Q-TRAN QTM-eLED+TW-AWN Power Supply and Lutron Athena Owner’s Manual

June 13, 2024
Q-TRAN

Q-TRAN QTM-eLED+TW-AWN Power Supply and Lutron Athena

Q-TRAN-QTM-eLED-TW-AWN-Power-Supply-and-Lutron-Athena-
PRODUCT

Product Information

  • Product Name: QTM-eLED+TW-AWN
  • Compliant: Yes
  • LED Power Supply : 100W-300W
  • Sample Part Number : QTM-eLED-300W-TW-AWN-2-UNV-24VDC-WH
  • Wattage Options : 100W, 200W, 300W
  • Control Option : TW-AWN-2 (2 Lutron Athena Nodes)
  • Primary Voltage : UNV (Universal)
  • Secondary Voltage: 24VDC
  • Color Options : White (Standard), Black Powder Coat Finish
  • Compatible LEDs: Static White, Tunable White, RGB, RGBW, Warm Dim Applications

Product Usage Instructions

  1. Ensure that the product is installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved.
  2. Select the desired wattage option (100W, 200W, or 300W) based on your lighting needs.
  3. Choose the control option TW-AWN-2 if you require two Lutron Athena Nodes for intensity and CCT control.
  4. Connect the primary voltage to the product. The primary voltage is universal (UNV).
  5. Connect the secondary voltage to the product. The secondary voltage is 24VDC.
  6. Select the desired color option for the product. The standard options are white or black powder coat finish.
  7. Select compatible LEDs based on your lighting requirements. The product is compatible with various types of LEDs, including static white, tunable white, RGB, RGBW, and warm dim applications.
  8. Refer to the voltage drop chart for distance recommendations to achieve a 5% voltage drop.
  9. Install the product in the appropriate location using the provided dimensions and knockouts.
  10. Refer to the technical information section for wattage,  voltage, and current specifications.
  11. Use the control option TW-AWN-2 to adjust intensity and CCT settings for your lighting application.
  12. Follow the provided dimming intensity curve and 0-10V dimmer settings for controlling the light intensity.

Instruction

  • Delivers superior performance with its 100W constant voltage LED drivers and proprietary TW dimming module
  • Incorporates a factory-installed Lutron Athena Wireless Nodes, which streamlines installation time and allows for simple programming using the Athena iOS or Android app
  • Using radio frequency, it connects seamlessly to Lutron wall controls, keypads, and sensors over a mesh network, providing an efficient lighting control solution
  • Can be recess or surface mounted
  • See QTM-eLED+TW for power supply without Athena Nodes

1

PRODUCT

| 2

WATTAGE

| 3

CONTROL

| 4

PRIMARY VOLTAGE

| 5

SECONDARY VOLTAGE

| 6

COLOR

---|---|---|---|---|---
QTM-eLED|  | TW-AWN-2| UNV| 24VDC|

Sample Part Number: QTM-eLED-300W-TW-AWN-2-UNV-24VDC-WH

Q-TRAN-QTM-eLED-TW-AWN-Power-Supply-and-Lutron-Athena-
FIG-1

COMPATIBLE LEDS

STATIC WHITE

SW24/1.5- 4.0|
---|---
SW24/5.0, SW-HE, SW- HE+|
SD-SW24/1.0-4.0|
SD- SW24/6.0|
SW- IA|
SW- XT|

OTHER

DW-HE Tunable Applications
DW-HE Warm Dim Applications
WD
SC
RGB
RGBW, RGBW- HE

SHEETS

Q-SHEETS SW|
---|---
Q-SHEETS DW Tunable Applications| ✔
Q-SHEETS DW Warm Dim Applications|
Q-SHEETS RGB|
Q-SHEETS RGBW|

MICRO 5

MICRO 5 SW|
---|---
MICRO 5 DW Tunable Applications| ✔
MICRO 5 DW Warm Dim Applications|
MICRO 5 RGB|

PRODUCT INFORMATION

  • Limited output voltage and current plus isolation for safe operation
  • Q-Tran proprietary dimming curve
  • Controllable with 2x Lutron Athena System inputs for CCT and Intensity
  • 0-10V dimming down to 0.1%
  • Fully potted driver(s) for moisture resistance
  • Suitable for dry and damp locations
  • Suitable for surface or recessed mounting
  • Primary voltage – universal (120-277V)
  • Wide operating temperature range: -4˚F to 122˚F
  • Fits up to (3):100W 24 VDC driver(s) and Tunable White Module
  • 5-year warranty
  • Driver has Class A sound rating
  • Class 2 output
  • CSA #239924
  • Low Voltage Lighting Systems
    • CSA class 3425-15 and class 3425-95
    • CSA standard C22.2 No. 250.0-08 – Luminaires
    • ANSI/ UL standard 2108 – Low voltage lighting systems
    • CSA standard C22.2 No 250.13-14 – Light emitting diode (LED equipment for lighting applications
    • ANSI/ UL standard8750 – Light emitting diode (LED) equipment for use in lighting products

VOLTAGE DROP CHART

This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved

VDC

| Load Wattage (W)| Distance from PS for 5% Voltage Drop
---|---|---
10

AWG

| 12

AWG

| 14

AWG

| 16

AWG

| 18

AWG

| 20

AWG

| 22

AWG

| 24

AWG

| 26

AWG

24

| 17| 897’| 564’| 355’| 223’| 140’| 88’| 55’| 35’| 22’
25| 567’| 356’| 224’| 141’| 88’| 56’| 35’| 22’| 14’
40| 309’| 194’| 122’| 77’| 48’| 30’| 30’| 12’| 7’
80| 130’| 82’| 51’| 32’| 20’| 13’| 8’| 5’| 3’
100| 84’| 53’| 33’| 21’| 13’| 8’| 5’| 3’|

PRODUCT – DIMENSIONS

Q-TRAN-QTM-eLED-TW-AWN-Power-Supply-and-Lutron-Athena-
FIG-2

TECHNICAL INFORMATION

Wattage| Max Load (Watts)| Secondary Voltage| Max Prim Amps @ 120V| Max Prim Amps @ 277V
---|---|---|---|---
100W| 1x100W| 24VDC| 0.95A| 0.40A
200W| 2x100W| 24VDC| 1.90A| 0.80A
300W| 3x100W| 24VDC| 2.85A| 1.20A

CONTROL
TW-AWN-2: 2 Lutron Athena Nodes. 1 zone of control for 100-300W. One node controls intensity, one node controls CCT.

Total Wattage

| TW-AWN-2
---|---
Node 1| Node 1
100W| Intensity| CCT
200W| Intensity| CCT
300W| Intensity| CCT

HOUSING

  • 18 gauge welded steel enclosure: 14.5″W x 8.00″H x 4.00″D
  • Door: 15.5″W x 9.00″H
  • Knockouts: 25
  • Built-in support bracket incorporated to secure housing for surface mounting
  • Rated for surface mount or recessed use
  • Fully rated to operate low voltage load at listed wattage (No derating required)
  • Voltage regulation to 2% or less of rated output voltage
  • The ability to be dimmed using 0-10V dimming
  • Universal input range of 120-277 Vrms
  • Low Voltage Lighting Systems
  • CSA Class 3425-15 and Class 3425-95
  • Short circuit protection (SCP)
  • Over voltage protection (OVP)
  • Over current protection (OCP)
  • Live tested by the manufacturer to ensure proper operation
  • Manufacturer offers a minimum of 5-year warranty
  • Terminal blocks are made of tin plated copper with a voltage rating of 300V and a current rating of 40A

LUTRON ATHENA NODE

  • Compatibility with Lutron Athena System
  • Enables wireless 0-10V Dimming for tunable white applications. One Athena Node controls intensity, one Athena node controls color temperature
  • The set of nodes mounted in a single QTM-eLED+TW power supply is controlled as a single zone
  • Each Athena wireless node must be installed within 25′ of two or more Athena wireless nodes for robust Athena control system connection
  • Must be used as part of a Lutron Athena control System

SPECIFICATIONS

Input 24VDC
Input Voltage (Vrms) 120
Input Current, max (Arms) 0.98
Inrush Current, max* (Apk)
Input Frequency (Hz) 50/60
Input Power (W) 117
Output 3000K
--- ---
Output Voltage, nom (V) 24
Output Current (A) 2.0
Output Power (Wmax) 100
Dimming 0-10V, max 2mA
Environmental Min
--- ---
THD (%)
PF (%) 0.90
Case Temp (ºF)

PROTECTIONS

  • Short Circuit Protection (SCP)
  • Over Voltage Protection (OVP)
  • Over Current Protection (OCP)
  • Class 2 Output

COMPLIANCE

  • EMI Spec
    • FCC 47 Part 15
    • EN61000-3-2
  • CSA Certified
    • UL-2108
    • UL-8750
    • CSA C22.2 No 250.0-08
    • CSA C22.2 No 250.13-14

COLOR

Color Balance
Life Time vs. Case Temperature

Q-TRAN-QTM-eLED-TW-AWN-Power-Supply-and-Lutron-Athena-
FIG-4

Dimming Intensity Curve
Dimming Intensity Curve (Zoom)

Q-TRAN-QTM-eLED-TW-AWN-Power-Supply-and-Lutron-Athena-
FIG-5

NODE AND CONDUIT ENTRY LOCATIONS

Q-TRAN-QTM-eLED-TW-AWN-Power-Supply-and-Lutron-Athena-
FIG-6

Conduit Entry Locations
Athena nodes must be installed on the secondary side of power supply center and require 1.0” of clearance in order to optimally function. Metal conduit must be 1.0” away from any node. Refer to the diagram above for recommendations for conduit entry into secondary compartment.

Lutron Athena Node
Mounted in the secondary wiring compartment only

© 2023 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | sales@q-tran.com | www.q-tran.com
Specification subject to change. Rev-07-26-23