JCC Lighting RadiaLED Rapid Range Instruction Manual
- June 9, 2024
- JCC Lighting
Table of Contents
RadiaLED® Rapid Range
RadiaLED® bulkhead body and LED module
Instruction Manual
RadiaLED Rapid Range
WARNINGS AND CAUTIONS
- To avoid electric shock or serious injury or property damage, isolate power before installing, removing or servicing the product
- It is recommended that this product is installed by an electrician or a competent person with sufficient experience to install this product
- To be installed in accordance with the local current wiring regulations and standards
- Any broken or damaged parts should be replaced as soon as possible
- JCC will not accept responsibility for claims arising from sub-standard installations; which will void the warranty
- Ensure that you have the tools and accessories required to complete the installation correctly
- This luminaire is suitable for indoor use or exterior use, wall or ceiling mounting
- Do not install in areas that are near to continual running water
- Do not carry out insulation tests with the LED module connected to the circuit
INSTALLATION INSTRUCTIONS
Note: This instruction sheet is for installing the LED Bulkhead body and
LED module-which are purchased separately- it requires the installer to
connect the LED Module’s wiring to the terminal block in the Bulkhead body in
addition to the mains input wiring
Mains supply Input : 220-240V~ 50/60Hz Class 2 with earth provision EM
versions Class I
Wattage | CCT | CRI:Ra | Lumens | LpcW |
---|---|---|---|---|
8W | 4000K | 84 | 760 | 95 |
8W | 3000K | 84 | 760 | 95 |
12W | 4000K | 84 | 1250 | 104 |
12W | 3000K | 84 | 1250 | 104 |
16W | 4000K | 84 | 1600 | 100 |
16W | 3000K | 84 | 1600 | 100 |
24W | 4000K | 84 | 2160 | 90 |
24W | 3000K | 84 | 2160 | 90 |
Standard operation mode | **Battery charging operation mode (initial | |||
charge 24hrs)** | Parasitic Power | |||
--- | --- | --- | ||
8W | 12W(8W+4W) | 0.5W | ||
12W | 16W(12W+4W) | 0.5W | ||
16W | 20W(16W+4W) | 0.5W | ||
24W | 28W(24W+4W) | 0.5W |
- Isolate power supply.
- Ensure that the body is installed in the correct orientation if wall mounted as indicated by the “THIS WAY UP” arrow inside the body(see fig.1.)This will ensure that the LED module is suspended correctly below the body when installing.(See fig.6.)
- Mains input cable entry options are in the centre of the body(see fig.2.)or 4 conduit entry point options on the side of the body(see fig.3.), you will need to drill a Ø20mm hole and use the supplied grommet(s) to maintain the IP rating of the fitting. It is recommended to drill this from the back of the body.
- To secure the body to the mounting surface you will also need to drill pilot holes of Ø4-6mm to accomodate the fixing screws. There are two mounting options: 4 x direct to the mounting surface or by using the option for BESA mounting in the centre of the body. The counter sunk molded fixing points are around the outside edge of the interior of the body adjacent to four conduit side entry points (see fig.3.) and in the centre for BESA mounting(see fig.2.)
- Connect the mains input into the terminal block in the body(see fig.4.) Terminal block is loop-in /loop-out to allow for continuous wiring.(Insulation tests can be carried out at this point) then suspend the LED Module from the security strap support(see fig.6.)
- Once insulation tests are complete, connect the wires from the LED module to the corresponding mains wires on the opposite side of the terminal block marked ”output to driver”
- For DALI/1-10V versions connect dimming controls to the dimming control input by removing the driver terminal cover and connect to either DA+/DA- for DALI or 1-10V connect to 1-10Vdc +/- then refit driver cover
MAINS INPUT
L¹ = Unswitched Live
L = Switched Live
= Earth(EM versions)
N = Neutral| OUTPUT TO LED DRIVER(MODULE)
L¹ = Unswitched Live
L = Switched Live
= Earth(EM versions)
N = Neutral
---|--- - For emergency versions, the batteries are enclosed in the invertor and are already connected so do not require commissioning.
- Once you have completed all of the connections, fit LED tray into the body by aligning the 4 slots and press into place until clipped in.
- To fit the diffuser align the 4 captive screws in the diffuser with the holes in the body which have corresponding lugs for alignment(see fig.5.). Ensure that the screws are not over-tightened as this could damage the gasket and effect the IP rating.
- Turn on mains supply and test operation( allow 24hrs for the battery to charge before testing emergency operation)
Emergency range routine inspection and test
All tests must be undertaken at times of least risk and in accordance with EN
50172:2004 as indicated below:
Weekly: Indicators of central power supply shall be visually inspected
for correct operation.
Monthly: (in addition to the daily check) If automatic testing devices
are used, the results of the short duration tests shall be recorded. Test
shall be carried out as follows:
a) Switch the luminaire over to emergency mode to operate from the
batteries by simulating a failure of supply to the normal lighting for a
period sufficient to ensure correct luminaire operation
NOTE: The period of simulation failure should be sufficient for the
purpose of this clause whilst minimising damage to the system components e.g
lamps. During this period, all luminaires and signs shall be checked to
ensure that they are present, clean and functioning correctly. At the end of
this test period, the supply to the normal lighting should berestored and any
indicator lamp or device should be checked to ensure that is showing that the
normal supply has been restored.
Annually: If automatic testing devices are used, the results of the short
duration tests shall be recorded. For all other systems the monthly inspection
shall be carried out and the following additional tests made:
a) Each luminaire and internally illuminated sign shall be tested monthly
as above but for its full duration in accordance with the manufacturer’s
information.
b) The normal supply for the luminaire should be restored and any charge
indicator lamp or device should be checked to ensure that it shows the normal
supply has been restored. The charging arrangements should be checked for
proper functioning.
c) The date of the test and its results shall be recorded in the system
logbook.
A copy of this report must accompany any fitting returned to the manufacturer
for any reason.
General Information
Our products are designed to comply with the requirements of UK law and the relevant industry national and international standards and should not be modified in any way. All emergency lighting systems should comply with the recommendations of BS5266-1: Code of Practice for the Emergency Lighting of Premises and be installed by competent engineers in accordance with the relevant wiring regulations. Before installing any type of Emergency Lighting always seek the advice and approval of the local Fire Prevention Officer (or equivalent authority).
Maintenance
Failed or faulty light sources connected to this equipment should be replaced
immediately. These units are designed especially for a long and trouble free
life. Under normal conditions, will require no routine maintenance or service
beyond the inspection and test regime of BS5266-1.
Both mains supply and battery protection fusing is incorporated internally.
Should access to these or any other part of the circuitry be required this
must be undertaken only by suitably qualified person. Special care must be
taken when removing the cover to circuitry and battery. Only replacement
components authorised by the company must be used. Disposal of replaced
components should be in accordance with the component manufacturers
instructions.
You can help protect the environment. Please remember to respect the local
regulations: hand in the non-working electrical equipment to an appropriate
waste disposal centre.
The packaging material is recyclable. Dispose of the packaging in an
environmentally friendly manner and make it available for the recyclable
material collection service.
when installed
V14_June_2022_RS
jcc.co.uk
Profile & Dimensions
Wattage | A | B | C | D |
---|---|---|---|---|
8W | Ø232.1 | 93.3 | Ø274 | 93.3 |
12W/16W/24W | Ø301 | 98.3 | Ø340 | 98.3 |
All dimensions in millimetres
Emergency test record sheet
Month | Test Type | First Year | Second Year | Third Year | Fourth Year | Fifth Year |
---|---|---|---|---|---|---|
Sign | Date | Sign | Date | Sign | Date | Sign |
January | Functional | |||||
February | Functional | |||||
March | Functional | |||||
April | Functional | |||||
May | Functional | |||||
June | Functional | |||||
July | Functional | |||||
August | Functional | |||||
September | Functional | |||||
October | Functional | |||||
November | Functional | |||||
December | 3 hour |
Photocell operation and settings
When ambient light level is below the “On” lux level selected, the sensor
automatically switches on the luminaire at 100% brightness.
When ambient light level is higher than the “Off” lux level selected, the
sensor automatically switches off the luminaire.
When set to disable, the sensor does not work.
| | 1| 2| 3| 4| On@| Off@
---|---|---|---|---|---|---|---
I| On| On| On| On| 5Lux| 25Lux
II| On| On| On| –| 10Lux| 50Lux
III| On| On| –| On| 25Lux| 75Lux
IV| On| On| –| –| 50Lux| 100Lux
V| On| –| On| –| 100Lux| 200Lux
VI| On| –| –| –| 150Lux| 300Lux
VII| –| On| –| –| 200Lux| 400Lux
VIII| –| –| –| –| Disable
Microwave on/off operation and settings
I: Up to 8m
II: Up to 6m
III: Up to 4m
VI: Up to 2m
| | 1| 2|
---|---|---|---|---
I| On| On| 100%
II| On| –| 75%
III| –| On| 50%
IV| –| –| 25%
Hold Time
| | 3| 4| 5|
---|---|---|---|---|---
I| On| On| On| 5s
II| On| On| –| 30s
III| On| –| On| 1min
IV| On| –| –| 3min
V| –| On| On| 5min
VI| –| On| –| 10min
VII| –| –| On| 20min
VIII| –| –| –| 30min
Refers to the time period the lamp remains at 100% illumination after no
motion detected.
I: 2lux (darkness operation only)
II: 10lux (Darkness operation only)
III: 25lux (twilight operation)
IV: 50lux (twilight operation only)
V: Disable* (darkness operation only)
Daylight Sensor
| | 6| 7| 8|
---|---|---|---|---|---
I| On| On| On| 2Lux
II| On| On| –| 10Lux
III| –| On| –| 25Lux
IV| On| –| –| 50Lux
V| –| –| –| Disable
*When set to Disable mode, the daylight sensor will switch on the lamp when motion is detected regardless of ambient light levels.
Important warranty information
This product is supported by a 2-year standard warranty which will extend to
5-years if registered within the first year of purchase.
(2 year on batteries). Please register at jcc.co.uk/warranty (Terms and
conditions apply).
The installer will be asked to provide the following information, which is
detailed on a label attached to the luminaire’s chassis:
Product Code/Date Code.
Note: Both the body and module must be registered to ensure that the
warranty is extended.BS EN ISO9001 – 2015 – Registered Firm Certificate
No. GB 1552
Microwave Dimming operation and settings – 8W/12W/16W /24W
Detection Area
****| | 1| 2|
---|---|---|---|---
I| On| On| 100%
II| –| On| 75%
III| On| –| 50%
IV| –| –| 10%
Ø16m x 6m High max
Detection area can be reduced by selecting the combination on the DIP switches
to fit precisely each application.
Hold Time
| | 3| 4|
---|---|---|---|---
I| On| On| 5s
II| –| On| 90s
III| On| –| 3min
IV| –| –| 10min
Refers to the time period the lamp remains at 100% illumination after no
motion is detected.
Daylight Sensor
| | 5| 6|
---|---|---|---|---
I| On| On| Disable
II| –| On| 50Lux
III| On| –| 15Lux
IV| –| –| 5Lux
The sensor can be set to only allow the lamp to illuminate below a defined
ambient brightness threshold. When set to Disable mode, the daylight sensor
will switch on the lamp when motion is detected regardless of ambient light
level. 50Iux: twilight operation, 15Iux, 5Iux: darkness operation only.
Corridor function(Stand-by period)
| | 7| 8|
---|---|---|---|---
I| On| On| 0s
II| –| On| 30s
III| On| –| 10min
IV| –| –| +∞
Refers to the time period the lamp remains at a low light level before it
completely switches off in the long absence of any occupancy. When set to ”
+∞ ”, the low light is maintained until motion is detected -Step Dim
Function. When set to “Os”, the light will turn off after hold time.
Stand-by DIM Level
This is pre-set at 20% and not adjustable
JCC Lighting Products Ltd.,
Innovation Centre, Beeding Close, Southern Cross Trading Estate, Bognor Regis,
West Sussex, PO22 9TS, United Kingdom
Technical Support: +44(0)1243 838986
Customer Services: +44(0)1243 838999
Documents / Resources
| JCC
Lighting RadiaLED Rapid
Range
[pdf] Instruction Manual
RadiaLED Rapid Range, Rapid Range, RadiaLED Rapid, Range, RadiaLED
---|---
| JCC
Lighting RadiaLED Rapid
Range
[pdf] Instruction Manual
RadiaLED Rapid Range, Rapid Range, RadiaLE, Range
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>