JCC Commercial Wall Bulkhead Instruction Manual
- May 15, 2024
- JCC
Table of Contents
Commercial Wall Bulkhead
Installation instructions for Wall Pack
Warnings & Cautions
-
It is recommended that luminaires are installed by a qualified electrician to ensure the installation complies with the local current wiring regulations
-
Do not install in areas that are exposed to continual running water or prone to flooding. Ensure that the mounting surface is both flat and stable
-
These products are designed for connection to a 220-240V~ 50/60Hz supply.
-
Any broken or damaged parts should be replaced as soon as possible.
JCC will not accept responsibility for claims arising from sub-standard installations -
It may be necessary to upgrade your MCBs to allow for increased inrush current.
-
This luminaire is suitable for outdoor use.
INSTALLATION
Specifications Colour temp: 4000K Ra: 80
Total circuit wattage | Lumens | LpcW |
---|---|---|
20W | 2000 | 100 |
30W | 2900 | 97 |
Beam angle: 110°
220-240V~ 50/60Hz Class I
Figure 1. Mains input
Standard versions
Emergency version
SL= Switched live
PL= Permanent live
Terminal block must comply to EN 60998-2-1 or EN 60998-2-2
Operating lux level for Photocell versions
| Dusk (on)| Dawn (off)
---|---|---
20W| 10-20lux| 30-80lux
30W| 10-20lux| 30-60lux
General Maintenance Requirements
This product has no user servicable parts. JCC Lighting Products would
recommend that the following maintenance is performed in order to prolong the
life of this product: Clean with a damp cloth and dry with a lint free cloth
or kitchen towel.
Do not use abrasive cleaners.
- Read instructions and check that you have all of the tools and accessories required to complete the installation correctly. Isolate power supply before starting the installation.
Installation procedure
- Remove cover by loosening all screws.
- Drill mounting holes and insert suitable wall plugs.
- Prepare the mains input cable for termination. Note that this product is class I and as such must be fitted with an earth connection.
- Terminate input wiring to the fitting as per Fig. 1.
- For emergency version, connect the battery connector lead to the invertor.
- Secure in desired location.
- Refit the cover and ensure the seal is correctly seated to maintain IP65 rating.
- Turn on power supply and test for correct operation.
Note – optimum mounting height – 3m
It is the responsibility of the installer to maintain the IP rating when mounting and connecting the mains.
Emergency version
Familiarise yourself with the enclosed emergency fittings test record sheet
and ensure it is completed as required and left with the end user.
Profile & Dimensions
| A| B| C| D
---|---|---|---|---
20W| 206| 188| 222| 85
30W| 288| 264| 308| 126
All dimensions in millimetres
You can help protect the environment. Please remember to respect the local
regulations: hand in the non-working electrical equipment to an appropriate
waste disposal centre. The packaging material is recyclable. Dispose of the
packaging in an environmentally friendly manner and make it available for the
recyclable material collection service.
Important warranty information
This product is supported by a 2-year standard warranty which will extend to
5-years if registered within the first year of purchase.
(2 year on batteries). Please register at jcc.co.uk/warranty (Terms and
conditions apply).
The installer will be asked to provide the following information, which is
detailed on a label attached to the luminaire’s chassis:
Product Code/Date Code.
BS EN ISO9001 – 2015 – Registered Firm Certificate No. GB 1552
JCC Lighting Products Ltd. Lux Park, Chichester Business Park, City Fields
Way, Tangmere, Chichester, West Sussex, PO20 2FT
Technical Support: +44(0)1243 838986 Customer Services: +44(0)1243 838999
Emergency Range Routine Inspection & Test
All tests must be undertaken at times of least risk and in accordance with EN
50172:2004 as indicated below:
Daily: Indicators of central power supply shall be visually inspected for
correct operation.
Monthly: (in addition to the daily check) If automatic testing devices are
used, the results of the short duration tests shall be recorded. Test shall be
carried out as follows:
a) Switch the luminaire over to emergency mode to operate from the batteries
by simulating a failure of supply to the normal lighting for a period
sufficient to ensure correct luminaire operation
NOTE: The period of simulation failure should be sufficient for the
purpose of this clause whilst minimising damage to the system components e.g
lamps. During this period, all luminaires and signs shall be checked to ensure
that they are present, clean and functioning correctly.
At the end of this test period, the supply to the normal lighting should be
restored and any indicator lamp or device should be checked ensure that is
showing that the normal supply has been restored.
Annually: If automatic testing devices are used, the results of the short
duration tests shall be recorded.
For all other systems the monthly inspection shall be carried out and the
following additional tests made:
a) Each luminaire and internally illuminated sign shall be tested monthly as
above but for its full duration in accordance with the manufacturer’s
information.
b) The normal supply for the luminaire should be restored and any charge
indicator lamp or device should be checked to ensure that it shows the normal
supply has been restored.The charging arrangements should be checked for
proper functioning.
c) The date of the test and its results shall be recorded in the system
logbook.
A copy of this report must accompany any fitting returned to the manufacturer
for any reason.
General Information
Our products are designed to comply with the requirements of UK law and the
relevant industry national and international standards and should not be
modified in any way. All emergency lighting systems should comply with the
recommendations of BS5266-1: Code of Practice for the Emergency Lighting of
Premises and be installed by competent engineers in accordance with the
relevant wiring regulations.
Before installing any type of Emergency Lighting always seek the advice and
approval of the local Fire Prevention Officer (or equivalent authority).
Maintenance
Failed or faulty light sources connected to this equipment should be replaced
immediately. These units are designed especially for a long and trouble free
life. Under normal conditions, will require no routine maintenance or service
beyond the inspection and test regime of BS5266-1.
Both mains supply and battery protection fusing is incorporated internally.
Should access to these or any other part of the circuitry be required this
must be undertaken only by suitably qualified person. Special care must be
taken when removing the cover to circuitry and battery. Only replacement
components authorised by the company must be used. Disposal of replaced
components should be in accordance with the component manufacturers
instructions.
Emergency Test Record Table
Month | Test Type | First Year | Second Year | Third Year | Fourth Year | Fifth Year |
---|---|---|---|---|---|---|
Sign | Date | Sign | Date | Sign | Date | Sign |
January | Functional | |||||
February | Functional | |||||
March | Functional | |||||
April | Functional | |||||
May | Functional | |||||
June | Functional | |||||
July | Functional | |||||
August | Functional | |||||
September | Functional | |||||
October | Functional | |||||
November | Functional | |||||
December | 3 hour |