JCC JC71741 Skypack QR Range Instruction Manual

October 27, 2023
JCC

JCC logo JC71741 Skypack QR Range
Instruction ManualJCC JC71741 Skypack QR Range

Skypack™ QR Range
Installation instructions for Skypack™ LED Battens

Warnings & Cautions

  • To avoid electric shock, serious injury or property damage, isolate power before installing, removing or servicing the product.
  • It is recommended that luminaires are installed by a qualified electrician to ensure the installation complies with the local current wiring regulations.
  • It may be necessary to upgrade your MCBs to allow for increased inrush current.
  • This luminaire is suitable for indoor use only.
  • This product cannot be covered with insulation material – do not cover.
  • Any broken or damaged parts should be replaced as soon as possible. JCC will not accept responsibility for claims arising from sub-standard installations; which will void the warranty.
  • Emergency product routine inspection and tests must be undertaken at times of least risk and in accordance with EN 50172:2004. A copy of this report must accompany any fitting returned to JCC for any reason.

INSTALLATION

  1. To remove the diffuser and LED tray from the body press both the release buttons at each end of the fitting as shown in Fig. 1.

  2. The diffuser and LED tray is secured to the body with security tabs, which will support the diffuser when installing the body.

  3. Secure the fitting in the desired postion either using the fixing points or BESA plates for conduit mounting.

  4. Terminate the wiring into the press fit terminal as shown in Fig. 2 or into fused terminal for the emergency version as shown in Fig. 3.

  5. Connect DALI or 1-10V dimming controls indicated as per Fig. 2(A)

  6. Connect batteries on emergency version (allow a full 24 hours for batteries to charge prior to testing). Please refer to periodic test procedure on page two.

  7. Refit the front cover by aligning the diffuser with the body and click into place.

  8. Turn on the mains supply and check operation.

N.B This luminaire is suitable for surface, BESA mounting or with conduit end entry to both ends.
Note: DO NOT carry out insulation tests with the driver connected to the circuit. JCC JC71741 Skypack QR Range fig

Specifications

Colour temp: 4000K Ra: 80

Skypack™| Product code| Total circuit wattage| Lumens| LpcW
---|---|---|---|---
4ft Single| JC71741| 23| 2760| 120
4ft Single EM| JC71741EM| 25| 2760| 110
4ft Twin| JC71742| 40| 4800| 120
4ft Twin EM| JC71742EM| 42| 4800| 114
5ft Single| JC71743| 37| 4440| 120
5ft Single EM| JC71743EM| 39| 4440| 113
5ft Twin| JC71744| 60| 7200| 120
5ft Twin EM| JC71744EM| 62| 7200| 116
6ft Single| JC71745| 54| 6480| 120
6ft Single EM| JC71745EM| 56| 6480| 116
6ft Twin| JC71746| 82| 9800| 120
6ft Twin EM| JC71746EM| 84| 9800| 117

Important warranty information

This product is supported by a 2-year standard warranty which will extend to 5-years if registered within the first year of purchase.
(2 year on batteries). Please register at jcc.co.uk/warranty (Terms and conditions apply).
The installer will be asked to provide the following information, which is detailed on a label attached to the luminaire’s chassis:
Product Code/Date Code.

Emergency range routine inspection and test

All tests must be undertaken at times of least risk and in accordance with EN 50172:2004 as indicated below:
Daily: Indicators of central power supply shall be visually inspected for correct operation.
Monthly: (in addition to the daily check) If automatic testing devices are used, the results of the short duration tests shall be recorded. Test shall be carried out as follows:
a) Switch the luminaire over to emergency mode to operate from the batteries by simulating a failure of supply to the normal lighting for a period sufficient to ensure correct luminaire operation
NOTE: The period of simulation failure should be sufficient for the purpose of this clause whilst minimising damage to the system components e.g lamps. During this period, all luminaires and signs shall be checked to ensure that they are present, clean and functioning correctly.At the end of this test period, the supply to the normal lighting should be restored and any indicator lamp or device should be checked to ensure that is showing that the normal supply has been restored.
Annually: If automatic testing devices are used, the results of the short duration tests shall be recorded.For all other systems the monthly inspection shall be carried out and the following additional tests made:
a) Each luminaire and internally illuminated sign shall be tested monthly as above but for its full duration in accordance with the manufacturer’s information.
b) The normal supply for the luminaire should be restored and any charge indicator lamp or device should be checked to ensure that it shows the normal supply has been restored. The charging arrangements should be checked for proper functioning.
c) The date of the test and its results shall be recorded in the system logbook.

A copy of this report must accompany any fitting returned to the manufacturer for any reason.

General Information

Our products are designed to comply with the requirements of UK law and the relevant industry national and international standards and should not be modified in any way. All emergency lighting systems should comply with the recommendations of BS5266-1: Code of Practice for the Emergency Lighting of Premises and be installed by competent engineers in accordance with the relevant wiring regulations. Before installing any type of Emergency Lighting always seek the advice and approval of the local Fire Prevention Officer (or equivalent authority).

Maintenance

Failed or faulty light sources connected to this equipment should be replaced immediately. These units are designed especially for a long and trouble free life. Under normal conditions, will require no routine maintenance or service beyond the inspection and test regime of BS5266-1.
Both mains supply and battery protection fusing is incorporated internally. Should access to these or any other part of the circuitry be required this must be undertaken only by a suitably qualified person. Special care must be taken when removing the cover to circuitry and battery. Only replacement components authorised by the company must be used. Disposal of replaced components should be in accordance with the component manufacturers instructions.
You can help protect the environment. Please remember to respect the local regulations: hand in the non-working electrical equipment to an appropriate waste disposal centre. The packaging material is recyclable.
Dispose of the packaging in an environmentally friendly manner and make it available for the recyclable material collection service.

Profile & Dimensions

JCC JC71741 Skypack QR Range fig 2

Emergency test record sheet

Month| Test Type| First Year| Second Year| Third Year| Fourth Year| Fifth Year
---|---|---|---|---|---|---
Sign| Date| Sign| Date| Sign| Date| Sign| Date| Sign| Date
January| Functional| | | | | | | | | |
February| Functional| | | | | | | | | |
March| Functional| | | | | | | | | |
April| Functional| | | | | | | | | |
May| Functional| | | | | | | | | |
June| Functional| | | | | | | | | |
July| Functional| | | | | | | | | |
August| Functional| | | | | | | | | |
September| Functional| | | | | | | | | |
October| Functional| | | | | | | | | |
November| Functional| | | | | | | | | |
December| 3 hour| | | | | | | | | |

BS EN ISO9001 – 2015
– Registered Firm Certificate No. GB 1552
JCC Lighting Products Ltd. Lux Park, Chichester Business
Park, City Fields Way, Tangmere, Chichester, West Sussex, PO20 2FT
Technical Support: +44(0)1243 838986
Customer Services: +44(0)1243 838999JCC JC71741 Skypack QR Range