LEDALITE ID-SL SyncLine Wall Fixture Instruction Manual
- June 13, 2024
- LEDALITE
Table of Contents
LEDALITE ID-SL SyncLine Wall Fixture
Product Information
The SyncLine is an architectural linear wall fixture system that allows for installing 4ft, 6ft, and 8ft modules. These modules can be installed as individual standalone units or joined together to create a continuous run.
The system components include
- SyncLine End kit(s) – SL Endcap – Rubber Gasket – #8-18 X 3/8 screws
- SyncLine Wall Mid kit(s) – SL Locking Plate – SL Wire Wall cover – #8-B X 9/32 screws
- SyncLine Wall End Run kit(s) – SL ER Wall Bracket – SL Wall Lever – SL Wall Wire cover – #8-18 X 3/8 screw – #8-B X 9/32 screws
- SyncLine wall joint kit(s) – SL Locking Plate – SL Wall Wire cover – SL Joiner Wall Bracket
SL Wall Mid Lever – Rubber Gasket – #8-18 X 3/8 screw – #8-B X 9/32 screws
The SyncLine suspended systems are available in module lengths of 4ft, 6ft, and 8ft. The overall lengths of the modules are:
- 4′ 3/16″
- 6′
- 8′
Two endcaps are required per run, regardless of the length of the run. One endcap should be installed on each end of the run.
Product Usage Instructions
- Disrupt or turn off the power before starting any installation, service, or maintenance.
- Ensure that the fixture is connected to the building ground via the provided ground wire before reconnecting to the mains power supply.
- Remove the dustcover from the top of the light engine pans if installed.
- For standalone mounting, use the provided mounting points and follow the local and national building and electric codes for installation.
- For continuous runs, mount the fixtures with the joiner wall bracket at wall joints.
- The spacing between the joint bracket and fixture should be 2 27/32 (72.22mm) from the end of the fixture in any configuration.
Note: It is important to install the SyncLine system in accordance with local and national building and electric codes to ensure compliance and safe operation.
System Overview
These instructions review how to install SyncLine wall fixtures. SyncLine 4ft, 6ft, and 8ft modules can be installed as individual standalone units, or they can be joined together to create continuous run. The graphic below shows the components required to install a typical run or a Syncline standalone fixtures. SyncLine Wall Mid kit(s)TOOLS REQUIRED: Phillips screwdriver, 3/8” nut driver flat or #2 Robertson screwdriver
Module Lengths
SyncLine suspended systems come in 4ft, 6ft, and 8ft modules. Overall module
lengths are shown below. Module lengths do not include endcaps.
Endcaps
Two endcaps are required per run regardless of the length of the run. One
endcap on each end of the run.
ATTENTION : Install in accordance with local and national building and
electric codes.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interreference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
IMPORTANT:
Disconnect or turn off power before attempting any installation, service or
maintenance
Fixture must be connected to building ground via the provided ground wire
before re-connecting to mains power supply .
Power Label Location
- Power labels can be found on top of light engine pans. If dustcover is installed, please remove before installation.
Power Feed Location
- Four power feed location provided on all length; two on each end of fixture.
Prepare Fixtures / Install ceiling mounting components
Arrange boxed fixtures on floor in specified mounting locations, based on
supplied layout drawings. Remove fixtures from boxes. Install all ceiling
mount components and vertical aircraft cables using separate installation
instruction for Aircraft Cable Mounting (Supplied).
Note : If conditions are dusty/dirty, recommended practice is to leave
fixtures in their plastic bags.
Cut small holes in the bag as needed to complete the following installation
sequence, and then completely remove the bag from the fixture when conditions
are clean. This prevents dust and dirt build up on the fixtures.
Module Lengths and Standalone Mounting Points
Syncline wall systems comes in 4ft, 6ft and 8ft. Standalone mounting points
and overall module lengths are shown below.
Continuous Run
For continuous runs, the fixture is mounted with the joiner wall bracket at
wall joints. A continuous run of two 4ft fixtures is shown below. The spacing
between joint bracket and fixture is 2 27/32” (72.22mm) from end of fixture in
any configuration.
ATTENTION : Install in accordance with local and national building and electric codes.
-
Install Wall Brackets
Determine fixture mounting location and secure wall brackets to the structure using appropriate fasteners (four per bracket, supplied by others). 4ft fixtures: Require two bracket assemblies; 6ft & 8ft fixtures: Require three bracket assemblies. Brackets must be installed a maximum of 1.6″ from end of the fixture (on 6ft & 8ft fixture, the third bracket should be installed in the middle).
See page 2 for the mounting bracket location. -
Install Utility Box and Utility Box Cover
Determine power feed location, install
2″x4″ utility box (supplied by others) parallel to the fixture. The utility box must be installed at least 3.8” from the end of fixture. The bottom of the utility box must not be lower than the bottom of the fixture. Complete connections at box with supplied power cord. Attach cover bracket. Punch the power access hole in the cover, feed the power cord through, and attach strain relief and box cover. -
Install Leveler and Wire Cover
Place the levelling plate onto the bracket followed by the wire cover plate.
NOTE : Levelling plate and wire cover plate must be installed in this order as they will not be accessible afterward. -
Remove Dust Cover
Remove dust cover from fixture. -
Prepare Wiring
POWER LOCATIONS:
Remove required 1/2″ round knockout(s). Insert power cord and apply strain relief to secure cord. For easier installation, remove LED pan. -
Complete Electrical Connections
NON-POWER LOCATIONS: Cap all wires and tuck into wire cavity. POWER LOCATIONS:
Remove installed quick wire connectors (if applicable) at power feed locations and complete electrical connections using wire nuts (supplied by others). Tuck wires into wire cavity.
NOTE : Use smallest appropriate wire nuts. -
Raise Fixture and Engage on Wall Brackets
With two people, raise fixture into position and engage it on hooks located on top of wall brackets.
POWER LOCATIONS : Prior to engaging fixture in mounting brackets, feed installed power cord through the access hole at back of the fixture. -
Raise Fixture and Engage on Wall Brackets Once engaged on hooks, rotate fixture down into position.
-
Gasket Installation
Cut, peel and stick gasket to edge of luminaire as shown. Every fixture ends requires gasket installation. Please note two layers of gasket are required . -
Gasket Installation
Ensure gasket is seated properly. Gasket should not protrude overall luminaire width and height. -
Gasket Installation
Gasket shown in grey above. -
Adding Additional Fixture
In the event of a row, the mid run bracket needs to be installed instead of the end of run bracket. See page 2 for more details. -
Join Additional Fixture to Create Row
On the additional fixture, pull out the two tabs.
Repeat procedure for the luminaire it will be joined to. -
Join Additional Fixture to Create Row
Using a set of pliers, ensure that tabs are perpendicular to fixture. This is required to ensure proper engagement to opposite fixture. -
Join Additional Fixture to Create Row
With two people, raise second fixture to wall. Hook fixture on the wall mount bracket. -
Join Additional Fixture to Create Row
At joint, insert temporary hooks into suspended fixture. Ensure temporary hook is engaged on both fixtures.
IMPORTANT : Do not attempt to join fixtures on floor. Instead, hang one fixture at a time and join modules at ceiling level. -
Complete Electrical Connections
Complete in-row electrical connections.
NON-POWER LOCATIONS: Use supplied quick-wire connectors. Tuck wires into wire cavity.
POWER LOCATIONS : Remove installed quick-wire connectors and complete electrical connections using wire nuts (supplied by others). Tuck wires into wiring cavity. -
Join Additional Fixture to Create Row
SLIDE MODULES TOGETHER: Drop in the locking plate provided in the joint kit. Locking plate will interlock the two fixtures together. -
Join Additional Fixture to Create Row
Once locking plate is inserted, secure locking plate to the crossplate. Using a Philips head screw driver, tightened screws until the two fixtures pull together creating a seamless gap. -
Secure Fixture
Fold wall mount bracket on top of joint fixtures. Using the provided Philips screws, lock the wall mount bracket to the fixtures. -
Secure fixture
Repeat step 6. Fold wall mount bracket on top of fixture. Using the provided Philips screws, lock the wall mount bracket to the fixtures. -
Level Fixture
Level fixture using the 8-32 x ½” screw with a Philips screw driver. -
Gasket Installation
Cut, peel and stick gasket to edge of luminaire as shown. Refer to step 4-4.2 for more instructions. -
Install Endcaps
Place endcap on top of crossplate. Align to luminaire. -
Install Endcaps
Using the provide Philips screws (black), attach endcaps to bracket.
IMPORTANT : Do not over-tighten endcap fasteners. Signify Ledalite recommends tightening fasteners by hand. When screwhead is flush with crossplate, turn an additional full turn -
Install Dust Cover
Tuck in dust cover into fixture.
PRF/PRA Interact Pro Foundation/Advance Install & Setup
*not for Enterprise or Signify Commissioned projects
To configure a lighting system with Interact sensors or RF nodes;
- Ensure the luminaires are installed and powered on.
- Download the Interact Pro app from either Apple’s App Store (for iOS) or Google’s Play Store.
- Register by tapping Request access on the login screen in the app.
- Click or scan the QR codes below to view instructions for setup.
Sensors in Rows
Single Sensor Controlling Whole Row
-
Purple & brown (or purple & grey/pink) control wires MUST be connected between fixtures.
Note :- A maximum of 8 drivers can be wired to one sensor; confirm fixture driver count with factory.
Multiple Sensors Controlling Separate Zones in a Row
- A maximum of 8 drivers can be wired to one sensor; confirm fixture driver count with factory.
-
Purple & brown (or purple & grey/pink) control wires MUST NOT be connected between zones.
Notes:-
A maximum of 8 drivers can be wired to one sensor; confirm fixture driver count with factory.
-
Only one sensor is allowed on a wired zone. (Sensors can be paired together wirelessly via a mobile app).
Sensor Spacing -
For correct operation, sensors should be placed a minimum distance of 8ft apart.
-
Wireless sensors should be placed no further than 40ft apart for good wireless signal connection. Sensor Sensor
-
Important Consideration When Using Sensors in a Row
-
For fixtures with wireless sensors (CS, SB or RA options):
DO NOT connect fixture purple & brown (or purple & grey/pink) control wires to an external dimming switch. Fixture mains wiring should not be connected to a circuit with an external on/off switch. -
For best aesthetic condition, place sensors at ends of row only so as not to break the continuous lens.
-
For better occupancy coverage in longer rows, sensors may be placed mid run, but keep in mind this will break the continuous lens into discrete sections.
Occupancy Sensor Coverage:
Note : Longer dimension of detection area (Y1, Y2) is parallel to longer
dimension of the luminaire.
Daylight sensor
The light sensor measures the total amount of light in a circular field of
approximately 80% of the PIR detection area. The following aspects should be
observed during installation:
- Minimum distance from the window ≥2ft (0.6m).
- Prevent light reflections from outside entering the sensor (for example sunlight reflection on a car hood) as this will lead to incorrect light regulation.
As a guideline the formula 0.72 x H can be used to calculate the minimum distance between the window and sensor whereby H is the height from the bottom of the window to the sensor.
The detection area for the movement sensor can be roughly divided into two parts:
- Minor movement (person moving ≤3ft/s or 0.9m/s).
- Major movement (person moving ≥3ft/s or 0.9m/s).
Photosensor spatial response
ATTENTION: Install in accordance with local and national building and electric codes.
2021 Signify Holding. All rights reserved. The information provided herein is
subject to change, without notice. Signify does not give any representation or
warranty as to the accuracy or completeness of the information included herein
and shall not be liable for any action in reliance thereon. The information
presented in this document is not intended as any commercial offer and does
not form part of any quotation or contract, unless otherwise agreed by
Signify.
Signify North America Corporation 400 Crossing Blvd, Suite 600 Bridgewater, NJ
08807 Telephone: 855-486-2216
Signify Canada Ltd. 281 Hillmount Road, Markham, ON, Canada L6C 2S3 Telephone:
800-668-9008
All trademarks are owned by Signify Holding or their respective owners.
www.signify.com
References
- Quick Start Guide - PRA :: Interact
- Quick Start Guide - PRF :: Interact
- Contact us | Philips lighting
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>