FW MURPHY OPLC Pressure Gauge Instruments Instruction Manual
- June 4, 2024
- FW MURPHY
Table of Contents
Pressure Gauge Instruments
Instruction Manual
Pressure Gage Instruments 4-1/2 in. (114 mm) Dial Installation and Operation
Instructions.
Models: OPLC, OPLFC, OPLBP, OPLFG, 45APE, 45APEF and PT167EX
Please read the following instructions before installing. A visual inspection
of this product for damage during shipping is recommended before mounting. It
is your responsibility to have a qualified person install the unit.
Before Beginning Installation of this Product:
- Disconnect all electrical power to the machine.
- Make sure the machine cannot operate during installation.
- Follow all safety warnings of the machine manufacturer.
- Read and follow all installation instructions.
OPLC and OPLFC gage instruments have high and low limit contacts to
monitor, alarm or shut down. The OPLC has a flanged case. A method to override
the low-limit contact for a start-up is provided on OPLC models. See Operation
Test Instructions.
OPLFC can be direct or panel mounted. OPLFG gage indication-only pressure
instrument is similar to OPLFC models, without switch (limit) contacts.
OPLBP is a version of the OPLC featuring pilot duty limit switches
connected to an internal latching control relay for on/off control directly or
through a motor starter. -OS and -ES options include oil sealed and
environment sealed case for corrosive environments, feature a panel mount case
or screw directly into the process. 45APE and 45APEF are versions of the OPLC
Series featuring 2 snap-acting SPDT switches instead of the pointer-type
contacts.
These units do not include low contact lockout.
PT167EX is a pressure switch gauge instrument connected to a threaded
pressure diaphragm housing. The instrument is enclosed in an explosion-proof
case and CSA rated for Class I, Division 1, Groups C and D.
Installation Precautions:
- Do NOT exceed rated pressure range.
- Dope or use teflon tape on connection threads.
- Do not block the inlet orifice.
- For direct mounting into the process, a vertical or ninety-degree mounting is recommended.
- Use the wrench on the shank to tighten or loosen the connection.
- Do not twist case when installing, this will damage internal components and will void the warranty.
- Do not over-tighten.
- Use shock mounts as necessary to prevent excessive vibration.
- If the liquid in the system freezes, it will expand and will damage the tube.
- For 45APE Series – Low setpoint should be limited to the lower 1/2 scale and upper setpoint should be limited to the upper 1 /2 scale.
Specifications
Dial: White on black, dual scale, psi/kPa standard, 4-1 /2 in. (114 mm)
diameter
Case: Die cast aluminum, surface or panel mount Process Connection:
1/4 NPTM to 1000 psi; 1/2 NPTM 1500-10,000 psi. Sensing Element: Bronze or 316
stainless steel bourdon tube Snap-Acting Switches: See wiring information
(45APE/45APEF) Overrange: Do not exceed 10% FS above full range Pressure
Relief Disc: Back of case (except EX models) Dry Relay Contact: OPLBP, 10 A@
120 VAC
Wire Connections (Surface Mount): 1/2 NPTF conduit entry with terminal block
Wire Connections (Panel Mount): Wire leads, 18 AWG (1.0 mm 2 ) x 9 in. (229
mm) long
Wire Connections (-ES, -OS): 1/2 NPTM conduit and wire leads, OPLFC Series: 18
AWG (1.0 mm 2 ) x 33 in. (838 mm) long Switch Point Accuracy: ± 1.5%
45APE/45APEF) Switch Reset Deadband: Approximately 10% FS (45APE/45APEF)
Gage Accuracy:
All models between switch points: ± 2% for first and last quarters of scale; middle half of scale is ± 1 % Based on testing performed with switch point at mid-scale which represents the worst case.45APE/45APEF Accuracy Outside Switch Points.
Range | Accuracy Above or Below Trip Point |
---|---|
<100 | 10 |
100-300 | 4 |
400-1500 | 2 |
2000 | 12 |
3000-5000 | 8 |
OPLC Series Wall Mount
Flanged case design intended for wall mount, it can also be direct mounted.
Shown with shock mounts and pulsation dampener.
OPLFC Series Flush Mount
Round case design to be mounted in a panel from 1/32 in. (1 mm) to 1/8 in. (3
mm) thick. It can also be direct mounted.
45APE Series Wall Mount
45APEF Series Flush Mount
Options -OS and -ES Flush Mount
Explosion-proof Case Mount
The explosion-proof case can be mounted from face or rear.
Wiring Information
Before Beginning Wiring of this Product:
- Perform the wiring operation with the power source OFF.
- Secure the area to be non-hazardous.
- Make sure the voltage and current requirements are within the contact ratings.
- Determine voltage and polarity for the application.
- Use the appropriate wire size.
- All connections should be made using spade (forked) or ring terminals.
- For pigtail connections use wire nuts.
- A conduit is recommended to protect wires from damage.
45APE and 45APEF
Contact Rating:
2 SPDT Snap-switches (one for high and low pressure), 2 A inductive, 250 VAC
each switch.
NOTE: Indication pointer shown at rest ( shelf) position. The low
setpoint should be limited to the lower 1/2 scale and upper setpoint should be
limited to the upper 1/2 scale.
OPLBP
Contact Rating:
SPDT, Dry Relay Contacts 10 A, 125 VAC. NOTE: Indication pointer shown at rest
(shelf) position.
OPLC and OPLFC
Contact Rating: 1 SPDT, Center Off; 2 A, 30 VDC / 0.1 A, 125 VAC pilot duty.
NOTE: Indication pointer shown at rest (shelf) position.
Making Adjustments
OPL Series Limit Contact Adjustments
Facing the dial, the left side knob is the Low limit contact and the High
limit contact is located to the right. To set the limit contacts simply tum
the fingertip-type knob to the desired point on the scale.
OPL Series Indicating Point Adjustments
To reset to zero or to a known value do as follows:
- Tum off electrical power. Remove the snap ring and very carefully remove the lens and contact assembly ( or open hinged cover).
- Hold the pointer hub with the thumb and forefinger then turn screw to the desired point. See DETAIL A.
- Replace lens and contact assembly and snap ring (or close hinged cover), and turn on the power.
45APE Series Trip Point Adjustments
The 45APE Series features a stacked limit indicator adjustments knob. The
bottom half knob adjusts the Low limit indicator, the top half is to adjust
the High limit indicator. To set the limit contacts simply tum the fingertip-
type knob to the desired point on the scale.
45APE Series Pointer Adjustments (if necessary)
Verify that pointer is at zero with zero pressure. To reset to zero or to a
known value proceed as follows:
- Tum off electrical power. Remove the snap ring and very carefully remove the lens and contact assembly (or open hinged cover).
- Hold the Switch Operator and the pointer hub with your thumb and forefinger, then tum the Pointer Adjustment screw to the desired point. See DETAIL B.
- If the Switch Operator needs adjustment, hold the Switch Operator and the pointer hub with the thumb and forefingers as shown on DETAIL C, and turn the adjustment screw until the Switch Operator aligns with the indicating pointer.
- Replace the lens and contact assembly and the snap ring (or close the hinged cover). Turn the power back on.
CAUTION: Don’t rotate set point arms past stop pins in a circle.
Operation Test Instructions
OPLC, OPLFC and OPLBP
- Perform operation test after the unit is installed and wired appropriately.
- When pressure is applied to the instrument, the pointer will travel in a clockwise direction. Adjust the limit contacts to the desired settings.
- To start, place the toggle switch in the START position or otherwise override low contact.
- After the indication pointer rises above the low limit contact, return the toggle switch or override device to the RUN position.
- To test the limit contacts, turn the limit contact to be tested until it touches the pointer. That will trip the control circuit.
- Reset the shutdown or alarm circuit device and repeat the above sequence for each contact/trip point.
- For the OPLC and OPLBP models, to maintain the NEMA 3R rating, torque the two cover screws down from 27 to 35 in. lbs after installation and testing are complete.
45APE and 45APEF
- Perform operation test after the unit is installed and wired appropriately.
- When pressure is applied to the instrument, the pointer will travel in a clockwise direction. Adjust the limit contacts to the desired settings.
- To test the switches, tug the trip point indicator until it is aligned with the switch gage pointer. This is the approximate trip point. Continue to rotate until the snap switch operates.
- Reset the shutdown or alarm circuit device.
In order to consistently bring you the highest quality, full-featured products. we reserve the right to change our specifications and designs at any time. FW MURPHY product names and the FW MURPHY logo are proprietary trademarks. This document includes textual matter and illustrations. is copyright protected with all rights reserved? (c) 2022 FW MURPHY. A copy of our typical warranty may be viewed or printed by going to www.fwmurphy.com/warranty.
FW MURPHY PRODUCTION CONTROLS
SALES, SERVICES & ACCOUNTING 4646 S. HARVARD AVE
TULSA, OK 74135
MANUFACTURING
2151 RANDON DYER ROAD ROSENBERG, TX 77471
5757 FARINON DRIVE SAN ANTONIO, TX 18249| DOMESTIC SALES & SUPPORT
FW MURPHY PRODUCTS
PHONE: 918 957 1000
EMAIL: INFO@FWMURPHY.COM
WWW.FWMURPHY.COM
FW MURPHY CONTROL SYSTEMS & SERVICES
PHONE: 281 633 4500
EMAIL: CSS-SOLUTIONS@FWMURPHY.COM|
INTERNATIONAL SALES & SUPPORT
CHINA
PHONE: +86 571 8788 6060
EMAIL: INTERNATIONAL@FWMURPHY.COM
LATIN
AMERICA & CARIBBEAN
PHONE: +1918 770 8775