IT-1)
(FET outputs.) Model NOT approved by CSA
Power Consumption: CD ignition: 350 μa @ 100V; 120 VAC: 0.6 watts;
24 VDC: 0.5 watts
Outputs:
Model B: Output turns on above trip point; output turns off when power is switched off; two (2) isolated SCR outputs, 0.5 amp @ 250 VDC
Models A, C and D: _Output turns on above trip point; output turns off below trip point; two (2) isolated FET outputs, 0.5 amp @ 250 VDC
Model E: Output one turns on above trip point, output turns off below trip point: output 2 turns on below trip point, output turns off above trip point: two (2) isolated FET outputs, 0.5 amp @250 VDC
Ambient Cold Junction Compensation Range: 32° to 122° F (1° C from 0° to 50° C)
Operating Temperature: -4° to 158° F (-20° to 70° C)
Storage Temperature: -40° to 300° F (-40° to 150° C)
Case: Die-cast aluminum
Reset Differential: FET models: decreases 3 degrees (°F or °C)
SCR model: Turn input power off to reset
Measurement Range: Monitor range 0°-1999° F or ° C (specify F or C in part number)
Accuracy: With J-type thermocouple: from 150°-1200° F (66°-649° C) ±1.5% of reading. With K-type thermocouple: from 400°-2000° F (204- 1076° C) ±1.5% of reading. At calibration temperature.
Laboratory Approvals: CSA approved for Class I, Division 2, Group D, hazardous locations
Thermocouple Lead Length:
150 ohm lead resistance affects monitor accuracy less than 1°
Trip Point Accuracy: ±3° F (±2° C) of reading
Trip Point Adjustment Range: 0-1999 degrees

*Approved for CD ignition, 80–250 VDC.

In order to consistently bring you the highest quality, full-featured products, we reserve the right to change our specifications and designs at any time.
FW MURPHY product names and the FW MURPHY logo are proprietary trademarks. This document, including textual matter and illustrations, is copyright protected with all rights reserved. (c) 2022 FW MURPHY. A copy of our typical warranty may be viewed or printed by going to www.fwmurphy.com/warranty.

**FW MURPHY PRODUCTION CONTROLS**
SALES, SERVICES & ACCOUNTING
4646 S. HARVARD AVE.
TULSA, OK 74135

MANUFACTURING
2151 RANDON DYER ROAD
ROSENBERG, TX 77471

5757 FARINON DRIVE
SAN ANTONIO, TX 78249

**DOMESTIC SALES & SUPPORT**

FW MURPHY PRODUCTS
PHONE: 918 957 1000
EMAIL: INFO@FWMURPHY.COM
WWW.FWMURPHY.COM

FW MURPHY CONTROL SYSTEMS & SERVICES
PHONE: 281 633 4500
EMAIL: CSS-SOLUTIONS@FWMURPHY.COM

**INTERNATIONAL SALES & SUPPORT**

CHINA
PHONE: +86 571 8788 6060
EMAIL: INTERNATIONAL@FWMURPHY.COM

LATIN AMERICA & CARIBBEAN
PHONE: + 1 918 770 8775
EMAIL: INTERNATIONAL@FWMURPHY.COM

SOUTH KOREA
PHONE: +82 70 7951 4100
EMAIL: INTERNATIONAL@FWMURPHY.COM

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals