MEAN WELL LRS-75-5 Single Output Switching Power Supply Owner’s Manual
- June 13, 2024
- MEAN WELL
Table of Contents
- LRS-75-5 Single Output Switching Power Supply
- ■ Features
- ■ Applications
- ■ GTIN CODE
- ■ Description
- ■ Model Encoding
- SPECIFICATION
- Block Diagram
- Derating Curve
- Static Characteristics
- Mechanical Specification
- Installation Manual
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
75W Single Output Switching Power Supply
LRS – 75 series
LRS-75-5 Single Output Switching Power Supply
https://www.meanwell.com/Upload/PDF/Enclosed_Type_EN.pdf
■ Features
- Universal AC input / Full range
- Withstand 300VAC surge input for 5 second
- No load power consumption<0.3W
- Miniature size and 1U low profile
- High operating temperature up to 70°C
- Protections: Short circuit / Overload / Over voltage
- Cooling by free air convection
- Compliance to IEC/BS EN/EN 60335-1(PD3) and IEC/BS EN/EN61558-1, -2-16 for household appliances
- Operating altitude up to 5000 meters (Note.7)
- Withstand 5G vibration test
- High efficiency, long life and high reliability
- LED indicator for power on
- Over voltage category III
- 100% full load burn-in test
- 3 years warranty
■ Applications
- Industrial automation machinery
- Industrial control system
- Mechanical and electrical equipment
- Electronic instruments, equipments or apparatus
- Household appliances
■ GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
■ Description
LRS-75 series is a 75W single-output enclosed type power supply with 30mm of
low profile design. Adopting the full range 85-264VAC input, the entire series
provides an output voltage line of 5V, 12V, 15V, 24V, 36V and 48V.
In addition to the high efficiency up to 91.5%, the design of metallic mesh
case enhances the heat dissipation of LRS-75 that the whole series operates
from -30°C through 70°C under air convection without a fan. Delivering an
extremely low no load power consumption (less than 0.3W), it allows the end
system to easily meet the worldwide energy requirement. LRS-75 has the
complete protection functions and 5G anti-vibration capability; it is complied
with the international safety regulations such as TUV BS EN/EN62368-1, BS
EN/EN60335-1,BS EN/EN61558-1/-2-16, UL62368-1 and GB4943. LRS-75 series serves
as a high price-to-performance power supply solution for various industrial
applications.
■ Model Encoding
SPECIFICATION
MODEL| LRS-75-5| LRS-75-12| LRS-75-15| LRS-75-24|
LRS-75-36| LRS-75-48
---|---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 5V| 12V| 15V| 24V| 36V| 48V
RATED CURRENT| 14A| 6A| 5A| 3.2A| 2.1A| 1.6A
CURRENT RANGE| 0 ~ 14A| 0 ~ 6A| 0 ~ 5A| 0 ~ 3.2A| 0 ~ 2.1A| 0 ~ 1.6A
RATED POWER| 70W| 72W| 75W| 76.8W| 75.6W| 76.8W
RIPPLE & NOISE (max.) Note.2| 100mVp-p| 120mVp-p| 120mVp-p|
150mVp-p| 200mVp-p| 200mVp-p
VOLTAGE ADJ. RANGE| 4.5 ~ 5.5V| 10.2 ~ 13.8V| 13.5 ~ 18V| 21.6 ~ 28.8V|
32.4 ~ 39.6V| 43.2 ~ 52.8V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION Note.4| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION Note.5| ±1.0%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME| 500ms, 30ms/230VAC 500ms,30ms/115VAC at full
load
HOLD UP TIME (Typ.)| 60ms/230VAC 12ms/115VAC at full load
INPUT| VOLTAGE RANGE| 85 ~ 264VAC 120 ~ 373VDC
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 86.5%| 89%| 89%| 90%| 91.5%| 91.5%
AC CURRENT (Typ.)| 1.4A/115VAC 0.85A/230VAC
INRUSH CURRENT (Typ.)| COLD START 65A/230VAC
LEAKAGE CURRENT| <0.75mA / 240VAC
PROTECTION| OVER LOAD| 110 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is
removed
OVER VOLTAGE| 5.75 ~ 6.75V| 13.8 ~ 16.2V| 18.75 ~ 21.75V| 28.8 ~ 33.6V|
41.4 ~ 48.6V| 55.2 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
ENVIRONMENT| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
OVER VOLTAGE CATEGORY| Ⅲ; Compliance to BS EN/EN61558, BS EN/EN50178,BS
EN/EN60664-1, BS EN/EN62477-1; altitude up to 2000 meters
SAFETY & **EMC (Note 8)**
| SAFETY STANDARDS| UL62368-1, TUV BS EN/EN62368-1, BS EN/EN60335-1, BS
EN/EN61558-1/-2-16,CCC GB4943.1, BSMI CNS15598-1, EAC TP TC 004,AS/NZS
62368.1(by CB),KC62368-1, BIS IS13252(Part1): 2010/IEC 60950-1: 2005 approved
WITHSTAND VOLTAGE| I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:1.25KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC / 25℃/
70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class B, BS
EN/EN55014, BS EN/EN61000-3-2,-3, GB/T 9254, BSMI CNS15936, EAC TP TC 020,KC
KSC 9832, KSC 9835
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS
EN/EN61000-6-2 (BS EN/EN50082-2), BS EN/EN55035, heavy industry level,EAC TP
TC 020,KC KSC 9832, KSC 9835
OTHERS| MTBF| 3334.3K hrs min. Telcordia SR-332 (Bellcore) ;
667.2Khrs min. MIL-HDBK-217F (25℃)
DIMENSION| 999730mm (LWH)
PACKING| 0.25Kg ; 45pcs/ 12.25Kg/ 0.77CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC
input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted
pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load
regulation.
4. Line regulation is measured from low line to high line at rated load.
5. Load regulation is measured from 0% to 100% rated load.
6. Length of set up time is measured at cold first start. Turning ON/OFF the
power supply very quickly may lead to increase of the set up time.
7. The ambient temperature derating of 5℃/1000m is needed for operating
altitude greater than 2000m(6500ft).
8. The power supply is considered a component which will be installed into a
final equipment. All the EMC tests are been executed by mounting the unit on a
360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-
confirmed that it still meets EMC directives. For guidance on how to perform
these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
※ Product Liability Disclaimer: For detailed information, please refer to
https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve
Static Characteristics
Mechanical Specification
Terminal Pin No. Assignment
Pin No. | Assignment |
---|---|
1 | AC/L |
2 | AC/N |
3 | FG |
4 | DC OUTPUT -V |
5 | DC OUTPUT +V |
Installation Manual