JCC JC110001 Emergency Range Instruction Manual
- June 4, 2024
- JCC
Table of Contents
JCC JC110001 Emergency Range
Installation instructions for JC110001 Emergency Bulkhead
Warnings & Cautions
-
To avoid electric shock, serious injury or property damage,isolate power before installing, removing or servicing the product.
-
It is recommended that luminaires are installed by a qualified electrician to ensure the installation complies with the local current wiring regulations.
-
It may be necessary to upgrade your MCBs to allow for increased inrush current.
-
This product is designed for connection to a 100-240V~ 50/60Hz.
-
It is recommended that the ambient room temperature should not exceed 26°C.
-
All testing should be carried out in accordance to EN 50172:2004
-
The light source of this luminaire is not replaceable: when the light source reaches the end of its life the whole of the luminaire must be replaced.
-
Read instructions and check that you have all of the tools and accessories required to complete the installation correctly.
Isolate power supply before starting installation. -
Do not carry out insulation tests with the product connected to the circuit.
-
Any broken or damaged parts should be replaced as soon as possible. JCC will not accept responsibility for claims arising from sub-standard installations; which will void the warranty.
-
This luminaire is suitable for indoor and outdoor use.
INSTALLATION
- 3W 100-240V~ 50/60Hz – Class II
- Colour temp: 7000K Ra: 84
- Wire preparation: 1-2.5 mm²
- Light source: Integral LED
- Wattage:3W
- Lumens: 120 lumens
Maintained(3M)
+ on/off Switched
+ Emergency
Maintained(3M)
+ Light on 24/7
+ Emergency
(linked)
Non-Maintained(3NM)
+ Light off 24/7
+ Emergency
(remove link)
-
Remove the two screws holding the diffuser to gain access to the interior.
-
Release the LED tray to access the mains input terminal by pressing the quick release tabs. This is hinged so the LED tray remains attached to the body.
-
Cable entry is available through rear, top and bottom or both ends.
Ensure appropriate grommets or compression couplings are used to maintain the IP65 rating where required. -
Connect the mains input supply as indicated on the above as per the required operation.
-
Connect the emergency battery leads to the circuit board where indicated.
-
Close the LED tray, ensuring it is secured using the securing tabs.
-
Refit the diffuser ensuring there is a good seal to maintain the IP65 rating.
-
Switch on mains supply and test for operation(allow 24hrs for batteries to charge). Charging and normal operation is indicated when the green light is on
-
Fit the legends on the front of the diffuser to suit the application from the three choices indicated on the right which are included.
-
Familiarise yourself with the enclosed emergency fittings test record sheet and ensure it is completed as required and left with the end user.
Supplied legends:
1 x left running man, 1 x right running man, 1 x directional arrow
Profile & Dimensions
All dimensions in millimetres
Non-replaceable control gear
Non-replaceable light source
Important warranty information
This product is supported by a 2-year standard warranty which will extend to 5
years if registered within the first year of purchase.
(5 year on batteries). Please register at jcc.co.uk/warranty – Terms and
conditions apply.
The installer will be asked to provide the following information, which is
detailed on a label attached to the luminaire’s chassis:
Product Code/Date Code.
BS EN ISO9001 – 2015 – Registered Firm Certificate No. GB 1552
JCC Lighting Products Ltd. Innovation Centre, Beeding Close, Southern Cross
Trading Estate, Bognor Regis, West Sussex, PO22 9TS, United Kingdom
Emergency Test Record
Installation Engineers: …………………………………………….
Luminaire Type: ………………………………………………………
Location: ………………………………………………………………..
Tel: ……………………………………………………
Batch Number: ……………………………………
Installation Date: ………………………………..
General Information
These instructions contain important information regarding safety. They
should be read carefully and retained at the installation for future
reference.The company will not accept any responsibility for any injury,
damage or loss that may arise as a result of incorrect installation, operation
or maintenance due to the non-adherance to these instructions. Our products
are designed to comply with the requirements of UK law and the relevant
industry national and international standards and should not be modified in
any way. All emergency lighting systems should comply with the recommendations
of BS5266-1: Code of Practice for the Emergency Lighting of Premises and be
installed by competent engineers in accordance with the relevant wiring
regulations. Before installing any type of Emergency Lighting always seek the
advice and approval of the local Fire Prevention Officer (or equivalent
authority).
Maintenance
Failed or faulty light sources connected to this equipment should be replaced
immediately. These units are designed especially for a long and trouble free
life and, under normal conditions, will require no routine maintenance or
service beyond the inspection and test regime of BS5266-1.
Both mains supply and battery protection fusing is incorporated internally.
Should access to these or any other part of the circuitry be required this
must be undertaken only by suitably qualified personel. Special care must be
taken when removing the cover to circuitry and battery. Only replacement
components authorised by the company must be used. Disposal of replaced
components should be in accordance with the component manufacturers
instructions.
Routine Inspection and Test
All tests must be undertaken at times of least risk and in accordance with EN
50172:2004 as indicated below:
Daily: Indicators of central power supply shall be visually inspected for
correct operation.
Monthly: (in addition to the daily check)
If automatic testing devices are used, the results of the short-duration tests
shall be recorded.
Test shall be carried out as follows:
a) Switch on in the Emergency mode each luminaire and each internally
illuminated exit sign from its battery by simulation of a failure of supply to
the normal lighting for a period sufficient to ensure that each lamp is
illuminated.
NOTE: The period of simulation failure should be sufficient for the
purpose of this clause whilst minimising damage to the system components e.g
lamps During this period, all luminaires and signs shall be checked to ensure
that they are present, clean and functioning correctly. At the end of this
test period, the supply to the normal lighting should be restored and any
indicator lamp or device should be checked to ensure that is showing that the
normal supply has been restored.
Annually:
If automatic testing devices are used, the results of the short-duration tests
shall be recorded. For all other systems the monthly inspection shall be
carried out and the following additional tests made:
a) each luminaire and internally illuminated sign shall be tested Monthly
as above but for its full duration in accordance with the manufacturer’s
information;
b) the supply of the normal light shall be restored and any indicator
lamp or device checked to ensure that it shows the normal supply has been
restored. The charging arrangements should be checked for proper functioning;
c) the date of the test and its results shall be recorded in the system
logbook.
A copy of this report must accompany any fitting returned to the manufacturer
for any reason.
Month | Test Type | First Year | Second Year | Third Year | Fourth Year | Fifth Year |
---|---|---|---|---|---|---|
Sign | Date | Sign | Date | Sign | Date | Sign |
January | Functional | |||||
February | Functional | |||||
March | Functional | |||||
April | Functional | |||||
May | Functional | |||||
June | Functional | |||||
July | Functional | |||||
August | Functional | |||||
September | Functional | |||||
October | Functional | |||||
November | Functional | |||||
December | 3 hour |
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>