TOSHIBA S15 Microdrive Motors Drives User Guide
- June 12, 2024
- Toshiba
Table of Contents
S15 Microdrive Motors Drives
Product Information
The product is the S15, a startup guide for version 1.8.0. It is
a device used to setup and program the basic parameters of a motor
system.
Startup Checklist
Before starting the setup process, the following checks should
be performed:
-
Visual Inspection:
- No foreign materials (metal shavings, hardware)
-
Input and Output Wiring:
-
Input leads are not wired to output terminals
-
Input, output and control wires are in separate conduit
-
Motor leads do not share conduit with any other motor
leads -
Verify input and output wire tightness and condition
(continuity, frayed wires, loose connections, pinched
insulation)
-
-
Motor Terminal Box:
- Verify no power factor correction capacitors are installed
- Verify wire tightness and condition (continuity, frayed wires,
loose connections, pinched insulation)
-
Drive to Motor Ground Connection (ASD chassis to motor
chassis):- Verify wire tightness and condition (continuity, frayed wires,
loose connections, pinched insulation)
- Verify wire tightness and condition (continuity, frayed wires,
-
Record the Electrical Distribution System:
- Delta/Wye with Grounded Secondary
- Grounding Capacitor: Enabled or Disabled (Note: Disable on
Ungrounded, Corner Grounded or High Impedance Grounding Systems to
avoid VFD failure)
-
Voltage:
- Verify voltages
-
Blower/Cooling Fan(s) Check:
- Verify fans operate and air flows in correct direction (bottom
to top)
- Verify fans operate and air flows in correct direction (bottom
-
Digital Inputs:
- Verify digital input operation
- The S15 has seven digital inputs available and one Safe Torque
O (STO) input. Four of the digital inputs can have more than one
function assigned. Digital inputs can be monitored on the keypad in
Monitor Mode, refer to S15 Application Note 1.1.0 Navigating Menus
& Parameters.
-
Digital Outputs:
- Verify digital output operation
- The S15 has three outputs available; two relay outputs and one
digital output. Two of the outputs can have more than one function
assigned. Parameter f139 determines if both functions are required
to be true to change state or only one function is required. Refer
to Section 11.7 of the S15 Instruction Manual E6582175 for more
details.
Product Usage Instructions
To use the S15 startup guide, follow these steps:
-
Perform a visual inspection to ensure there are no foreign
materials present, such as metal shavings or hardware. -
Check the input and output wiring:
-
Make sure the input leads are not wired to output
terminals. -
Ensure that the input, output, and control wires are in
separate conduit. -
Motor leads should not share conduit with any other motor
leads. -
Verify the tightness and condition of the input and output
wires, checking for continuity, frayed wires, loose connections,
and pinched insulation.
-
-
Inspect the motor terminal box:
-
Ensure no power factor correction capacitors are
installed. -
Check the tightness and condition of the wires, looking for
continuity, frayed wires, loose connections, and pinched
insulation.
-
-
Verify the drive to motor ground connection:
- Check the tightness and condition of the wires, ensuring
continuity, and looking for frayed wires, loose connections, and
pinched insulation.
- Check the tightness and condition of the wires, ensuring
-
Record the electrical distribution system information,
specifically whether it is Delta/Wye with Grounded Secondary. Also,
determine if the grounding capacitor is enabled or disabled. Note
that on Ungrounded, Corner Grounded or High Impedance Grounding
Systems, the grounding capacitor should be disabled to avoid VFD
failure. Refer to Section 1.3.3 of the S15 Instruction Manual
E6582175 for more details. -
Verify the voltages.
-
Check the blower/cooling fan(s) to ensure they operate and air
flows in the correct direction (bottom to top). -
Verify the operation of digital inputs:
- There are seven digital inputs available on the S15, along with
one Safe Torque O (STO) input. Some of the digital inputs can have
multiple functions assigned to them. Use the keypad in Monitor Mode
to monitor digital inputs. Refer to S15 Application Note 1.1.0
Navigating Menus & Parameters for more information.
- There are seven digital inputs available on the S15, along with
-
Verify the operation of digital outputs:
- The S15 has three outputs available, including two relay
outputs and one digital output. Some of the outputs can have
multiple functions assigned to them. Parameter f139 determines if
both functions are required to be true to change state or if only
one function is required. Refer to Section 11.7 of the S15
Instruction Manual E6582175 for more details.
- The S15 has three outputs available, including two relay
S15 Application Note 1.8.0 Startup Guide Setup and program the basic parameters.
Estimated Time: 20-30 Minutes Level: 1 Prerequisite:
· S15 Application Note 1.1.0 Navigating Menus & Parameters
A STEP
Startup Checklist
Visual Inspection
No foreign materials (metal shavings, hardware)
Input and Output Wiring Input leads are not wired to output terminals Input,
output and control wires are in separate conduit Motor leads do not share
conduit with any other motor leads Verify input and output wire tightness and
condition (continuity, frayed wires, loose connections,
pinched insulation)
Motor Terminal Box Verify no power factor correction capacitors are installed Verify wire tightness and condition (continuity, frayed wires, loose connections, pinched insulation)
Drive to Motor Ground Connection (ASD chassis to motor chassis) Verify wire tightness and condition (continuity, frayed wires, loose connections, pinched insulation)
Record the Electrical Distribution System
Delta/Wye with Grounded Secondary
Grounding Capacitor Enabled Disabled
This should be DISABLED on Ungrounded, Corner Grounded or High Impedance
Grounding Systems otherwise it could result in a VFD failure. Refer to Section
1.3.3 of the S15 Instruction Manual E6582175 for more details.
© Toshiba International Corporation 2021 www.toshiba.com/tic Email: TIC-
ASD@toshiba.com 855-803-7089 13131 West
Little York Road, Houston, TX
A STEP
Startup Checklist
Voltage
Verify voltages
Line voltage = ±10% of drive rating DC bus = Line voltage * 1.414 Control
voltage = 24 VDC
Parameter L1 L2
Measured Value
L1 L3
L2 L3
L1 GND
L2 GND
L3 GND
DC Bus (PA/+ PC/-)
Control Voltage (P24 CC)
SW1 Switch Move to Sink or Source, otherwise pra will blink on the keypad. Sink Source
Motor Rotation Run the drive at 5 Hz with the keypad (default setting). If
incorrect, swap two of the output leads (T1, T2 or T3) and retest rotation.
Verify motor rotates in the correct direction
Blower/Cooling Fan(s) Check Verify fans operate and air flows in correct direction (bottom to top)
Analog Inputs Verify polarity. Scaling can be adjusted with parameters F201 to F221.
VIC (4-20mA)
VIA (0-10VDC)
VIB (-10 to +10VDC)
© Toshiba International Corporation 2021 www.toshiba.com/tic Email: TIC- ASD@toshiba.com 855-803-7089 13131 West Little York Road, Houston, TX
A STEP
Startup Checklist
Digital Inputs
Verify digital input operation
The S15 has seven digital inputs available and one Safe Torque O (STO) input.
Four of the digital inputs can have more than one function assigned. Digital
inputs can be monitored on the keypad in Monitor Mode, refer to S15
Application Note 1.1.0 Navigating Menus & Parameters.
Function Parameters
f111
Terminal F (Default – Forward Run)
f151
Assigned Function 16: Preset Speed Bit 4
0: No Function
Function Parameters
f112
Terminal R (Default – Reverse Run)
f152
Assigned Function 4: Reverse Run
0: No Function
Function Parameters
f113
Terminal RES (Default – Reset)
f153
Assigned Function 8: Reset
0: No Function
Function Parameters
f114
Terminal S1 (Default – Preset Speed 1)
f154
Assigned Function 10: Preset Speed Bit 1
0: No Function
Function Parameters
Terminal S2 (Default – Preset Speed 2)
f115
Terminal S3 (Default – Preset Speed 3)
f116
Assigned Function 12: Preset Speed Bit 2
14: Preset Speed Bit 3
f155 0: No Function
f156 0: No Function
N/A
N/A
Terminal VIB/S4 (Default – Preset Speed 4)
f117 16: Preset Speed Bit 4
© Toshiba International Corporation 2021 www.toshiba.com/tic Email: TIC- ASD@toshiba.com 855-803-7089 13131 West Little York Road, Houston, TX
A STEP
Startup Checklist
Digital Outputs
Verify digital output operation
The S15 has three outputs available; two relay outputs and one digital output. Two of the outputs can have more than one function assigned. Parameter f139 determines if both functions are required to be true to change state or only one function is required. Refer to Section 11.7 of the S15 Instruction Manual E6582175 for more details.
Function Parameters
Terminals FLA/FLB/FLC (Default – Fault Status)
f132
N/A
Assigned Function 10: Fault Status
Function Parameters
Assigned Function
Terminals RY/RC (Default – Run Status)
f130
f137
4: Low-Speed Detection Signal 255: Always ON
Function Parameters
Assigned Function
Terminals OUT/NO (Default – Speed Reach)
f131
f138
6: Speed Reach
255: Always ON
Analog Outputs Refer to S15 App Note 1.4.0 Analog Output Calibration for
calibration procedure and parameters.
Verify analog output operation
Terminal
Function Parameter
FM
fmsl
Default Output Frequency
New Function Assigned 0: Output Frequency
© Toshiba International Corporation 2021 www.toshiba.com/tic Email: TIC- ASD@toshiba.com 855-803-7089 13131 West Little York Road, Houston, TX
B STEP
Startup Parameters
Programming
Verify the basic parameters and record new values of any changed parameters
Recommended Carrier Frequency is 4.0kHz. Change f701 before thr to avoid dealing with percentages. Motor kW and RPM are not necessary to enter in the drive unless performing an auto-tune. Refer to S15 App Note 2.8.0 Motor Auto- tuning.
Parameter
Description
Default Value
New Value
aul cmod fmod
Overload Characteristic Selection
Command Mode Selection (Start/Stop Command)
Frequency Setting Mode Selection 1 (Frequency Reference)
1 1: Panel Keypad 0: Setting dial 1
0: Disabled 0: Terminal Block 0: Setting Dial 1 (saved at power off)
acc
Acceleration Time 1
10.0 s
dec
Deceleration Time 1
10.0 s
fh
Maximum Frequency
80.0 Hz
ul
Upper Limit Frequency
60.0 Hz
ll vl vlv pt
Lower Limit Frequency
Base Frequency 1 (Motor Nameplate Frequency)
Base Frequency Voltage 1 (Motor Nameplate Voltage)
V/Hz Control Mode Selection
0.0 Hz 60.0 Hz 230, 460, or 575V 0: Constant Torque
0: Constant Torque
f701 thr f300 f301 f303 f750
Current/Voltage Display Unit Selection Motor Electronic Thermal Protection
(Motor Nameplate Current) PWM Carrier Frequency
Auto-Restart Control Selec on (Catching a Spinning Motor)
Retry Selec on (Automatic Reset for Non-Critical Faults)
Easy Key Func on Selec on (Setup Easy Key as Local/Remote)
0: %
1: Amps/Volts
100 %/ VFD FLA 12.0 kHz
0: Disabled
0: Disabled
0: Disabled
0
0: Easy Mode Switching 0: Easy/Standard Switching
© Toshiba International Corporation 2021 www.toshiba.com/tic Email: TIC- ASD@toshiba.com 855-803-7089 13131 West Little York Road, Houston, TX
C STEP
Model Information
Model Information
Record the model information from the nameplate sticker and CPU versions
through monitor mode
Information Type
Serial No
Details
Infromation CPU1 Version CPU2 Version
Details