Mean Well DDR-120A-48 DIN Rail Type DC-DC Converter Specification And Data Sheet

June 12, 2024
MEAN WELL

Mean Well DDR-120A-48 DIN Rail Type DC-DC Converter

Features

  • Compliance to BS EN/EN50155 and BS EN/EN45545-2 railway standard Width only 32mm
  • 2:1 wide input range
  • -40~+70°C wide working temperature
  • 150% peak load capability
  • DC output adjustable
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Protections: Short circuit / Overload / Over voltage / Input reverse polarity / Input under voltage protection
  • 4KVdc I/O isolation (Reinforced isolation)
  • 3 years warranty

Applications

  • Bus, tram, metro or railway system
  • Industrial control system
  • Semi-conductor fabrication equipment
  • Factory automation
  • Electro-mechanical
  • Wireless network
  • Telecom or datacom system

GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

DDR-120 series is a 120W DIN Rail type DC-DC converter with main features including DIN rail-type easy installation, ultra slim width (32mm), 2:1 wide input voltage, fanless design, -40~+70°C wide operating temperature, 4KVdc 1/O isolation, 150% peak load, adjustable output voltage and full protective functions. This series of models has various input options: 9~18V / 16.8~33.6V / 33.6~67.2V/67.2~154V and various output options: 12V / 24V / 48V and can be used for industrial & railway control, security control, communication system and other fields. Suitable applications include DC buck/boost regulator, increasing system insulation level and voltage drop compensation along cable…..etc.

Model Encoding

Mean Well DDR-120A-48 DIN Rail Type DC-DC Converter-
fig2

SPECIFICATION

MODEL| DDR-120A-12| DDR-120A-24| DDR-120A-48| DDR- 120B-12| DDR-120B-24| DDR-120B-48
---|---|---|---|---|---|---

OUTPUT

| DC VOLTAGE| 12V| 24V| 48V| 12V| 24V| 48V
RATED CURRENT| 8.3A| 4.2A| 2.1A| 10A| 5A| 2.5A
CURRENT RANGE| 0 ~ 8.3A| 0 ~ 4.2A| 0 ~ 2.1A| 0 ~ 10A| 0 ~ 5A| 0 ~ 2.5A
RATED POWER| 99.6W| 100.8W| 100.8W| 120W| 120W| 120W
PEAK CURRENT| 12.45A| 6.3A| 3.15A| 15A| 7.5A| 3.75A
PEAK POWER Note.5| 150W (3sec.)| 180W (3sec.)
RIPPLE & NOISE (max.) **Note.2| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p
VOLTAGE ADJ. RANGE| 9 ~ 14V| 24 ~ 28V| 48 ~ 56V| 9 ~ 14V| 24 ~ 28V| 48 ~ 56V
VOLTAGE TOLERANCE Note.3| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 60ms @12Vdc| 500ms, 60ms @24Vdc
HOLD UP TIME (Typ.)**| Please refer to page 7 Hold up Time( Load de-rating curve )

INPUT

| VOLTAGE RANGE Note.4| 9 ~ 18Vdc| 9 ~ 18Vdc| 9 ~ 18Vdc| 16.8 ~ 33.6Vdc| 16.8 ~ 33.6Vdc| 16.8 ~ 33.6Vdc
EFFICIENCY (Typ.)| 88.5%| 88.5%| 88.5%| 89%| 89.5%| 91%
DC CURRENT (Typ.)| 11.2A @12Vdc| 5.6A @24Vdc
INRUSH CURRENT (Typ.)| 5A @12Vdc| 5A @ 24Vdc

INTERRUPTION OF VOLTAGE SUPPLY

| EN50155:2007-comply with 3ms@ full load| EN50155:2007-comply with S1 level (6ms) @ full load, S2 level (10ms) @ 70% load
EN50155:2017-comply with S1 level| EN50155:2017-comply with S1 level

PROTECTION

|

OVERLOAD

| Normally works within 150% rated output power for more than 3 seconds and then constant current protection 105~135% rated output power with auto- recovery

OVER VOLTAGE

| 14.4 ~ 16.8V| 28.8 ~ 33.6V| 57.6 ~ 67.2V| 14.4 ~ 16.8V| 28.8 ~ 33.6V| 57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
REVERSE POLARITY| By internal MOSFET, no damage, recovers automatically after fault condition removed
UNDER VOLTAGE LOCKOUT| 12Vin (A – type) :Power ON≥9V , OFF≤8.5V| 24Vin (B – type) :Power ON≥16.8V , OFF≤16.5V

ENVIRONMENT

| WORKING TEMP.| -40 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 5 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 5 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 55℃)
VIBRATION| Component:10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC61373
OPERATING ALTITUDE| 5000 meters

SAFETY & EMC

(Note 6)

| SAFETY STANDARDS| IEC 62368-1, UL 62368-1, EAC TP TC 004, AS/NZS 62368.1 approved; Design refer to UL508
WITHSTAND VOLTAGE| I/P-O/P:4KVdc  I/P-FG:2.5KVdc  O/P-FG:2.5KVdc
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500Vdc / 25℃/ 70% RH

EMC EMISSION

| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032| Class B
Radiated| BS EN/EN55032| Class B
Voltage Flicker| BS EN/EN61000-3-3| —–
Harmonic Current| —–| —–

EMC IMMUNITY

| BS EN/EN55035 , BS EN/EN61000-6-2(BS EN/EN50082-2)
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 3, 6KV contact; criteria A
Radiated| BS EN/EN61000-4-3| Level 3, 10V/m ; criteria A
EFT / Burst| BS EN/EN61000-4-4| Level 3, 2KV ; criteria A
Surge| BS EN/EN61000-4-5| Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-FG ;criteria A
Conducted| BS EN/EN61000-4-6| Level 3, 10V ; criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m ; criteria A

RAILWAY STANDARD

| Compliance to BS EN/EN45545-2 for fire protection ; Meet BS EN/EN50155 / IEC60571 including IEC61373 for shock & vibration, BS EN/EN50121-3-2 for EMC (except for 9~18Vin)

OTHERS

| MTBF| 1769.5K hrs min.       Telcordia SR-332 (Bellcore) ; 214.5K hrs min.        MIL-HDBK-217F (25℃)
DIMENSION| 32125.2102mm (WHD)
PACKING| 510g; 28pcs/15.3Kg/1.22CUFT

NOTE

| 1.  All parameters NOT specially mentioned are measured at normal input (A:12Vdc , B:24Vdc) , rated load and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.

3.  Tolerance : includes set up tolerance, line regulation and load regulation.

4.  Derating may be needed under low input voltage. Please check the derating curve for more details.

5.  3 seconds max., please refer to peak loading curves.

6.  The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”

(as available on http://www.meanwell.com)

7.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

MODEL| DDR-120C-12| DDR-120C-24| DDR-120C-48| DDR- 120D-12| DDR-120D-24| DDR-120D-48
---|---|---|---|---|---|---

OUTPUT

| DC VOLTAGE| 12V| 24V| 48V| 12V| 24V| 48V
RATED CURRENT| 10A| 5A| 2.5A| 10A| 5A| 2.5A
CURRENT RANGE| 0 ~ 10A| 0 ~ 5A| 0 ~ 2.5A| 0 ~ 10A| 0 ~ 5A| 0 ~ 2.5A
RATED POWER| 120W| 120W| 120W| 120W| 120W| 120W
PEAK CURRENT| 15A| 7.5A| 3.75A| 15A| 7.5A| 3.75A
PEAK POWER Note.5| 180W (3sec.)
RIPPLE & NOISE (max.) **Note.2| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p| 50mVp-p
VOLTAGE ADJ. RANGE| 9 ~ 14V| 24 ~ 28V| 48 ~ 56V| 9 ~ 14V| 24 ~ 28V| 48 ~ 56V
VOLTAGE TOLERANCE Note.3| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 60ms @48Vdc| 500ms, 60ms @110Vdc
HOLD UP TIME (Typ.)**| Please refer to page 7 Hold up Time( Load de-rating curve )

INPUT

| VOLTAGE RANGE Note.4| 33.6 ~ 67.2Vdc| 33.6 ~ 67.2Vdc| 33.6 ~ 67.2Vdc| 67.2 ~ 154Vdc| 67.2 ~ 154Vdc| 67.2 ~ 154Vdc
EFFICIENCY (Typ.)| 89.5%| 91%| 92%| 89.5%| 91%| 91.5%
DC CURRENT (Typ.)| 2.8A @48Vdc| 1.3A @110Vdc
INRUSH CURRENT (Typ.)| 5A @48Vdc| 5A @110Vdc

INTERRUPTION OF VOLTAGE SUPPLY

| EN50155:2007-comply with S1 level (6ms) @ full load, S2 level (10ms) @ 60% load| EN50155:2007-comply with S2 level (10ms) @ full load
EN50155:2017-comply with S1 level| EN50155:2017-comply with S1 level

PROTECTION

|

OVERLOAD

| Normally works within 150% rated output power for more than 3 seconds and then constant current protection 105~135% rated output power with auto- recovery

OVER VOLTAGE

| 14.4 ~ 16.8V| 28.8 ~ 33.6V| 57.6 ~ 67.2V| 14.4 ~ 16.8V| 28.8 ~ 33.6V| 57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
REVERSE POLARITY| By internal MOSFET, no damage, recovers automatically after fault condition removed
UNDER VOLTAGE LOCKOUT| 48Vin (C – type) :Power ON≥33.6V , OFF≤33V| 110Vin (D – type):Power ON≥67.2V , OFF≤65V

ENVIRONMENT

| WORKING TEMP.| -40 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 5 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 5 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 55℃)
VIBRATION| Component:10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC61373
OPERATING ALTITUDE| 5000 meters

SAFETY & EMC

(Note 6)

| SAFETY STANDARDS| IEC 62368-1, UL 62368-1, EAC TP TC 004, AS/NZS 62368.1 approved; Design refer to UL508
WITHSTAND VOLTAGE| I/P-O/P:4KVdc  I/P-FG:2.5KVdc  O/P-FG:2.5KVdc
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500Vdc / 25℃/ 70% RH

EMC EMISSION

| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032| Class B
Radiated| BS EN/EN55032| Class B
Voltage Flicker| BS EN/EN61000-3-3| —–
Harmonic Current| —–| —–

EMC IMMUNITY

| BS EN/EN55035 , BS EN/EN61000-6-2(BS EN/EN50082-2)
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 3, 6KV contact; criteria A
Radiated| BS EN/EN61000-4-3| Level 3, 10V/m ; criteria A
EFT / Burst| BS EN/EN61000-4-4| Level 3, 2KV ; criteria A
Surge| BS EN/EN61000-4-5| Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-FG ;criteria A
Conducted| BS EN/EN61000-4-6| Level 3, 10V ; criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m ; criteria A
RAILWAY STANDARD| Compliance to BS EN/EN45545-2 for fire protection ; Meet BS EN/EN50155 / IEC60571 including IEC61373 for shock & vibration,

BS EN/EN50121-3-2 for EMC

OTHERS

| MTBF| 1769.5K hrs min.       Telcordia SR-332 (Bellcore) ; 214.5K hrs min.        MIL-HDBK-217F (25℃)
DIMENSION| 32125.2102mm (WHD)
PACKING| 510g; 28pcs/15.3Kg/1.22CUFT

NOTE

| 1.  All parameters NOT specially mentioned are measured at normal input (C:48Vdc , D:110Vdc) , rated load and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.

3.  Tolerance : includes set up tolerance, line regulation and load regulation.

4.  Derating may be needed under low input voltage. Please check the derating curve for more details.

5.  3 seconds max., please refer to peak loading curves.

6.  The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”

(as available on http://www.meanwell.com)

7.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

Mean Well DDR-120A-48 DIN Rail Type DC-DC Converter-
fig3
Derating Curve

Output derating VS input voltage

Peak Loading

Mean Well DDR-120A-48 DIN Rail Type DC-DC Converter-
fig6

Input Fuse

There is a fuse connected in series to the positive input line, which is used to protect against abnormal surge. Fuse specifications of each model are shown as below.

I Input Under-Voltage Protection

If input voltage drops below Vimin, the internal control IC shuts down and there is no output voltage. It recovers automatically when input voltage reaches above Vimin, please refer to the cruve below.

Mean Well DDR-120A-48 DIN Rail Type DC-DC Converter-
fig7

Input Reverse Polarity Protection

There is a MOSFET connected in series to the negative input line. If the input polarity is connected reversely, the MOSFET opens and there will be no output to protect the unit.

Input Range and Transient Ability

The series has a wide range input capability. With -30% / +40% of rated input voltage(except A Type), it can withstand that for 1 second.

Inrush Current

Inrush current is suppressed by a current limit circuit during the initial start-up, and then the circuit is bypassed by a MOSFET to reduce power consumption after accomplishing the start-up.

Hold-up Time
EN50155:2007 version -D type is in compliance with S2 level (10ms), while A types are in compliance with S1 level (3ms) at full load output condition. To fulfil the requirements of S2 level (10ms), B types require de-rating their output load to 70%, C types require de-rating their output load to 60%, please refer to the curve diagrams below.

Mean Well DDR-120A-48 DIN Rail Type DC-DC Converter-
fig9

Efficiency vs Load & Vin Curve

The efficiency vs load & Vin curves of each model are shown as below.

Mean Well DDR-120A-48 DIN Rail Type DC-DC Converter-
fig10

Immunity to Environmental Conditions

Test method Standard Test conditions Status
Cooling Test EN 50155 section 12.2.3 (Column 2, Class TX)

EN 60068-2-1

| Temperature: -40℃

Dwell Time: 2 hrs/cycle

| No damage

Dry Heat Test

| EN 50155 section 12.2.4 (Column 2, Class TX)

EN 50155 section 12.2.4 (Column 3, Class TX & Column 4, Class TX) EN 60068-2-2

|

Temperature: 70℃ / 85℃ Duration: 6 hrs / 10min

|

PASS

Damp Heat Test, Cyclic

|

EN 50155 section 12.2.5

EN 60068-2-30

| Temperature: 25℃~55℃ Humidity: 90%~100% RH Duration: 48 hrs|

PASS

Vibration Test

| EN 50155 section 12.2.11

EN 61373

| Temperature: 19℃ Humidity: 65%

Duration: 10 mins

|

PASS

Increased Vibration Test

|

EN 50155 section 12.2.11

EN 61373

| Temperature: 19℃ Humidity: 65%

Duration: 5 hrs

|

PASS

Shock Test

|

EN 50155 section 12.2.11

EN 61373

| Temperature: 21± 3℃ Humidity: 65 ± 5%

Duration: 30ms*18

|

PASS

Low Temperature Storage Test

|

EN 50155 section 12.2.3 (Column 2, Class TX)

EN 60068-2-1

|

Temperature: -40℃ Dwell Time: 16 hrs

|

PASS

Salt Mist Test

|

EN 50155 section 12.2.10 (Class ST4)

|

Temperature: 35℃±2℃ Duration: 96 hrs

|

PASS

EN45545-2 Fire Test Conditions

Test Items     Hazard Level
  Items Standard

HL1

|

HL2

|

HL3

 |

Oxygen index test

| EN 45545-2:2013

EN ISO 4589-2:1996

|

PASS

|

PASS

|

PASS

R22

|

Smoke density test

| EN 45545-2:2013

EN ISO 5659-2:2006

|

PASS

|

PASS

|

PASS

 |

Smoke toxicity test

| EN 45545-2:2013 NF X70-100:2006|

PASS

|

PASS

|

PASS

R24

|

Oxygen index test

| EN 45545-2:2013

EN ISO 4589-2:1996

|

PASS

|

PASS

|

PASS

R25

|

Glow-wire test

| EN 45545-2:2013

EN 60695-2-11:2000

|

PASS

|

PASS

|

PASS

R26

|

Vertical flame test

| EN 45545-2:2013

EN 60695-11:2003

|

PASS

|

PASS

|

PASS

Mechanical Specification

Mean Well DDR-120A-48 DIN Rail Type DC-DC Converter-
fig11

Installation Manual

Please refer to : http://www.meanwell.com/manual.html

FAQ’s

What is the brand and model of the DC-DC converter that Mean Well offers?

Brand: Mean Well ,Model: DDR-120A-48

What is the input voltage range of the Mean Well DDR-120A-48 converter?

The input voltage range of the DDR-120A-48 is 9.2VDC to 18VDC.

What is the output voltage of the Mean Well DDR-120A-48 converter?

The output voltage of the DDR-120A-48 is 48VDC.

Can the DDR-120A-48 converter handle a wide temperature range?

Yes, the Mean Well DDR-120A-48 can operate within a temperature range of -30°C to +70°C.

What type of converter is the DDR-120A-48?

The DDR-120A-48 is a DIN rail type DC-DC converter.

What is the power rating of the Mean Well DDR-120A-48?

The DDR-120A-48 has a power rating of 120 watts.

Is the Mean Well DDR-120A-48 suitable for industrial applications?

Yes, the DDR-120A-48 is designed for industrial applications that require reliable DC-DC conversion.

What are the protection features of the DDR-120A-48 converter?

The DDR-120A-48 offers protection against overvoltage, overcurrent, and short circuits.

Does the Mean Well DDR-120A-48 comply with any safety standards?

Yes, the DDR-120A-48 is compliant with UL 508 and UL 60950-1 safety standards.

Can the DDR-120A-48 converter be mounted on a DIN rail?

Yes, the DDR-120A-48 is specifically designed for DIN rail mounting.

What is the efficiency of the Mean Well DDR-120A-48 converter?

The DDR-120A-48 has a high efficiency rating of up to 92%.

What applications is the Mean Well DDR-120A-48 commonly used for?

The DDR-120A-48 converter is commonly used in industrial automation, telecommunications, and various DC-powered systems.

Download This PDF Link: Mean Well DDR-120A-48 DIN Rail Type DC-DC Converter Specification And Data Sheet 

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals