TOSHIBA VN-U00151SY-E Air to Air Heat Exchangers Instruction Manual
- June 12, 2024
- Toshiba
Table of Contents
VN-U00151SY-E Air to Air Heat Exchangers
Product Information
Product Name: Heat Recovery Ventilation
Unit
Model Name: VN-U00151SY-E, VN-U00351SY-E,
VN-U00651SY-E, VN-U01001SY-E, VN-U00251SY-E, VN-U00501SY-E,
VN-U00801SY-E
Usage: Commercial
Language: English
Original Instruction: Yes
Product Usage Instructions
Please read the following instructions carefully before using
the Heat Recovery Ventilation Unit:
Definition of Qualified Installer or Qualified Service
Person
The Heat Recovery Ventilation Unit must be installed,
maintained, repaired, and removed by a qualified installer or
qualified service person. A qualified installer or qualified
service person is an agent who has the necessary qualifications and
knowledge described in the table below.
Agent | Qualified Installer | Qualified Service Person |
---|---|---|
Qualifications and Knowledge | 1-EN | 2-EN |
Definition of Protective Gear
When transporting, installing, maintaining, repairing, or
removing the Heat Recovery Ventilation Unit, it is important to
wear protective gloves and safety work clothing. Additionally,
specific protective gear must be worn for certain types of work as
mentioned in the table below to prevent injuries and accidents.
Work Undertaken | Protective Gear Worn |
---|---|
All types of work | Protective gloves, safety working clothing |
Electrical-related work | Gloves for electricians and protection from heat |
Work done at heights (50 cm or more) | Helmets for use in industry |
Transportation of heavy objects | Shoes with additional protective toe cap |
Safety Cautions
The following safety cautions are provided to prevent injury to
users, other people, and damages to property. Please read and
understand the meanings of the indications below:
-
WARNING: Text set off in this manner indicates
that failure to adhere to the directions in the warning could
result in serious bodily harm (1) or loss of life if the product is
handled improperly. -
CAUTION: Text set off in this manner indicates
that failure to adhere to the directions in the caution could
result in slight injury (2) or damage (3) to property if the
product is handled improperly.
1: Serious bodily harm indicates loss of
eyesight, injury, burns, electric shock, bone fracture, poisoning,
and other injuries that require hospitalization or long-term
treatment as an outpatient.
2: Slight injury indicates injury, burns,
electric shock, and other injuries that do not require
hospitalization or long-term treatment as an outpatient.
3: Damage to property indicates damage
extending to buildings, household effects, domestic livestock, and
pets.
HEAT RECOVERY VENTILATION UNIT
Installation Manual
Concealed Microcomputer Control Type
Model name:
VN-U00151SY-E VN-U00351SY-E VN-U00651SY-E VN-U01001SY-E
VN-U00251SY-E VN-U00501SY-E VN-U00801SY-E
For commercial use
English
1
Original instruction
Thank you very much for purchasing TOSHIBA Heat recovery ventilation unit.
Please read this owner’s manual carefully before using your Heat recovery
ventilation unit. · Obtain the “Owner’s manual” and “Installation manual” from
constructor (or dealer). Request to constructor or dealer · Please clearly
explain the contents of the Owner’s manual and hand over it.
· Read this Installation Manual thoroughly to fully understand everything
about your Toshiba Heat recovery ventilation unit and be able to install it
properly.
· Ask a qualified installer or qualified service person to perform
installation. · System parts such as a wired remote controller (sold
separately) are necessary for using this unit. · After installation, perform a
test operation and confirm the safety, then explain to the customer how to use
this unit. Give this installation manual to the customer and ask him / her to
keep it with the owner’s manual.
Handover to the customer
· Hand the owner’s manual and installation manual to the customer. · Before
the handover, explain fully to the customer the contents of the owner’s
manual.
Contents
1 Precautions for safety . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 3 2 Accessory parts . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 7 3 Cautions for installation . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 4
Reference diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 10 5 Installation . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 11 6 Electrical connection . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 7
Installation method for each system configuration . . . . . . . . . . . . . .
. . . . . . . . . . . 15 8 Advanced system. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 9
Advanced control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 30 10 Test run . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 39 11 Maintenance . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
39 12 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . 41 13 Fan characteristics.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 43
Please read carefully through these instructions that contain important information which complies with the “Machinery Directive” (Directive 2006/42/EC), and ensure that you understand them.
Generic Denomination: Heat recovery ventilation unit
Definition of Qualified Installer or Qualified Service Person
The Heat recovery ventilation unit must be installed, maintained, repaired and
removed by a qualified installer or qualified service person. When any of
these jobs is to be done, ask a qualified installer or qualified service
person to do them. A qualified installer or qualified service person is an
agent who has the qualifications and knowledge described in the table below.
Agent Qualified installer (1)
Qualified service person (1)
Qualifications and knowledge which the agent must have
· The qualified installer is a person who installs, maintains, relocates and
removes the Heat recovery ventilation unit made by Toshiba Carrier
Corporation. He or she has been trained to install, maintain, relocate and
remove the Heat recovery ventilation unit made by Toshiba Carrier Corporation
or, alternatively, he or she has been instructed in such operations by an
individual or individuals who have been trained and is thus thoroughly
acquainted with the knowledge related to these operations.
· The qualified installer who is allowed to do the electrical work involved in
installation, relocation and removal has the qualifications pertaining to this
electrical work as stipulated by the local laws and regulations, and he or she
is a person who has been trained in matters relating to electrical work on the
Heat recovery ventilation unit made by Toshiba Carrier Corporation or,
alternatively, he or she has been instructed in such matters by an individual
or individuals who have been trained and is thus thoroughly acquainted with
the knowledge related to this work.
· The qualified installer who is allowed to work at heights has been trained
in matters relating to working at heights with the Heat recovery ventilation
unit made by Toshiba Carrier Corporation or, alternatively, he or she has been
instructed in such matters by an individual or individuals who have been
trained and is thus thoroughly acquainted with the knowledge related to this
work.
· The qualified service person is a person who installs, repairs, maintains,
relocates and removes the Heat recovery ventilation unit made by Toshiba
Carrier Corporation. He or she has been trained to install, repair, maintain,
relocate and remove the Heat recovery ventilation unit made by Toshiba Carrier
Corporation or, alternatively, he or she has been instructed in such
operations by an individual or individuals who have been trained and is thus
thoroughly acquainted with the knowledge related to these operations.
· The qualified service person who is allowed to do the electrical work
involved in installation, repair, relocation and removal has the
qualifications pertaining to this electrical work as stipulated by the local
laws and regulations, and he or she is a person who has been trained in
matters relating to electrical work on the Heat recovery ventilation unit made
by Toshiba Carrier Corporation or, alternatively, he or she has been
instructed in such matters by an individual or individuals who have been
trained and is thus thoroughly acquainted with the knowledge related to this
work.
· The qualified service person who is allowed to work at heights has been
trained in matters relating to working at heights with the Heat recovery
ventilation unit made by Toshiba Carrier Corporation or, alternatively, he or
she has been instructed in such matters by an individual or individuals who
have been trained and is thus thoroughly acquainted with the knowledge related
to this work.
1-EN
2-EN
Definition of Protective Gear
When the Heat recovery ventilation unit is to be transported, installed,
maintained, repaired or removed, wear protective gloves and `safety’ work
clothing. In addition to such normal protective gear, wear the protective gear
described below when undertaking the special work detailed in the table below.
Failure to wear the proper protective gear is dangerous because you will be
more susceptible to injury, burns, electric shocks and other injuries.
Work undertaken All types of work
Electrical-related work Work done at heights (50 cm or more) Transportation of
heavy objects
Protective gear worn Protective gloves `Safety’ working clothing Gloves to provide protection for electricians and from heat Helmets for use in industry Shoes with additional protective toe cap
These safety cautions describe important matters concerning safety to prevent injury to users or other people and damages to property. Please read through this manual after understanding the contents below (meanings of indications), and be sure to follow the description.
Indication
Meaning of Indication
WARNING
Text set off in this manner indicates that failure to adhere to the directions in the warning could result in serious bodily harm (1) or loss of life if the product is handled improperly.
CAUTION
Text set off in this manner indicates that failure to adhere to the directions
in the caution could result in slight injury (2) or damage (3) to property if
the product is handled improperly.
1: Serious bodily harm indicates loss of eyesight, injury, burns, electric
shock, bone fracture, poisoning, and other injuries which leave aftereffect
and require hospitalization or long-term treatment as an outpatient.
2: Slight injury indicates injury, burns, electric shock, and other injuries
which do not require hospitalization or longterm treatment as an outpatient.
3: Damage to property indicates damage extending to buildings, household
effects, domestic livestock, and pets.
MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT Read the OWNER’S MANUAL carefully before operation.
Service personnel are required to carefully read the OWNER’S MANUAL and INSTALLATION MANUAL before operation.
Further information is available in the OWNER’S MANUAL, INSTALLATION MANUAL, and the like.
Warning indications on the Heat recovery ventilation unit
Warning indication
Description
WARNING
ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before
servicing.
WARNING
ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before
servicing.
WARNING
Moving parts. Do not operate unit with inspection cover removed. Stop the unit
before the servicing.
WARNING
Moving parts. Do not operate unit with inspection cover removed. Stop the unit
before the servicing.
CAUTION
High temperature parts. You might get burned when removing this cover.
CAUTION
High temperature parts. You might get burned when removing this cover.
3-EN
2
4-EN
3
1 Precautions for safety
The manufacturer shall not assume any liability for the damage caused by not
observing the description of this manual.
WARNING
General · Before starting to install the Heat recovery ventilation unit, read
carefully through the Installation Manual, and follow its instructions to
install the Heat recovery ventilation unit. · Only a qualified installer (1)
or qualified service person (1) is allowed to install the Heat recovery
ventilation unit. If the Heat recovery ventilation unit is installed by an
unqualified individual, a fire, electric shocks, injury, water leakage, noise
and/or vibration may result. · If using separately sold products, make sure to
use Toshiba specified products only. Using unspecified products may cause
fire, electric shock, water leak or other failure. · Before opening the
electrical control cover or inspection cover of the Heat recovery ventilation
unit, set the circuit breaker to the OFF position. Failure to set the circuit
breaker to the OFF position may result in electric shocks through contact with
the interior parts. Only a qualified installer (1) or qualified service
person (1) is allowed to remove the electrical control cover or inspection
cover of the Heat recovery ventilation unit and do the work required. · Before
carrying out the installation, maintenance, repair or removal work, set the
circuit breaker to the OFF position. Otherwise, electric shocks may result. ·
Place a “Work in progress” sign near the circuit breaker while the
installation, maintenance, repair or removal work is being carried out. There
is a danger of electric shocks if the circuit breaker is set to ON by mistake.
· Only a qualified installer (1) or qualified service person (1) is allowed
to undertake work at heights using a stand of 50 cm or more or to remove the
electrical control cover or inspection cover of the Heat recovery ventilation
unit to undertake work. · Wear protective gloves and safety work clothing
during installation, servicing and removal.
5-EN
· When working at heights, use a ladder which complies with the ISO 14122
standard, and follow the procedure in the ladder’s instructions. Also wear a
helmet for use in industry as protective gear to undertake the work.
· When cleaning the filter or heat exchange element of the Heat recovery
ventilation unit, set the circuit breaker to OFF without fail, and place a
“Work in progress” sign near the circuit breaker before proceeding with the
work.
· When working at heights, put a sign in place so that no-one will approach
the work location, before proceeding with the work. Parts and other objects
may fall from above, possibly injuring a person below.
· The Heat recovery ventilation unit must be transported in stable condition.
In case an accident such as dropping of the unit occurs while transporting the
Heat recovery ventilation unit, contact the dealer.
· Do not move or repair any unit by yourself. There is high voltage inside the
unit. You may get electric shock when removing the cover and main unit.
· Do not modify the products. Do not also disassemble or modify the parts. It
may cause a fire, electric shock or injury.
· Confirm whether there is a risk of the Heat recovery ventilation unit
falling down during maintenance or repairing work.
· Before opening the Supply / Exhaust air grill, set the circuit breaker to
the OFF position. Otherwise, your hand may be caught in the rotating parts
inside and an injury may result.
Selection of installation location · Do not install the Heat recovery
ventilation unit in a location that may
be subject to a risk of exposure to a combustible gas. If a combustible gas
leaks and becomes concentrated around the unit, a fire may occur. · When
transporting the Heat recovery ventilation unit, wear shoes with additional
protective toe caps, protective gloves and other protective clothing. · When
transporting the Heat recovery ventilation unit, do not take hold of the bands
around the packing carton. You may injure yourself if the bands should break.
· Install the Heat recovery ventilation unit at least 2.5 m above the floor
level since otherwise the users may injure themselves or receive electric
shocks if they poke their fingers or other objects into the Heat recovery
ventilation unit while it is running.
6-EN
· Do not place any combustion appliance in a place where it is directly
exposed to the wind of Heat recovery ventilation unit, otherwise it may cause
imperfect combustion.
· Use a hand track or forklift to carry the unit. When carrying it by human
power, have four persons otherwise, you may strain your back.
· Do not install the place where there is a wind flow that rotates the fan
while operation is stopped. (If the Heat recovery ventilation unit is
connected to other booster fans or Fresh air intake unit through a common
duct, the Heat recovery ventilation unit may not operate if the fan is
rotating while operation is stopped.)
Installation · Use a winch or hoist to install Heat recovery ventilation unit.
· When the Heat recovery ventilation unit is to be suspended, the
designated hanging bolts (M10 to M12) and nuts (M10 to M12) must be used. ·
Install the Heat recovery ventilation unit at enough strong places to
withstand the weight of the unit. If the strength is not enough, the unit may
fall down resulting in injury. · Follow the instructions in the Installation
Manual to install the Heat recovery ventilation unit. Failure to follow these
instructions may cause the product to fall down or topple over or give rise to
noise, vibration, water leakage, etc. · When connecting other booster fans to
the common duct with Heat recovery ventilation unit, be sure to link the
operation with Heat recovery ventilation unit.
Electrical wiring · Only a qualified installer (1) or qualified service
person (1) is
allowed to carry out the electrical work of the Heat recovery ventilation
unit. Under no circumstances must this work be done by an unqualified
individual since failure to carry out the work properly may result in electric
shocks and/or electrical leaks. · When repairing the electrical parts or
undertaking other electrical jobs, wear gloves to provide protection for
electricians and from heat. Failure to wear this protective gear may result in
burn. · Use wiring that meets the specifications in the Installation Manual
and the stipulations in the local regulations and laws. Use of wiring which
does not meet the specifications may give rise to electric shocks, electrical
leakage, smoking and/or a fire.
· Connect earth wire. (Grounding work) Incomplete earthing causes an electric
shock.
· Do not connect earth wires to gas pipes, water pipes, and lightning rods or
earth wires for telephone wires.
· After completing the repair or relocation work, check that the earth wires
are connected properly.
· Install a circuit breaker that meets the specifications in the installation
manual and the stipulations in the local regulations and laws. Use an
exclusive power supply circuit for the Heat recovery ventilation unit at the
rated voltage.
· Install the circuit breaker where it can be easily accessed by the agent.
· When installing the circuit breaker outdoors, install one which is designed
to be used outdoors.
· Under no circumstances must the power cable be extended. Connection trouble
in the places where the cable is extended may give rise to smoking and/or a
fire.
· Electrical wiring work shall be conducted according to law and regulation in
the community and installation manual. Failure to do so may result in
electrocution or short circuit.
· When carrying out electric connection, use the wire specified in the
Installation Manual and connect and fix the wires securely to prevent them
applying external force to the terminals. Improper connection or fixing may
result in fire.
7-EN
4
8-EN
5
Test run · Before operating the Heat recovery ventilation unit after having
completed the work, check that the electrical control cover and inspection
cover are closed, and set the circuit breaker to the ON position. You may
receive an electric shock if the power is turned on without first conducting
these checks. · When there is some kind of trouble (such as when a check code
display has appeared, there is a smell of burning, abnormal sounds are heard,
or water is leaking) has occurred in the Heat recovery ventilation unit, do
not touch the Heat recovery ventilation unit yourself but set the circuit
breaker to the OFF position, and contact a qualified service person. Take
steps to ensure that the power will not be turned on (by marking “out of
service” near the circuit breaker, for instance) until qualified service
person arrives. Continuing to use the Heat recovery ventilation unit in the
trouble status may cause mechanical problems to escalate or result in electric
shocks, etc. · After the work has finished, use an insulation tester set (500
V Megger) to check the resistance is 1 M or more between the charge section
and the non-charge metal section (Earth section). If the resistance value is
low, a disaster such as a leak or electric shock is caused at user’s side. ·
Upon completion of the installation work, check the insulation resistance.
Then conduct a test run to check that the Heat recovery ventilation unit is
operating properly.
Explanations given to user · Upon completion of the installation work, tell
the user where the circuit
breaker is located. If the user does not know where the circuit breaker is, he
or she will not be able to turn it off in the event that trouble has occurred
in the Heat recovery ventilation unit. · After the installation work, follow
the Owner’s Manual to explain to the customer how to use and maintain the
unit. · If there is a danger of the Heat recovery ventilation unit falling, do
not approach the Heat recovery ventilation unit but set the circuit breaker to
the OFF position, and contact a qualified service person (*1) to have the
repairs done. Do not set the circuit breaker to the ON position until the
repairs are completed.
Relocation · Only a qualified installer (1) or qualified service person (1)
is
allowed to relocate the Heat recovery ventilation unit. It is dangerous for
the Heat recovery ventilation unit to be relocated by an unqualified
individual since a fire, electric shocks, injury, water leakage, noise and/or
vibration may result.
(*1) Refer to the “Definition of Qualified Installer or Qualified Service
Person”.
9-EN
10-EN
CAUTION
· The external air intake opening should be positioned away from the exhaust
openings of combustion gases. The intake of such gases could cause a lack of
oxygen in the room. The external air intake opening should not be positioned
where discharged air may directly enter it. A situation like this will lead to
the room being contaminated and this may pose a health risk.
· Netting or something similar should be provided at the external air intake
opening to prevent birds or other things interfering with the unit.
· Nests or other foreign objects should be removed. That could cause a lack of
oxygen in the room.
· To pierce the metal duct through the metal lath or the wire lath or the
metal plate of the wooden facility, do not forget to insulate electrically
between the duct and the wall. Otherwise, it would cause an electric shock or
an electric leakage.
· Install the outdoor duct in a falling gradient toward the outside so as to
prevent water from coming in. If it is not installed so, the building is
likely to be flooded, wetting the household effects.
· Heat-insulate the outdoor duct (including the indoor side, if necessary) to
prevent dewing. If heat insulation is not adequate, water likely goes indoor
and wets the household properties.
· When it is high humid and high temperature inside the ceiling, a ventilation
system must be installed inside the ceiling. Otherwise, it could cause a fire
or an electric leakage.
· Install the power line and the connecting line with accuracy so the power
source cover may not float. If the installation of the electrical control
cover is inappropriate, the pin connection area is likely to cause a heat
generation, a fire and an electric shock due to dust or powder.
· Do not use the unit at the other voltages than the rated one. It could cause
a fire or an electric shock.
· Do not install the unit in locations with large amounts of oily smoke, such
as food preparation areas. It could cause a fire.
· Do not install the unit at the place of a high temperature or a flame. It
could cause a heat generation or a fire.
· Do not install in locations with high humidity, such as close to bathroom or
other similar environment. It could cause an electric shock or an electric
leakage or other troubles.
· Install an earth leakage breaker that is not tripped by shock waves. If an
earth leakage breaker is not installed, an electric shock may be caused.
· Do not install the unit and inside air intake in a place such as a machine
factory, chemical plant, or research institute, where acids, alkaline, organic
solvents, or coating materials are handled and toxic gases and/or corrosive
gases may be produced. Otherwise gas poisoning may occur and/or the inside of
the unit may be eroded or deteriorated. The deterioration and erosion may
result in a fire.
· After installation, switch off the circuit breaker for safety if the unit
will not be used for a long time.
· Attach the parts such as the inspection cover securely.
To disconnect the appliance from main power supply · This appliance must be
connected to the main power supply by
means of a switch with a contact separation of at least 3 mm.
Disposal
Dispose of Heat recovery ventilation unit in accordance with the Directive
2012/19/EU WEEE (Waste Electrical and Electronic Equipment).
11-EN
6
12-EN
2 Accessory parts
Name
Installation manual
CD-ROM (Owner’s manual and Installation manual)
Owner’s manual
Quantity 1 1 1
Shape — — —
Usage
(Hand it to the customers.)
(For other languages that do not appear in this manual, please refer to the
enclosed CD-ROM.)
(Hand it to the customers.)
Seal material
3
For sealing of wire connecting port
(50 × 50 × 3 t)
3 Cautions for installation
Make the inspection opening at the specific place on the ceiling so the constant cleaning or the equipment checking of filter and heat exchange element can be performed. Be sure to clean filter and heat exchanger element once or twice a year to prevent their degradation of performance or condensation.
· The inspection opening shown below is necessary to clean the heat exchange
element and the filter as required. If not cleaned, they are likely to get
clogged, resulting in degradation of performance.
· Use forklift to carry in the Heat recovery ventilation units and use winch
or hoist at installation of them.
VN-U00151SY-E
Heat exchange element 716
25
Unit: mm
278
102.5
791
530
735
EA (Exhaust Air)
Outdoor side
OA (Outdoor Air)
RA (Return Air)
Indoor side
SA (Supply Air)
13
102.5
18
98.7
778
98.7
23.2
45
301.5
167.3
25
158.2
7
VN-U00251SY-E
Heat exchange element 716
102.5
530
735
EA (Exhaust Air)
Outdoor side
OA (Outdoor Air)
13
18
109.2
35.2
68
778 301.5
167.3
RA (Return Air) Indoor side SA (Supply Air)
109.2
102.5
Ø145 Ø166.2
Inspection cover
Fixing bracket
Filter (Two for each element)
VN-U00351SY-E
Heat exchange element (Two) 818
125
630
880
EA (Exhaust Air)
Outdoor side
OA (Outdoor Air)
RA (Return Air)
Indoor side
SA (Supply Air)
125
13
Ø98 Ø117
Inspection cover
Fixing bracket
Filter (Two for each element)
Weight: 29 kg Heat exchange element: 1
18
109.2
35.2
68
880 330.5
109.2
Inspection cover
Fixing bracket Filter (Two for each element)
Ø145 Ø166.2
13-EN
166.5 25
936
25
25
791
25
Unit: mm
278
158.2
Weight: 29 kg Heat exchange element: 1
Unit: mm
305
152.5
Weight: 40 kg Heat exchange element: 2
14-EN
VN-U00501SY-E, U00651SY-E
Heat exchange element (Two) 858
150
720
1020
150
EA (Exhaust Air)
Outdoor side
OA (Outdoor Air)
13
18
119.2
920
66.8
78
363
166.5
RA (Return Air) Indoor side SA (Supply Air)
119.2
25
1076
25
Unit: mm
337
168.5
Ø195 Ø225.2
Inspection cover
Fixing bracket Filter (Two for each element)
Weight: 47 kg Heat exchange element: 2
VN-U00801SY-E, U01001SY-E
Heat exchange element (Two) 1068
175
880
1230
EA (Exhaust Air)
Outdoor side
OA (Outdoor Air)
18
13
134.2
98
82.5
1130 411
175
166.5
RA (Return Air) Indoor side SA (Supply Air)
134.2
25
1286
25
Unit: mm
386
193
Ø245 Ø274.9
Inspection cover
Fixing bracket Filter (Two for each element)
Weight: 63 kg Heat exchange element: 2
15-EN
8
16-EN
9
· Helmet must be worn to protect your head from falling objects. Especially,
when you work under an inspection opening, helmet must be worn to protect your
head from falling objects from the opening.
The manufacturer shall not assume any liability for the damage caused by not
observing the description of following.
Observe the following conditions when using the Heat recovery ventilation unit
Installation requirements Outdoor air conditions Return air conditions
: Temperature range -15°C to +50°C, relative humidity 80% or less : Temperature range -20°C to +52°C, relative humidity 80% or less : Temperature range +5°C to +40°C, relative humidity 80% or less
· If Heat recovery ventilation unit is used under conditions in which air after heat exchange is saturated, condensation or frosts occur in the heat exchange element. When such condition is expected, use the heater by heating air at the low temp side. (For the detail, refer to “Dewing and frosting”)
· Do not install the Heat recovery ventilation unit in a place where flames can come into contact with the unit. If the Heat recovery ventilation unit is used for a long time without observing the conditions above, deterioration or deformation of resin parts will occur and a malfunction may result.
Do not use the Heat recovery ventilation unit in location such as kitchen,
bathroom, swimming pool or air conditioning cultivation room etc.
· Use of it in the location where large amount of soot are present leads to
the clogging in the filter or in the heat exchanger element, cause not to
function properly.
· Use of it in the location where high humidity is present can cause
condensation water drops from the inside of the unit.
Dewing and frosting
· In cold regions, the surface (or inside) of the unit or the duct connector
may be affected by condensation or frosting depending on the outdoor air
conditions or temperature / humidity of the ceiling cavity even though the
conditions for use are observed. In this case, add a heat insulator.
· Do not install the unit in a place where there is something that must not
become wet. Depending on the temperature or humidity of outdoor air and the
installation place, water droplets may fall from the unit.
· As shown in the figure to the below, suppose a high temp absorbing air
condition A and a low temp absorbing air condition B are plotted on the air
line figure, then a high temp air A is heat-exchanged by the unit and goes out
of the saturation curve as shown by Point C. In this case, the unit will be
dewed or frosted. To avoid this, heating a low temp air B up to B’ is required
so as to get C’ below the saturation curve, before using the unit.
Saturation Curve Absolute humidity (kg/kg’)
A
C C’
B B’
Dry-bulb temperature (°C)
17-EN
· Calculation example from Psychrometric chart When the temperature exchange efficiency is 73.5% and the enthalpy efficiency is 60.5%
Example 1
In the following conditions, since the air after heat exchange is not saturated, condensation will not occur in the heat exchange element.
Suction air at the high temp side Suction air at the low temp side Air after heat exchange
Dry-bulb temp [°CDB]
Wet-bulb temp [°CWB]
A
35
29
B’
20
17
C’
24
22.5
Humidity [%] 64.3 60.9 77.1
Example 2
In the following conditions, since the air after heat exchange is saturated and dew condensation occurs in the heat exchanger element, use heater by heating the air from point B to point B’. (Humidity of point C’ should be less than 90% as a guide.)
Suction air at the high temp side Suction air at the low temp side Air after heat exchange
Dry-bulb temp [°CDB]
Wet-bulb temp [°CWB]
A
35
31.8
B
18
14
C
22.5
(22.5)
Humidity [%] 80 65
100
Suction air at the high temp side Suction air at the low temp side Air after heat exchange
Dry-bulb temp [°CDB]
Wet-bulb temp [°CWB]
A
35
31.8
B’
22.1
17.7
C’
25.6
24.3
Humidity [%] 80 65
89.7
· Our Heat recovery ventilation unit has been tested under condensation test
condition described in JIS B 8628, “Air-to-air heat and energy exchanger and
ventilators” and found that condensation water does not drop. Due to changes
in temperature and humidity, dew condensation occurs even under similar
conditions, may cause condensation water to drop from the inside of the unit.
· Be sure to cover two ducts (OA, EA) at the outdoor side with heat insulators
(Material: Glass Wool, Thickness25 mm or more) to prevent condensation and
slope them downward to the outdoor side. (For its detail, refer
to “5. Installation Duct installation”)
· When the inside of the room is cooled by another air conditioner during the
summer season and the surrounding of the Heat recovery ventilation unit is
expected to become high temperature and high humidity, covering also two ducts
at the indoor side with the heat insulators to prevent condensation is
recommended.
· If the unit sucks high moisture air such as fog (relative humidity of 80% or
more), condensation water may drop from the unit. Do not operate the Heat
recovery ventilation unit temporarily while high moisture air is present.
When such a condition is expected, avoid setting the 24-hour ventilation and
the nighttime heat purge.
· Use of Heat recovery ventilation unit in bypass mode in winter may cause
condensation on the inside of the product or its discharge port. When such a
condition is expected, use it in heat exchange mode.
· In cold areas where the wind is strong, due to the outside air sometimes
entering while the Heat recovery ventilation unit stops, use of the unit in
combination with an intermediate mounting type electric shutter is
recommended.
· Do not install the unit near the water heater.
18-EN
· Refrain from the following duct installation works.
-
Excessive bending
-
Multi-times bending
-
Making the connecting duct 4) Bending near the exhaust air
smaller
duct
· Do not install it near the water-heater · Do not use in bathrooms or food
preparation areas or in similar condition place.
If the unit is used at the place of much soot and high humidity large amounts
of oily smoke, the filter or the heat exchange element gets clogged and it
will be disable to be use. · Duct length must be longer than 850 mm.
4 Reference diagram
Pipe hood
Outdoor air intake duct
Hanging bolt Supply air duct
SA (Supply air)
Heat insulation material
OA (Outdoor air)
EA (Exhaust air)
Exhaust air duct
RA (Return air)
Return air intake duct
Inside supply opening (Supply / Exhaust air grille)
Room intake opening (Supply / Exhaust air grille)
19-EN
10
20-EN
5 Installation
Attaching the washer and the nut
- Preparation of the hanging bolt, nut, and washer is required.
- Attach the washer and the nut to the hanging bolt (see the table on the below) according to the diagram on the below.
Hanging bolt (M10 or M12) Nut (M10 or M12)
Hanging bracket
Washer (M10 or M12)
Washer (M10 or M12)
Use the washer just under the hanging bracket to prevent the bolt from falling
off.
Nut (M10 or M12)
Fixing the unit
Hanging bolt (M10 or M12)
Hanging bolt
Nut Washer Hanging bracket
Washer Nut
- Hang the hanging bracket on the hanging bolt, then adjust the nut so that the unit is level.
- Use a double nut and fasten it firmly so that the nut does not become
loose.
· If the unit is not installed properly, it will vibrate and may pose a hazard.
· If the unit is not level, the damper unit will not work properly.
· Install the unit firmly enough to support its own weight.
11
B
Unit: mm
D
Cautions installing unit body upside down
· The hanging bracket does not need to be replaced. · The printed image is
reversed. · The EA adapter need to upside down.
Standard installation
EA (Exhaust
Air)
Outdoor side
OA (Outdoor
Air)
RA (Return Air)
Indoor side
SA (Supply Air)
C
Screws
Electrical control box
Upside down installation
A
150 to 250
E or more
160 Maintenance space
Check port 450 or more
Model VN-U0***1SY-E
A
B
C
D
E
015 / 025
735 778 791 716 700
035
880 880 936 818 600
050 / 065 1020 920 1076 858 600
080 / 100 1230 1130 1286 1068 600
CAUTION
· Use a commercially available vibration-proof fixture when the unit is
installed in a place where preventing vibration is necessary.
· Leave a space of 450 mm × 450 mm or more for checking the filter, heat
exchanging element, power source, or motor. Refer to “3. Cautions for
installation” for the location of the space required.
Hanging bolt Vibration-proof fixture
Vibration-proof fixture
Unit
Electrical control box
Duct installation
· Duct installation is necessary to protect against access to live parts, rain
water or contact with moving parts.
· Seal the junction of an adaptor and a duct with an aluminium tape firmly to
prevent any air leakage. · The room intake opening should be positioned as far
as possible from the indoor supply opening.
· Use the specified ducts. (See the Model List)
· Install two outdoor ducts so they will be in the down gradient toward
outdoor to prevent water from coming in. (Gradient: 1/100 to 1/50) (See the
figure below) Heat-insulate two outdoor ducts (including outdoor air and
exhaust air duct) to prevent dewing. (Material: Glass Wool, Thickness-25 mm)
(See the figure below) To pierce the metal duct through the metal lath or the
wire lath or the metal plate of the wooden facility, insulate electrically
between the duct and the wall. (Refer to the laws and regulations of the
country concerned and the technical standard.)
· When fixing the duct with screws, fix them so that the screws are in the
hatched areas in the figure below.
Heat insulator
Aluminium tape
When using duct connection screws
Duct
Unit
Adapter
Hatched area
Heat insulator (Insulates the adapter and the aluminium tape) Outdoor air
intake duct, Exhaust air duct
Slope (1/100 to 1/50)
Aluminium tape
Aluminium tape
21-EN
22-EN
6 Electrical connection
WARNING
· Use the specified wires for wiring connection to the terminals. Securely fix
them to prevent external forces applied to the terminals from affecting the
terminals. Incomplete connection or fixation may cause a fire or other
trouble.
· Connect earth wire. (grounding work) Incomplete earthing cause an electric
shock. Do not connect earth wires to gas pipes, water pipes, lightning
conductor or telephone earth wires.
· Appliance shall be installed in accordance with national wiring regulations.
Capacity shortage of power circuit or incomplete installation may cause an
electric shock or a fire.
CAUTION
· The wire size and wire length of the communication line differs depending on
the outdoor unit series to be connected.
· If incorrect / incomplete wiring is carried out, it will cause an electrical
fire or smoke. · Install an earth leakage breaker that is not tripped by shock
waves.
If an earth leakage breaker is not installed, an electric shock may be caused.
· Use the cord clamps attached to the product. · Do not damage or scratch the
conductive core and inner insulator of power and control wires when peeling
them. · Use the power supply wire and control wires of specified thickness,
type, and protective devices required. · Do not connect 208 to 240 V power to
the terminal blocks (Uv (U1)), (Uv (U2)), (A), (B) for control wiring.
(Otherwise,
the system will fail.) · Perform the electric wiring so that it does not come
to contact with the high-temperature part of the pipe.
The coating may melt resulting in an accident.
REQUIREMENT
· For power supply wiring, strictly conform to the Local Regulation in each
country. · After connecting wires to the terminal blocks, provide a trap and
fix wires with the cord clamp.
Power supply wire and communication wires specifications
Power supply wire and communication wires are locally procured. For the power
supply specifications, follow to the table below. If capacity is little, it is
dangerous because overheat or burnout may be caused. · Power supply wire
specification: Cable 3-core 2.5 mm², in conformity with Design 60245 IEC 57.
Power supply
Power supply
220 – 240 V, 50 Hz 208 – 230 V, 60 Hz
Power supply switch / circuit breaker or power supply wiring / fuse rating for Heat recovery ventilation units should be selected by the accumulated total current values of the Heat recovery ventilation units.
Power supply wiring
Below 50 m
3 × 2.5 mm2 (power supply and earth)
Control wiring, Central controller wiring
· 2-core with non-polarity wires are used for the Control wiring between Heat
recovery ventilation unit and Central controller wiring.
· To prevent noise trouble, use 2-core shield wire.
Communication line
TU2C-Link models (U series) can be combined with TCC-Link models (other than U series). For details of communication type, refer to the following table.
Communication type and model names
Communication type
TU2C-Link (U series and future models)
Outdoor unit
MMY-MUP This letter indicates U series model.
Indoor unit
MM -UP This letter indicates U series model.
Heat recovery ventilation unit
VN-U SY This letter indicates U series model.
Wired remote controller
RBC-A U This letter indicates U series model.
Wireless remote controller kit & receiver unit
RBC-AXU This letter indicates U series model.
Remote sensor
TCB-TC U This letter indicates U series model.
TCC-Link (Other than U series) Other than U series MMY-MAP MCY-MHP Other than
U series MM -AP
Other than U series
Other than U series
Other than U series
Other than U series
U series outdoor unit: SMMS-u (MMY-MUP ) Other than U series outdoor unit: SMMS-i, SMMS-e etc. (MMY-MAP )
23-EN
12
24-EN
13
<In the case of combining with outdoor units of Super Modular Multi System u
series (SMMS-u)>
Follow the wiring specifications in the table below even when units other than
U series are mixed in the indoor units and remote controllers to be connected.
Uv line and Uc line (L2, L3, L4) (2-core shield wire, non-polarity)
Uh line (L1) (2-core shield wire, non-polarity)
Wire size: Wire size:
1.0 to 1.5 mm²
1.0 to 1.5 mm² 2.0 mm²
(Up to 1000 m)
(Up to 1000 m) (Up to 2000 m)
· U (v, h, c) line means of control wiring. Uv line: Between indoor and
outdoor units. Uh line: Central control line. Uc line: Between outdoor and
outdoor units.
· Uv line and Uc line are independent from another refrigerant line. Total
length of Uv and Uc lines (L3 + L4)
in each refrigerant line is up to 1000 m.
REQUIREMENT
For connection of Uv line / Uc line or Uh line, wire each line using wires
with the same type and size. If different wire types and size are mixed and
used in a system, communication trouble is caused.
System of U series
[Uh line] L1 = Up to 2000 m
Central control device
Outdoor unit
Uh U3 U4
L1
U3 U4
Uh
Uv
Uc
U1 U2 U5 U6
U3 U4
Uh
Uv
Uc
U1 U2 U5 U6
U3 U4
Uh
Uv
Uc
U1 U2 U5 U6
L4
L2
L3
[Uv and Uc line] L2 = Up to 1000 m (L3 + L4) = Up to 1000 m
Heat recovery ventilation unit
U3 U4 Uh
AB
U3 U4 Uh
AB
Indoor unit
U1 U2
U1 U2
U1 U2
U1 U2
Uv
Uv
Uv
Uv
AB
AB
AB
AB
(*1)
Remote controller
U3 U4 Uh
AB
U3 U4 Uh
AB
Heat recovery ventilation unit
<In the case of combining with outdoor units other than Super Modular Multi System u series (SMMS-u)>
Control wiring between indoor units, and outdoor unit (L2, L3) (2-core shield
wire, non-polarity)
Central control line wiring (L1) (2-core shield wire, non-polarity)
Control wiring between outdoor units (L4) (2-core shield wire, non-polarity)
1.25 mm² Wire size:
2.0 mm²
(Up to 1000 m) (Up to 2000 m)
Wire size: 1.25 to 2.0 mm² (Up to 100 m)
· The length of the communication line (L1 + L2 + L3) means the total length of the inter-unit wire length between indoor and outdoor units added with the central control system wire length.
REQUIREMENT
For connection of between indoor and outdoor units line / between outdoor and
outdoor units line or central control line, wire each line using wires with
the same type and size. If different wire types and size are mixed and used in
a system, communication trouble is caused.
Combination system of U series and others
Central control device
Uh U3 U4
Outdoor unit
U3 U4
U3 U4
L1
U3 U4
U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6
L4
L2
L3
[Communication line] (L1 + L2 + L3) = Up to 2000 m L4 = Up to 100 m
Heat recovery ventilation unit
U3 U4 Uh
AB
U3 U4 Uh
AB
Indoor unit
U1 U2
U1 U2
U1 U2
U1 U2
Uv
Uv
Uv
Uv
AB
AB
AB
AB
(*1)
Remote controller
U3 U4 Uh
AB
U3 U4 Uh
AB
Heat recovery ventilation unit
*1. This connection is prohibited. Connect the Heat recovery ventilation unit (U series) with U3 and U4 line.
*1. This connection is prohibited. Because central controller cannot recognize Heat recovery ventilation unit and cannot operate Heat recovery ventilation unit at all. (Heat recovery ventilation does not appear in central controller.)
25-EN
26-EN
Remote controller wiring
· 2-core with non-polarity wire is used for the remote controller wiring and group remote controllers wiring.
Remote controller wiring, remote controller inter-unit wiring
Wire size: 0.5 to 2.0 mm²
Total wire length of remote controller wiring and remote controller inter-unit wiring = L + L1 + L2 + … Ln
In case of one remote controller
In case of two remote controller
Max. length of each remote control wiring between indoor units = L1, L2, …, Ln
Up to 500 m Up to 300 m Up to 200 m
CAUTION
· The remote controller wire (Communication line) and AC 208 to 240 V wires
cannot be parallel to contact each other and cannot be stored in the same
conduits. If doing so, a trouble may be caused on the control system due to
noise or other factor.
· If U series models (TU2C-Link) are combined with models other than U series
(TCC-Link), the wiring specifications and maximum number of connect-able
indoor units will be changed. Pay attentions to their communication
specifications when carrying out the installation, maintenance, or repair. For
its details, refer to the “Communication line” in “6. Electrical connection”.
Heat recovery ventilation unit
Remote controller L wiring
Remote controller
Heat recovery ventilation unit
Heat recovery ventilation unit
Heat recovery ventilation unit
L1
L2
Remote controller inter-unit wiring
Ln
For number of Max. connect-able units, refer to the following table.
Max. number of connect-able indoor units, and communication type
Unit type
Outdoor unit
U series U series U series U series
Indoor unit (including Heat recovery ventilation unit)
U series
U series
U series U series
Remote controller Remote sensor
U series
U series
U series
U series
Communication type
TU2C-Link
TCC-Link
Max. number of connect-able units
16
8
- DN code setting of Heat recovery
Not
ventilation unit about
necessary
communication type
- DN code
(factory
default)
Necessary * DN code FC: 0000
: Other than U series
REQUIREMENT
After carrying out installation of additional indoor unit, relocation, or
repairing, set the addresses again. For its detail, refer to the Installation
Manual attached to the outdoor unit.
Wire connection
Remove the 2 screws and loosen the 2 screws on the front surface of the
electric control cover to open the
cover.
· Make a cut in the bushing and connect the power supply wire (R (L), S (N))
and the remote controller wire (A, B). · Connect the central control wire U3,
U4 or the external output terminal block (1 to 5) if necessary. · Tighten the
screws on the terminal board firmly, then fix the wiring on the electrical
control box using the
accessory cord clamp. · Perform grounding work. · Attach the electrical
control cover so that wires are not pinched. · Refer to “7. Installation
method for each system configuration” about setting the switch and DN setting.
· After wiring is completed, stick the seal material over the bushing. The
seal material is accessory parts.
Screw (Remove) Electrical control box
After connecting the wire, cut the attached seal material as the drawing, and
stick on the wire connecting port.
Cut
Screw (Remove)
Electrical control cover
Attached seal material
Screws (Loosen)
Communication wire terminal block Wiring for the central control (U3, U4)
Wiring for the remote controller (A, B)
Power supply terminal block (R(L), S(N))
RS
Electrical control box Ground screw Cord clamp Remote controller wire In a
central control system, connect the copper braid shield of central control
wire (2-core shielded wire).
Central control wire
Bushing
Earth screw
Power supply wire
Select side C or D for the cord clamp position referring to the following table according to the cable type and diameter. * Cord clamp can be attached on either right or left side. When twin system are connected, clamp two cables with one cord clamp.
Wire type Cabtyre cable Cabtyre cable
Specification 3-core stranded wire 2.5 mm² 3-core stranded wire 1.5 mm²
Cord clamping position
Side C
Side D
Side C (Space: 8.5 mm)
Side D (Space: 4 mm)
27-EN
14
28-EN
Power supply wire
40
Earth wire
S(N) R(L)
25
Central control wire
40
10
15
Remote controller wire
10
15
REQUIREMENT
· Pass the wires through the grommet of wiring connection holes of the Heat
recovery ventilation unit. · Keep a margin (Approx.100 mm) on a wire. · The
low-voltage circuit is provided for the remote controller.
Switching between extra high and high (Remote controller-less setting)
Change the “extra-high/high” setting with the DIP switch “SW701-3” on the P.C.
board (MCC-1784). * Once the Set data has been changed by the DIP switch, to
reset it to 0000, it need changing using remote
controller (sold separately). Change the DN code to 0000. After setting has
been completed, restart the Heat recovery ventilation unit and check the
operation is no ploblem.
However, the factory default of DN code [5D] is “Extra High”, so basically
setting change is not necessary.
SW701-3
- DIP SW setting change is necessary for all the Heat recovery ventilation unit in the group.
SW701 ON ON
OFF 1 2 3 4
ON: Extra-high OFF: Free (Factory default)
15
7 Installation method for each system
configuration
Settings and electric wiring differ depending on the system configuration. Perform electric wring according to the system examples shown in the table below. (Refer to page 20 to 23 for details.)
System example
A Heat recovery ventilation unit system (One Heat recovery ventilation unit is
used.)
Heat recovery ventilation unit AB
AB
AB
RBC-AW(M)SU5*
Operation
· Using the remote controller for the Heat recovery ventilation unit RBC-
AW(M)SU5*, the unit can be started or stopped, control the ventilation fan
speed, and select the ventilation mode.
· If two remote controllers are used, the latter operation overrides the
former and their indications always reflect the result of the latter
operation.
- Remote controllers other than RBC-AW(M)SU5* are not compatible with heat recovery ventilation systems. (Some functions cannot be available.)
B Heat recovery ventilation unit system (Multiple Heat recovery ventilation units are used.)
Heat recovery ventilation unit
AB
Heat recovery ventilation unit
AB
AB
AB
RBC-AW(M)SU5*
· Using the remote controller for the Heat recovery ventilation unit RBC-
AW(M)SU5*, the unit can be started or stopped, control the ventilation fan
speed, and select the ventilation mode.
· If two remote controllers are used, the latter operation overrides the
former and their indications always reflect the result of the latter operation
and the settings of the header unit.
- Remote controllers other than RBC-AW(M)SU5* are not compatible with heat recovery ventilation systems. (Some functions cannot be available.)
C Heat recovery ventilation unit system linked with Air conditioners
Outdoor unit U1 U2 U1 U2
Air conditioner
AB
U1 U2 Air conditioner
AB
Heat recovery Heat recovery
ventilation
ventilation
unit
unit
AB
AB
AB
AB
· The wired remote controller RBC-AW(M)SU5* can be used the ON/OFF of the Heat recovery ventilation unit and the ventilation fan speed and select ventilation mode.
- Remote controllers other than RBC-AW(M)SU5 are not compatible with heat recovery ventilation systems. (Some functions can not be available.)
· The wired remote controller RBC-AW(M)SU5 can be used to ON/OFF the Heat recovery ventilation unit separately from Air conditioner. - Setting modifications are required for separate control. Refer to “9. Advanced control”.
· If two remote controllers are used, the latter operation overrides the former and their indications always reflect the result of the latter operation. In addition, the indications of the Heat recovery ventilation unit always reflect the setting of the unit with the smallest indoor unit address number.
RBC-AW(M)SU5*
RBC-AW(M)SU5*
· In the case of Heat recovery ventilation unit system linked Air conditioner
(C, F system), the type of ventilation fan speed that you can select from the
remote controllers are less than Heat recovery ventilation unit ONLY sysytem
(A, B, D system).
29-EN
30-EN
System example D Central control system (When controlling the Heat recovery
ventilation unit only)
Central controller BMS-CT2560U*
U3 U4
U3 U4
Heat recovery Heat recovery
ventilation
ventilation
unit
unit
AB
AB
AB
AB
U3 U4
Heat recovery Heat recovery
ventilation
ventilation
unit
unit
AB
AB
AB
AB
RBC-AW(M)SU5*
RBC-AW(M)SU5*
E Central control system
(When controlling the air conditioner and the Heat recovery ventilation unit
separately)
Outdoor unit
U1 U2 U3 U4
Central controller BMS-CT2560U*
U3 U4
U1 U2
Air conditioner
Air conditioner
AB
AB
AB
AB
U3 U4
Heat recovery Heat recovery
ventilation
ventilation
unit
unit
AB
AB
AB
AB
RBC-ASCU, RBC-AMTU3 and RBC-AW(M)SU5*
RBC-AW(M)SU5*
Operation
· The central controller can be used to ON/OFF the whole system and separately
ON/OFF groups of the Heat recovery ventilation units.
· The functions that can control Heat recovery ventilation from central
controller may differ depend on the of central controller.
· If the central controller and the remote controller for the Heat recovery
ventilation unit are used, the latter operation overrides the former.
· The RBC-AW(M)SU5 can be used to control the ventilation fan speed and
ventilation mode of the Heat recovery ventilation unit. The remote
controllers for the Air conditioners (RBC-ASCU1 and RBC-AMTU3) cannot be
used to control the group of the Heat recovery ventilation units. Remote
controllers other than RBC-AW(M)SU5 are not compatible with heat recovery
ventilation systems. (Some functions can not be available.)
· The central controller can be used to ON/OFF the whole system and separately
ON/OFF groups of Air conditioners and the Heat recovery ventilation units.
(Air conditioners and Heat recovery ventilation units are not linked in this
system.)
· The functions that can control Heat recovery ventilation from central
controller may differ depend on the of central controller.
If three control devices are used; · About the central controller and the
remote controllers for
Air conditioner or the central controller and the remote controllers for Heat
recovery ventilation units, the latter operation overrides the former and
their indications always reflect the result of the latter operation. · About
the remote controllers for Air conditioner and Heat recovery ventilation units
are not affected by each other’s operations. Remote controllers other than
RBC-AW(M)SU5 are not
compatible with heat recovery ventilation systems. (Some functions can not be
available.)
· In the case of Heat recovery ventilation unit system linked Air conditioner
(C, F system), the type of ventilation fan speed that you can select from the
remote controllers are less than Heat recovery ventilation unit ONLY sysytem
(A, B, D system).
System example
Operation
F Central control system
· The central controller can be used to ON/OFF the whole
(When controlling the air conditioner and Heat recovery ventilation unit together)
Outdoor unit
Central controller BMS-CT2560U*
system. It can also be used to ON/OFF the Heat recovery ventilation unit
separately (*).
· The central controller cannot be used to control the ventilation fan speed
or ventilation mode of the Heat recovery ventilation unit.
U1 U2 U3 U4
U3 U4
- Central controller cannot recognize Heat recovery ventilation. (Heat recovery ventilation does not appear in central controller.)
U1 U2
U1 U2
· If multiple control devices are used; the central controller
Air conditioner
Air conditioner
Heat recovery Heat recovery
ventilation
ventilation
unit
unit
and the remote controllers, the latter operation overrides the former
regardless of which device is used.
· The remote controller for the Heat recovery ventilation unit
AB
AB
RBC-AW(M)SU5* and the remote controller for the Air
AB
AB
conditioners RBC-AMS5E can be used to control the
ventilation fan speed and ventilation mode of the Heat
AB
AB
recovery ventilation unit.
- Remote controllers other than RBC-AW(M)SU5* are not compatible with heat recovery ventilation systems. (Some functions can not be available.)
RBC-AMS5E
RBC-AW(M)SU5 · If the RBC-ASCU1 and RBC-AMTU3 is used; the
ventilation fan speed or ventilation mode of the Heat
recovery ventilation unit cannot be controlled.
· The remote controllers other than RBC-ASCU1* can be
used to ON/OFF the Heat recovery ventilation unit
separately.
- Setting modifications are required for separate control. Refer to “9. Advanced control”
· In the case of Heat recovery ventilation unit system linked Air conditioner (C, F system), the type of ventilation fan speed that you can select from the remote controllers are less than Heat recovery ventilation unit ONLY sysytem (A, B, D system).
31-EN
16
32-EN
17
Heat recovery ventilation unit system
Heat recovery ventilation unit system linked with Air conditioners
Central control system
System example
A
B
C
D
E
F
Central control
None
Only Heat recovery
When controlling the air conditioner and the Heat When controlling the air conditioner and Heat
ventilation unit is used. recovery ventilation unit separately
recovery ventilation unit together
No. of Heat recovery ventilation units
1
Multiple
1
Multiple
Multiple
1
Multiple
1
Multiple
Operation together with the Air conditioners
No
Yes
No
Yes
Remote controller inter-unit wiring
Not necessary
Necessary
Necessary
Not necessary
Necessary
Central control wiring
Not necessary
Necessary (Header unit only)
Not necessary
1. Line (system) address
Fixed * The line (system) address is fixed as 31 for the Heat recovery ventilation unit.
2. Changing the indoor unit address
No.2 of SW701
No.1 to 4 of SW702
No.1 and 2 of SW703
(Or if you need to set using remote controller, change DN code [13]. Factory
default: 0001)
Not necessary
Necessary (Do not duplication) SW701 to SW703 (Or DN code [13])
Not necessary
Necessary (Do not duplication) SW701 to SW703 (Or DN code [13])
Necessary (Do not duplication) SW701 to SW703 (Or DN code [13])
Not necessary
Necessary (Do not duplication) SW701 to SW703 (Or DN code [13])
Not necessary
Necessary (Do not duplication) SW701 to SW703 (Or DN code [13])
Circuit board of the Heat recovery ventilation unit
3. Changing the group address
No.4 of SW703
(Or if you need to set using remote controller, change DN code [14]. Factory
default: 00Un)
Necessary No.4 of SW703: ON (Or DN code [14]: 0001)
Necessary
Header
No.4 of SW703: ON
(Or DN code [14]: 0001)
Follower
No.4 of SW703: OFF
(Or DN code [14]: 0002)
- Settings of the header unit reflect the indications of the remote controller.
Not necessary
- Check that all Heat recovery ventilation units are “Follower”.
No.4 of SW703: OFF
(Or DN code [14]: 0002) - Settings of the follower unit with the smallest indoor unit address number reflect the indication of the remote controller.
Necessary
Header
No.4 of SW703: ON
(Or DN code [14]: 0001)
Follower
No.4 of SW703: OFF
(Or DN code [14]: 0002)
- Settings of the header unit reflect the indications of the remote controller.
Necessary Header No.4 of SW703: ON (Or DN code [14]: 0001)
Necessary
Header
No.4 of SW703: ON
(Or DN code [14]: 0001)
Follower
No.4 of SW703: OFF
(Or DN code [14]: 0002)
- Settings of the header unit reflect the indications of the remote controller.
Not necessary
- Check that all Heat recovery ventilation units are “Follower”.
No.4 of SW703: OFF
(Or DN code [14]: 0002) - Settings of the follower unit with the smallest indoor unit address number reflect the indication of the remote controller.
4. Fix / Automatic changeover of the central control address
No.3 of SW703
(Or if you need to set using remote controller, change DN code [03]. Factory
default: 00Un)
Not necessary No.3 of SW703: OFF (Or DN code [03]: 00Un)
- SW703 ON (Fix): Central control address equals indoor unit address. OFF (Auto): Central control address equals DN code [03].
Not necessary No.3 of SW703: OFF (Or DN code [03]: 00Un)
- SW703 ON (Fix): Central control address equals indoor unit address. OFF (Auto): Central control address equals DN code [03].
- Refer to the Installation Manual of the central control device.
5. Changing the terminator Not necessary
No.1 of SW301
No.1 of SW301: OFF
Necessary
Not necessary
No.1 of SW301: ON
No.1 of SW301: OFF
(100 )
- Set 1 header unit only. * Adjust settings on the air conditioner.
Checking before turning on the power
Complete the settings of the Heat recovery ventilation unit and wiring.
· Complete the settings of the Heat recovery ventilation unit and wiring.
· Refer to the Installation Manual of the air conditioner for the settings and
wiring.
Complete the settings of · Complete the settings of the Heat recovery ventilation unit and wiring.
the Heat recovery
· Refer to the Installation Manual of the air conditioner for the settings and wiring.
ventilation unit and
wiring.
Turning on the power
Turn on the breaker of all the Heat recovery ventilation units.
Turn on the Heat recovery ventilation unit first. Refer to the Installation Manual of the air conditioner for its power supply.
Turn on the breaker of all the Heat recovery ventilation units.
Turn on the Heat recovery ventilation unit first. Refer to the Installation Manual of the air conditioner for its power supply.
Central control address setting
Not necessary
Refer to the Installation Manual of the central control device.
33-EN
34-EN
Changing the group address, indoor unit address, and central control address
About the switches on the circuit board of the Heat recovery ventilation unit
SW701 ON ON
SW702 ON
SW703 ON
OFF 1234 1234 1234
Changing the indoor unit address : ON -: OFF When there are multiple Heat recovery ventilation units, do not duplicate the value No.2 of SW701 and between No.1 to No.4 of SW702 and between No.1 and No.2 of SW703. (Factory default: 1)
Changing the group address Header (Individual): ON Follower: OFF · When the
system equipped with the Heat recovery
ventilation unit(s) only is used, set only one unit as the header unit. · When
the system equipped with the Heat recovery ventilation unit and air
conditioners is used, be sure to set all the Heat recovery ventilation units
as follower units. (Factory default: Follower)
Changing the central control address Fixed: ON Auto: OFF The settings do not
need to be adjusted. (Leave the value OFF.)
Indoor unit address switch (: ON –: OFF) Address switch number Address switch number
Address switch number
Address switch number
Address SW701 SW702 SW703 Address SW701 SW702 SW703 Address SW701 SW702 SW703 Address SW701 SW702 SW703
2123412
2123412
2123412
2123412
1 — — — — — — — 17 — — — — — — 33 — — — — — — 49 — — — — —
2 — — — — — — 18 — — — — — 34 — — — — — 50 — — — —
3 — — — — — — 19 — — — — — 35 — — — — — 51 — — — —
4 — — — — — 20 — — — — 36 — — — — 52 — — —
5 — — — — — — 21 — — — — — 37 — — — — — 53 — — — —
6 — — — — — 22 — — — — 38 — — — — 54 — — —
7 — — — — — 23 — — — — 39 — — — — 55 — — —
8 — — — — 24 — — — 40 — — — 56 — —
9 — — — — — — 25 — — — — — 41 — — — — — 57 — — — —
10 — — — — — 26 — — — — 42 — — — — 58 — — —
11 — — — — — 27 — — — — 43 — — — — 59 — — —
12 — — — — 28 — — — 44 — — — 60 — —
13 — — — — — 29 — — — — 45 — — — — 61 — — —
14 — — — — 30 — — — 46 — — — 62 — —
15 — — — — 31 — — — 47 — — — 63 — —
16 — — — 32 — — 48 — — 64 —
I
Address switch number
Address switch number
Address switch number
Address switch number
Address SW701 SW702 SW703 Address SW701 SW702 SW703 Address SW701 SW702 SW703 Address SW701 SW702 SW703
2123412
2123412
2123412
2123412
65 — — — — — — 81 — — — — — 97 — — — — — 113 — — — —
66 — — — — — 82 — — — — 98 — — — — 114 — — —
67 — — — — — 83 — — — — 99 — — — — 115 — — —
68 — — — — 84 — — — 100 — — — 116 — —
69 — — — — — 85 — — — — 101 — — — — 117 — — —
70 — — — — 86 — — — 102 — — — 118 — —
71 — — — — 87 — — — 103 — — — 119 — —
72 — — — 88 — — 104 — — 120 —
73 — — — — — 89 — — — — 105 — — — — 121 — — —
74 — — — — 90 — — — 106 — — — 122 — —
75 — — — — 91 — — — 107 — — — 123 — —
76 — — — 92 — — 108 — — 124 —
77 — — — — 93 — — — 109 — — — 125 — —
78 — — — 94 — — 110 — — 126 —
79 — — — 95 — — 111 — — 127 —
80 — — 96 — 112 — 128
35-EN
18
36-EN
19
Manual Indoor unit address setting using the remote controller
(If you need to set using remote controller.) Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and outdoor wiring has not been started (manual setting using the remote controller)
Wiring example of 2 refrigerant lines
Refrigerant line 1
Refrigerant line 2
Outdoor unit
Indoor unit 1 Indoor unit 2 HRV unit
Indoor unit 3 Indoor unit 4
Remote controller
Heat recovery ventilation unit can not be set the address even if the automatic address is set from outdoor unit in the system of Refrigerant line
- Perform the address setting individually using remote controller. (Indoor
unit 1,2 or 3,4 can be set the automatic address by the outdoor unit.)
In the example above, disconnect the remote controller connections between the indoor units and connect a wired remote controller to the target unit directly before address setting.
Field setting menu
Pair the Heat recovery ventilation unit to set and the remote controller one-
to-one. Turn on the power.
1 Push [ Menu] to open the “Menu”
2 Push and hold [ Menu] and [
open “Field setting menu”
Push and hold 4 seconds.
] at the same time to
DN setting
Detailed data of various models of air conditioner and Heat recovery
ventilation unit can be set.
REQUIREMENT
Be sure to stop operation of the air conditioners and Heat recovery
ventilation units.
1 In the “Field setting menu” screen, push [ ] and
[ ] to select “DN setting”, and then push [ Set/Fix] 2 Push [ ] and [ ] to
select “Indoor unit” and the
push [ Set/Fix] If “Indoor unit” was selected, the fans and louvres of the
indoor units operate.
When doing group connections: The fans and louvres of the selected indoor
units operate.
3 Push [ ] to black highlight the code (DN), and then
push [ ] and [ ] to set the code
4 Push [ ] to black highlight the data, and then push
[ ] and [ ] to set the data
5 After finishing setting the data of the code (DN), push
[ Set/Fix] “Continue?” is displayed.
6 To set the data of other codes (DN), push [ Set/Fix] To not do other
settings, push [ Return] The changes are fixed, and the “Field setting menu”
screen returns. ” ” appears while data is changing.
When doing group connections: Push [ Return] to open the unit selection
screen. In the unit
selection screen, push [ Return] to briefly display ” “, and then return to
the “Field setting menu” screen.
3 Push [ ] and [ ] to select an item
4 Push [ Set/Fix] The setting screen opens.
37-EN
38-EN
Confirming the indoor unit addresses and the position of an indoor unit using
the remote controller
Checking and setting addreses
Show the line address, indoor address, and group address of indoor units on
the remote controller, operate the fan of relevant indoor units to check the
relationship of the addresses and the indoor units, and if needed manually
change the addresses.
1 Select “Indoor unit address” from
“Address” in the “Field setting menu”, and push [ Set/Fix] At first, the fans
and louvres of all indoor units in the group operate.
Group address Indoor address Line address
The address is indicated as “-“.
2 Push [ Menu]
Each push of [ Menu] displays in order: Entire
31
group Header unit Follower unit 1 … The fans and louvres of the relevant indoor units
operate.
3 If you need to change the address manually
from the remote control, push [ Set/Fix]
31
The screen for settings appears.
- The priority of the DIP switch and the remote
31
controller setting is the latter.
4 Push [ ] and [ ] to move the black
highlight, and then push [ ] and [ ] to
set the address
5 After manually setting the addresses of all
indoor units, push [ Set/Fix] The message “Address confirm?” appears on
screen.
6 Push [ Set/Fix] The changes are fixed. ” ” appears while data is changing.
Header/Follower (Settings required to use 2 remote controllers to do
operations)
When using 2 remote controllers, you need to set “Header remote controller”
and “Follower remote controller”.
1 In the “Initial setting” screen, push [ ] and [ ] to
select “Header/Follower”, and then push [ Set/Fix] 2 Push [ ] and [ ] to
select “Header remote
controller” or “Follower remote controller”
3 Push [ Set/Fix] When ” ” appears, return to the “Initial setting” screen.
Settings for each system configuration
NOTE The line (system) address is fixed as 31 for the Heat recovery
ventilation unit.
A Heat recovery ventilation unit system (One Heat recovery ventilation unit is used.)
Heat recovery ventilation unit
Earth
LN
Uh Uh (U3) (U4)
A
B
Power supply
AB
Remote controller (header)
AB
Remote controller (follower)
Changing the group address (SW703 or DN code [14]) The setting for group
address change are necessary. Set the No.4 of SW703: ON. Or No.4 of SW703: OFF
and DN code [14]: 0000 or 0001 to set the remote controller as the header.
(Factory default setting SW703 No.4: OFF and DN code [14]: 00Un) * When
“Header: ON” is selected, “Individual: ON”
will be selected in this system. (In short, this case “Header” = “Individual”)
Changing the indoor unit address (DN code [13]) The setting does not need to
be adjusted. (Factory default: 0001)
39-EN
20
40-EN
21
B Heat recovery ventilation unit system (Multiple Heat recovery ventilation units are used.)
Heat recovery ventilation unit
Heat recovery ventilation unit
Heat recovery ventilation unit
Earth
Earth
Earth
LN
Uh Uh (U3) (U4)
A
B
LN
Uh Uh (U3) (U4)
A
B
LN
Uh Uh (U3) (U4)
A
B
Power supply
Power supply
Power supply
Remote controller (header)
AB
Remote controller inter-unit wiring
Remote controller (follower)
AB
- For group control, install remote controller inter-unit wiring between the units.
- TCC-Link: Up to 8 units can be installed for group control. TU2C-Link: Up to 16 units can be installed for group control.
Changing the group address (SW703 or DN code [14]) The setting for group
address change are necessary. 1. In multiple Heat recovery ventilation units,
set the No.4 of SW703: ON, or set No.4 of SW703: OFF and DN code
[14]: 0001 to the only one unit to the header. Settings of the header unit
reflect to the indications of the remote controller. 2. For other units, do
not change the No.4 of SW703 or DN code [14]. If you need to reset to the
follower, set the
No.4 of SW703: OFF and DN code [14]: 00Un or 0002. (Factory default
(Follower): No.4 of SW703: OFF and DN code [14]: 00Un)
Changing the indoor unit address (SW701, SW702, 703 or DN code [13]) Settings
for changing the indoor unit address are necessary. · Do not duplicate the
value. (SW701, SW702 and SW703: 1 to 128, or DN code [13]: 1 to 128) The
header unit does not need to be selected as “1”. (Factory default: 1) * The
priority of DIP SW and DN code is the latter.
C Heat recovery ventilation unit system linked with Air conditioners
Power supply
Outdoor unit
L1 L2 L3 N
U1 U2 U3 U4 U5 U6
Control wiring between indoor and outdoor units Control wiring between indoor
units
Indoor unit
Indoor unit
Heat recovery ventilation unit
LN
Uv Uv (U1)(U2)
A
B
LN
Uv Uv (U1)(U2)
A
B
LN
Uh Uh (U3)(U4)
A
B
Power supply
Power supply
Power supply
Heat recovery ventilation unit
LN
Uh Uh (U3)(U4)
A
B
Power supply
Remote controller (header)
AB
Remote controller inter-unit wiring
- For group control with Air conditioners, install inter-unit wiring between the units.
- TCC-Link: Up to 8 units can be installed for group control. TU2C-Link: Up to 16 units can be installed for group control.
Remote controller
(follower)
AB
Changing the group address (SW703 or DN code [14]) The settings of the group
address does not need to be adjusted. Leave the value “Follower”. No.4 of
SW703: OFF and DN code [14]: 00Un or 0002 (Factory default (Follower): No.4 of
SW703: OFF and DN code [14]: 00Un) Settings of the follower unit with the
smallest indoor unit address number reflect to the indication of the remote
controller.
Changing the indoor unit address (SW701, SW702 and SW703 or DN code [13])
Settings for changing the indoor unit address are necessary. · Do not
duplicate the value. (SW701, SW702 and SW703: 1 to 128, or DN code [13]: 1 to
128) The header unit does not need to be selected as “1”. (Factory default:
-
- The priority of DIP SW and DN code is the latter.
41-EN
42-EN
D Central control system (When controlling the Heat recovery ventilation unit only) For the settings of the central control address, refer to the Installation Manual of the central control device.
Power supply
Central controller
LN Uh Uh (U3)(U4)
Central control wiring
Heat recovery ventilation unit
Heat recovery ventilation unit
Heat recovery ventilation unit
LN
Uh Uh (U3)(U4)
A
B
Power supply
LN
Uh Uh (U3)(U4)
A
B
Power supply
LN
Uh Uh (U3)(U4)
A
B
Power supply
Heat recovery ventilation unit
LN
Uh Uh (U3)(U4)
A
B
Power supply
Remote controller
(header)
AB
Remote controller
Remote controller
(follower)
A B (header)
AB
Remote controller (follower)
Remote controller inter-unit wiring
Remote controller inter-unit wiring
- Central control wiring must be connected to the header Heat recovery ventilation unit only.
- For group control, install inter-unit wiring between the units.
- TCC-Link: Up to 8 units can be installed for group control. TU2C-Link: Up to 16 units can be installed for group control.
AB
Changing the group address (SW703 or DN code [14]) The setting for group
address change are necessary. 1. In multiple Heat recovery ventilation units,
set the No.4 of SW703: ON, or set No.4 of SW703: OFF and DN code
[14]: 0001 to the only one unit to the header. Setting needs to units which
is connected central control wiring of each group. Settings of the header
unit reflect to the indications of the remote controller. 2. For other units,
do not change the No.4 of SW703 or DN code [14]. If you need to reset to the
follower, set the
No.4 of SW703: OFF and DN code [14]: 00Un or 0002. (Factory default
(Follower): No.4 of SW703: OFF and DN code [14]: 00Un)
Changing the indoor unit address (SW701, SW702 and SW703 or DN code [13]) Settings for changing the indoor unit address are necessary. Do not duplicate the value. (SW701, SW702 and SW703: 1 to 128, or DN code [13]: 1 to 128) The priority of DIP SW and DN code is the latter.
Changing the terminator (No.1 of SW301)
Settings for changing the terminator are necessary. Select “ON” for one of the
header unit. (Factory default: OFF)
100 : ON (1 header unit only) None: OFF (the other units)
SW301 ON
ON
OFF 12
Changing the terminator 100 : ON None: OFF (Factory default: OFF)
E Central control system (When controlling the air conditioner and the Heat
recovery ventilation unit separately)
For the settings of the central control address, refer to the Installation
Manual of the central control device.
Power supply
Outdoor unit
L1 L2 L3 N
Uv Uv Uh Uh Uc Uc (U1) (U2) (U3) (U4) (U5) (U6)
Central
control
wiring
Power supply
LN
Uh Uh (U3)(U4)
Central controller
Control wiring between indoor and outdoor units
Control wiring between indoor units
Central control wiring
Indoor unit
Indoor unit
Heat recovery ventilation unit
LN
Uv Uv (U1)(U2)
A
B
LN
Uv Uv (U1)(U2)
A
B
LN
Uh Uh (U3)(U4)
A
B
Heat recovery ventilation unit
LN
Uh Uh (U3)(U4)
A
B
Power supply
Power supply
Power supply
Power supply
Remote controller (header)
AB
Remote controller (follower)
AB
Remote controller (header)
AB
Remote controller (follower)
AB
Remote controller inter-unit wiring
Remote controller inter-unit wiring
- Central control wiring of the Heat recovery ventilation unit is necessary only for the header unit.
- For group control, install inter-unit wiring between the units.
- TCC-Link: Up to 8 units can be installed for group control. TU2C-Link: Up to 16 units can be installed for group control.
Changing the group address (SW703 or DN code [14]) The setting for group
address change are necessary. 1. In multiple Heat recovery ventilation units,
set the No.4 of SW703: ON, or set No.4 of SW703: OFF and DN code
[14]: 0001 to the only one unit to the header. Settings of the header unit
reflect to the indications of the remote controller. 2. For other units, do
not change the No.4 of SW703 or DN code [14]. If you need to reset to the
follower, set the
No.4 of SW703: OFF and DN code [14]: 00Un or 0002. (Factory default
(Follower): No.4 of SW703: OFF and DN code [14]: 00Un) Settings of the
header unit reflect to the indications of the remote controller. (Factory
default: Follower)
Changing the indoor unit address (SW701, SW702 and SW703 or DN code [13])
Settings for changing the indoor unit address are necessary. · Do not
duplicate the value. (SW701, SW702 and SW703: 1 to 128, or DN code [13]: 1 to
128) * The header unit does not need to be selected as “1”. (Factory default:
-
- The priority of DIP SW and DN code is the latter.
43-EN
22
44-EN
F Central control system (When controlling the air conditioner and Heat
recovery ventilation unit together)
· For the settings of the central control address, refer to the Installation
Manual of the central control device. · Do not perform the central control
wiring with the Heat recovery ventilation unit.
Power supply
Outdoor unit
L1 L2 L3 N
Uv Uv Uh Uh Uc Uc (U1) (U2) (U3) (U4) (U5) (U6)
Central control wiring
Power supply
Central controller
LN Uh Uh (U3)(U4)
Control wiring between indoor and outdoor units Control wiring between indoor units
Indoor unit
LN
Uv Uv (U1)(U2)
A
B
Indoor unit
LN
Uv Uv (U1)(U2)
A
B
Heat recovery ventilation unit
LN
Uh Uh (U3)(U4)
A
B
Heat recovery ventilation unit
LN
Uh Uh (U3)(U4)
A
B
Power supply
Power supply
Power supply
Power supply
Remote controller
(header)
AB
Remote controller inter-unit wiring
- For group control with Air conditioners, perform inter-unit wiring between the units.
- TCC-Link: Up to 8 units can be installed for group control. TU2C-Link: Up to 16 units can be installed for group control.
Remote controller (follower)
AB
Changing the group address (SW703 or DN code [14]) The settings of the group
address does not need to be adjusted. Leave the value “Follower”. No.4 of
SW703: OFF and DN code [14]: 00Un or 0002. (Factory default (Follower): No.4
of SW703: OFF and DN code [14]: 00Un) The settings of the follower unit with
the smallest indoor unit address number reflect to the indication of the
remote controller.
Changing the indoor unit address (SW701, SW702 and SW703 or DN code [13])
Settings for changing the indoor unit address are necessary. · Do not
duplicate the value. (SW701, SW702 and SW703: 1 to 128, or DN code [13]: 1 to
128) The header unit does not need to be selected as “1”. (Factory default:
-
- The priority of DIP SW and DN code is the latter.
23
8 Advanced system
WARNING
· Use wiring that meets the specifications in the Installation Manual and the
stipulations in the local regulations and laws. Use of wiring which does not
meet the specifications may give rise to electric shocks, electrical leakage,
smoking and/or a fire.
· When carrying out electric connection, use the wire specified in the
Installation Manual and connect and fix the wire securely to prevent them
applying external force to the terminals. Improper connection of fixing may
result in fire.
· Electrical wiring work shall be conducted according to law and regulation in
the community and Installation Manual. Failure to do so may result in
electrocution or short circuit.
REQUIREMENT
When external input / output function is used, connect the control adapter
sold separately. Connect it to Control P.C. board (MCC-1784). It does not
function even if connected to other P.C. board.
External input / output function List · Depending on the model, some DN codes
may not be displayed on the remote controller. Also, the number of
data that can be set may differ. · DN codes (functions) that are not displayed
on the remote controller cannot be set. · CN60 can be used in models with a
refrigeration cycle (excluding “fan output”). · The color of the connector or
lead wire may change due to material procurement, but the function is the
same. This lead wire color is the original color of the optional adapter. It
doesn’t matter if you use local supply lead wires. When using CN60, 61, 70,
73, 80, 610, remove the power terminal block mounting plate and insert it.
WHT: White, YEL: Yellow, RED: Red, GRN: Green, ORN: Orange, BRN: Brown, BLK: Black, BLU: Blue
No.
Connector No.
Color (Con-
nector)
PIN No.
Color* (Lead
wire)
DN Code Data
Function
Note
Adapter (sold separately)
1
RED
–
– DC12 V (COM) Common for Pin.2 to 6
2
BLU
–
– Defrost output
ON signal when outdoor unit is in defrosting
CN60
3 ORN
–
1
(Operation status signal
WHT
output)
4
YEL
–
–
Thermostat ON ON signal when indoor unit is
output
“thermostat-ON”
–
Cooling output
ON when operation mode is cooling
TCBKBCN60OPE
5
BRN
–
–
Heating output
ON when operation mode is heating
6
BLK
–
– Fan output
ON when indoor unit fan is ON
45-EN
46-EN
No.
Connector No.
Color (Con-
nector)
PIN No.
1
CN61
2
2
(Leaving-ON prevention
YEL
control)
3
4 5 6
CN70
1
3 (Option error WHT
input)
2
CN73
1
4 (Demand
RED
control input)
2
1
2
CN80 5 (Outside error GRN
input) 3
CN610
6 (Option output)
1 YEL 2
3
Color* (Lead wire)
BLU
WHT
ORN
YEL RED BRN
BLU
WHT
BLU
WHT RED
BLU RED
BLU
DN Code Data
Function
Note
Adapter (sold separately)
External ON/OFF control
(Factory default)
0000 ON/OFF input
- You can change pulse (ON) / static (OFF) for No.1 of SW701.
(Setting is common to CN61,
72E
CN705 and CN706)
0001 Fire alarm input Normal OPEN (Albeit contact)
0002 Notice code input Display code 201
0003
Ventilation fan speed input
Low speed
–
– 0 V (COM)
Common for Pin.1, 3
Input signal makes switching of TCB-
permission (OFF) /
KBCN61HAE
prohibition (ON)
Prohibition of
of individual remote controller
–
– remote controller operation (During prohibition,
operation input “Central controlling mark” is shown on the LCD.)
- Common circuit with Pin.2 of
CN705
–
–
Operation output
On signal during “remote controller ON”
–
– DC12 V (COM) Common for Pin. 4, 6
–
– Alarm output
On signal during alarm output (non recovery fatal error)
0000
Filter display input
When signal is input, filter sign symbol is displayed on RC
2A
0001
External error input
When signal is input, error symbol
is displayed on RC
TCB-
(Indoor unit does not stop)
KBCN70OAE
0002 Humidifier input Factory default
–
– 0 V (COM)
–
0003 Fire alarm input
Normal OPEN (Albeit contact) (Factory default)
0005 Fire alarm input Normal CLOSE (Break contact)
0B 0006 Notice code input Display code 202
TCBKBCN73DEE
0010
Humidifier ON/ OFF input
–
–
– 0 V (COM)
–
–
– DC12 V (COM) –
–
—
–
After the signal input is as follows: 1) 3 sec. Thermo-off forcedly
TCBKBCN80EXE
–
–
Outside error input
- 1 min. Generates Error code “L30” (Interlock from
outside) to stop the operation
forcedly
–
–
ON when outside temperature is
–
–
Cold air detection very low
output
(For detail, refer to the Service
TCBKBCN610V-E
–
–
Manual)
No.
Connector No.
CN704
7 (External output)
CN705 8 (External
input)
CN706 9 (External
input)
Color (Con-
nector)
PIN No.
1
2 WHT
3 4 5 1
2
3 RED
4
5
1
WHT (Natural)
2
Color* (Lead wire) WHT
YEL
RED ORN BRN GRN YEL
RED WHT
BLK
BLU
ORN
DN Code Data
Function
Note
Adapter (sold separately)
–
– DC12 V (COM) Common for Pin.2
–
–
ON output (Supply fan)
ON when operation is ON
0000
ON during normal operation (Factory default)
0001 ED
0002
0003
ON during normal operation, 24-hour ventilation or nighttime heat purge
operation
ON during 24-hour ventilation or nighttime heat purge operation
ON when SA fan is ON
TCBKBCN704V-E
0004
ON when EA fan is ON
–
– DC12 V (COM) Common for Pin.4 to 5
–
–
External damper output
ON during normal operation, 24-hour ventilation or nighttime heat purge operation
0000 Alarm output
EE
0001
Bypass mode output
ON during an error (Factory default)
ON when operation is bypass mode
–
– DC12 V (COM) Common for Pin. 2, 5
Input signal makes switching of
permission / prohibition of
–
–
Prohibition of remote controller
operation input
individual remote controller operation (During prohibition, “Central controlling mark” is shown on the LCD.)
- Common circuit with Pin.3 of
CN61
Select fan speed:
High (open) / Medium (close)
–
–
Ventilation fan speed input
speed * If Pin.1 of CN61 setting is 0003,
the priority is CN61
(Fan speed operates on Low) TCB-
–
–
Ventilation mode input
Select ventilation mode:
Bypass mode (close) / Heat exchange mode (open)
KBCN705V-E
External ON/OFF control
ON (close) / OFF (open)
- Common circuit with Pin.1 of
–
–
ON/OFF input * Non-voltage
CN706 * You can change pulse (ON) /
static (OFF) for No.1 of SW701
(Setting is common to
CN61, CN705 and CN706)
0000 ON/OFF linked Factory default
4E 0001 ON linked
–
0002 OFF linked
–
ON/OFF input External ON/OFF control
–
– With DC12 or Common circuit with Pin.5 of
DC24 voltage
CN705
- You can change pulse (ON) /
–
– 0 V (COM)
static (OFF) for No.1 of SW701 (Setting is common to CN61, TCB-
CN705 and CN706)
KBCN706V-E
0000 ON/OFF linked Factory default
4E 0001 ON linked
–
0002 OFF linked
–
The connecting method refer to follow.
47-EN
24
48-EN
How to connect the control adapter
1 CN60: Operation status signal output
(On P.C. board MCC-1784)
Diagram of local supply parts
Local supply
(To CN60)
Terminal
Relay
No.
Diagram of connector
COM (DC12 V) 1 Defrost output 2
(From local supply parts)
3
1
4
5
6
COM (DC12 V) 1
2
(From local supply parts)
2
Thermo ON output 3
4
5
6
COM (DC12 V) 1
2
(From local supply parts)
3
3
Cooling output 4
5
6
COM (DC12 V) 1
2
(From local supply parts)
4
3
4
Heating output 5
6
25
Note Locally procure relays and other devices suitable for DC12 V output. *
Use an adapter (sold
separately) to connect to the connector.
Note ON signal when outdoor unit is in defrosting. (When receiving defrost
signal from outdoor unit.)
ON signal when indoor unit is “Thermostat-ON”.
ON when operation mode is cooling.
ON when operation mode is heating.
COM (DC12 V) 1
2
(From local supply parts)
3
5
4
5
Fan output 6
2 CN61: Leaving-ON prevention control
(On P.C. board MCC-1784)
Diagram of local supply parts Local supply
(To CN61)
Terminal
Relay
Power supply
No.
Diagram of connector
ON/OFF input 1 COM (0 V) 2
(From local supply parts)
3
1
4
5
6
COM (0 V) 1
2
(From local supply parts)
2
Prohibition of remote 3
controller operation 4
input 5
6
(Description of CN61 continues on next page)
ON when indoor unit fan is ON.
Note Locally procure relays and other devices suitable for shorting connector
pins. Use an adapter (sold
separately) to connect to the connector.
Note External ON/OFF control (Factory default). It is necessary to set the
DN
code when using the other input function.
Input signal makes switching of permission / prohibition of individual remote
controller operation.
49-EN
50-EN
(Continued description of CN61 from the previous page) Diagram of local supply
parts
Local supply
(To CN61)
Terminal
Relay
Note
Locally procure relays and other devices suitable for DC12 V output. * Use an
adapter (sold
separately) to connect to the connector.
No.
Diagram of connector
1
2
3
3
ON output 4
(From local supply parts)
COM (DC12 V) 5
6
1
2
3
4
4
COM (DC12 V) 5 Alarm output 6
(From local supply parts)
Note On signal during “remote controller ON”.
On signal during alarm output (non recovery fatal trouble).
[Additional note for No.1] · This input can use for linking to “ON/OFF” from external device or remotely controlled. · For Heat recovery ventilation unit linked with air conditioner system, if a command is sent to one of the units in the group, all units operate together. · When a remote controller is used with the Heat recovery ventilation unit: The latter operation of the remote controller or the switch of the external device overrides the former. · When no remote controller is used with the Heat recovery ventilation unit: The operation of the Heat recovery ventilation unit is confined to that together with the external device. · Operation together with a pulse transmission device such as a building management system: Select “ON (Pulse)” for No.1 of SW701 (changeover switch for pulse/static). * Factory default: Static
SW701 ON ON
OFF 12
Changing the pulse / static Pulse: ON Static: OFF Select “ON” for No.1 of SW701 (Factory default: Static)
SW701 ON
Pulse input
Action
Pulse interval 200 msec or more
ON
OFF
[Additional note for No.2] · This input can use for switching the remote
controller between permission/prohibition. · During prohibition, “Central
controlling mark” is shown on the LCD. · If a command is sent to one of the
group, the permission/prohibition setting of the remote controller in the
group can be switched.
[Additional note for No.3] · This output is linked with the “remote controller
ON” state. (Not fan ON)
[Additional note for No.4] · This output can use for monitoring an abnormal
signal. * It is possible to monitor an abnormal signal from the Heat recovery
ventilation unit.
3 CN70: Option trouble input
(On P.C. board MCC-1784)
Diagram of local supply parts Local supply
(To CN70)
Terminal
Relay
Note
Locally procure relays and other devices suitable for shorting connector pins.
- Use an adapter (sold separately) to connect to the connector.
Power supply
No.
Diagram of connector
1
Trouble input 1 COM (0 V) 2
(From local supply parts)
Note
ON signal when trouble occurs. (Factory default: No function) * It is
necessary to set the DN
code when using this function.
OFF
Static input
Pulse width 200 to 300 msec
ON
OFF
51-EN
26
52-EN
4 CN73: Demand control input
(On P.C. board MCC-1784)
Diagram of local supply parts Local supply
(To CN73)
Terminal
Relay
Power supply
No.
Diagram of connector
1
Alarm input 1 COM (0 V) 2
(From local supply parts)
5 CN80: Outside trouble input
(On P.C. board MCC-1784)
Diagram of local supply parts Local supply
(To CN80)
Terminal
Relay
Power supply
No.
Diagram of connector
COM (12 V) 1
1
2
(From local supply parts)
Outside error input 3
Note
Locally procure relays and other devices suitable for shorting connector pins.
- Use an adapter (sold separately) to connect to the connector.
27
6 CN610: Cold air detection output
(On P.C. board MCC-1784) Diagram of local supply parts
Local supply
(To CN610)
Terminal
Relay
Note
Locally procure relays and other devices suitable for DC12 V output.
- Use an adapter (sold separately) to connect to the connector.
Note
Normal OPEN (Factory default) * It is necessary to set the DN
code when using the other function.
No.
Diagram of connector
1
COM (12 V) 1
(From local supply parts)
2
Outside error output 3
Note
ON when outside temperature is very low.
Note
Locally procure relays and other devices suitable for shorting connector pins.
- Use an adapter (sold separately) to connect to the connector.
[Additional note for No.1] · A signal will be output when low outside air temperature is detected in linking with Heat recovery ventilation unit operation (ON/OFF). * For its control contents or setting detail, refer to the Service Manual.
Note
After the signal input is as follows: 1) 3 sec.
Thermostat-off forcedly 2) 1 min.
Generates trouble code “L30” (Interlock from outside)
53-EN
54-EN
7 CN704: External output
(On P.C. board MCC-1784) Diagram of local supply parts
Local supply
(To CN704)
Terminal
Relay
No.
Diagram of connector
COM (DC12 V) 1 ON output 2
(From local supply parts)
1
3
4
5
1
2
2
COM (DC12 V) 3
External damper output 4
5
(From local supply parts)
1
(From local supply parts)
2
3
COM (DC12 V) 3
4
Alarm output 5
Note Locally procure relays and other devices suitable for DC12 V output.
Use an adapter (sold
separately) to connect to the connector.
Note ON when operation is ON. It is necessary to set the DN
code when changing the output ON signal.
ON during normal operation, 24hour ventilation or night-time heat purge
operation.
ON during an trouble (Factory default). * It is necessary to set the DN
code when using the other output function.
[Additional note for No.1] · This output can use for connecting an auxiliary
fan or monitoring operation. · This output is linked with the “fan ON” state.
(Not remote controller ON) · Contact is on during normal operation as factory
default. Contact is off during 24-hour ventilation mode, night-time heat
purge operation, delay mode or cold mode (temperature is below -10°C) as
factory default. The operation output settings can be changed the DN code.
[Additional note for No.2] · This output can use for connecting an electric
damper (electric shutter). · The electric damper (electric shutter) works
during normal operation, 24-hour ventilation mode, and nighttime hear purge
operation. · The electric damper (electric shutter) also works in the
following circumstances: While the operation is stopped intermittently in
24-hour ventilation mode While the operation is paused during nighttime heat
purge operation While operating in cold mode (Temperature is below -10°C) ·
The electric damper (electric shutter) does not works in the following
circumstances: While the operation is stopped Before the monitoring
operation of nighttime heat purge operation starts While in the delay mode
[Additional note for No.3] · This output can use for monitoring an abnormal
signal or the operation signal of bypass mode. * It is possible to monitor an
abnormal signal or the operation signal of bypass mode from the Heat recovery
ventilation unit. · Detection of an abnormal signal is possible, as factory
default.
55-EN
28
56-EN
8 CN705: External input
(On P.C. board MCC-1784)
Diagram of local supply parts Local supply
(To CN705)
Terminal
Relay
Power supply
No.
Diagram of connector
COM (DC12 V) 1 Prohibition of remote 2
(From local supply parts)
controller operation 3
1
input 4
5
COM (DC12 V) 1
2
Ventilation fan speed input 3 2
4
5
(From local supply parts)
COM (DC12 V) 1
2
3
3 Ventilation mode input 4
5
(From local supply parts)
COM (DC12 V) 1
2
3
(From local supply parts)
4
4
ON/OFF input 5
29
Note Locally procure relays and other devices suitable for shorting connector
pins. * Use an adapter (sold
separately) to connect to the connector.
Note Input signal makes switching of permission / prohibition of individual
remote controller operation.
Select fan speed: High (open) / Medium (close)
[Additional note for No.1] · This input can use for switching the remote
controller between permission/prohibition. · During prohibition, “Central
controlling mark” is shown on the LCD. · If a command is sent to one of the
group, the permission/prohibition setting of the remote controller in the
group can be switched.
[Additional note for No.2] · This input can use for switching between
High/Medium ventilation fan speed. · If a command is sent to one of the units
in the group, all the Heat recovery ventilation units in the group operate
together. · The latter operation of the remote controller or the external
device overrides the former.
[Additional note for No.3] · This input can use for switching between bypass
mode/heat exchange mode. · If a command is sent to one of the units in the
group, all the Heat recovery ventilation units in the group operate together.
· The latter operation of the remote controller or the external device
overrides the former.
[Additional note for No.4] · This input can use for linking to “ON/OFF” from
external device or remotely controlled. · When the output signal of the
external device is a no voltage a-contact. (static signal) · For Heat recovery
ventilation unit linked with air conditioner system, if a command is sent to
one of the units in the group, all units operate together. · When a remote
controller is used with the Heat recovery ventilation unit: The latter
operation of the remote controller or the switch of the external device
overrides the former. · When no remote controller is used with the Heat
recovery ventilation unit: The operation of the Heat recovery ventilation unit
is confined to that together with the external device. · Operation together
with a pulse transmission device such as a building management system: Select
“ON (Pulse)” for No.1 of SW701 (changeover switch for pulse/static). * Factory
default: Static
Select ventilation mode: Bypass mode (close) / Heat exchange mode (open)
External ON/OFF control (Factory default: ON/OFF linked).
- It is necessary to set the DN code when changing the type of ON/OFF link.
57-EN
58-EN
9 CN706: External input
(On P.C. board MCC-1784) Diagram of local supply parts
Local supply
(To CN706)
Terminal
DC12 V or DC24 V
No.
Diagram of connector
ON/OFF input 1
(From local supply parts)
1
COM (0 V) 2
Note Locally procure relays and other devices suitable for shorting connector
pins. Use an adapter (sold
separately) to connect to the connector.
Note External ON/OFF control (Factory default: ON/OFF linked). It is
necessary to set the DN
code when changing the type of ON/OFF link.
[Additional note for No.1] · This input can use for linking to “ON/OFF” from external device or remotely controlled. · When the output signal of the external device is DC12 V or DC24 V. (static signal) · For Heat recovery ventilation unit linked with air conditioner system, if a command is sent to one of the units in the group, all units operate together. · When a remote controller is used with the Heat recovery ventilation unit: The latter operation of the remote controller or the switch of the external device overrides the former. · When no remote controller is used with the Heat recovery ventilation unit: The operation of the Heat recovery ventilation unit is confined to that together with the external device. · Operation together with a pulse transmission device such as a building management system: Select “ON (Pulse)” for No.1 of SW701 (changeover switch for pulse/static). * Factory default: Static
9 Advanced control
REQUIREMENT
· When the unit is used for the first time, it takes a while for the remote
controller to recognize operation input after the power is turned on. This is
not a malfunction.
· For details on the auto address setting of Air conditioners when operating
together with a SMMS series air conditioner (adjust the auto address setting
on the circuit board of the outdoor interface), refer to the Installation
Manual of the SMMS series air conditioner.
· For details on the auto address setting of Air conditioners when operating
together with a DI·SDI series air conditioner (the action is performed when
the power is turned on), refer to the Installation Manual of the DI·SDI series
air conditioner.
· Turn on the Heat recovery ventilation unit first. Refer to the Installation
Manual of the air conditioner about its power supply.
· When shipped from the factory, all the settings are set to [Factory
default]. Change the settings of the Heat recovery ventilation unit if
necessary.
· Change settings using the main remote controller (wired remote controller).
- The settings cannot be changed using the wireless remote controller, the sub
remote controller, or a system
without a remote controller (system with only the central remote controller). Therefore, prepare the main remote controller and install it.
Changing the advanced control settings
Basic procedure for changing the settings Change settings while the operation is OFF and power supply is ON.
CAUTION
Do not change any setting codes other than those in this manual; otherwise, the unit may not work or some problems may occur.
Changing the settings of the Heat recovery ventilation unit (For RBC- AW(M)SU5) In the case of RBC-ASCU1 and RBC-AMTU3, the display position is different, but it can be set in the same way. For RBC-AW(M)SU5, set from “9. DN setting” in the Field setting menu.
59-EN
30
60-EN
31
Codes (DN codes) for changing settings Codes in the table below are necessary for local advanced control.
Code 01 03 13 14 28 31 47
48
49
Description
SET DATA and description
Lighting-up hours of 0000: None
the Filter Sign
0001: 150 H
0002: 2500 H
0003: 5000 H
0004: 10000 H
Central control address
0001: No.1 unit to 0128: No.128 unit (TU2C-Link) No.1 unit to 0064: No.64 unit
(TCC-Link)
00Un: Unfixed
Indoor unit address 0001: No.1 unit to 0128: No.128 unit (TU2C-Link) No.1 unit to 0064: No.64 unit (TCC-Link)
Group address
0000: Individual 0001: Header 0002: Follower 00Un: Unfixed
Auto recovery from a power failure
0000: Invalid
0001: Valid
- Resumes the status just before the power failure
Single operation of the fan
0000: Invalid 0001: Valid
ON/OFF operation for the Heat recovery ventilation unit only
Operation pattern and ventilation fan speed at 24-hour ventilation
0000: Medium fan speed (continuous) 0001: “Before stop” fan speed
(continuous) 0002: Low fan speed (continuous) 0003: High fan speed
(intermittent) “High” may be “Extra High” 60 minutes ON / 60 minutes OFF
Unbalanced ventilation fan speed
(Main setting)
0000: Normal
0001: SA (High) > EA (Medium) or SA (Medium) > EA (Low)
- SA: Fan speed follows the remote controller setting
- EA: Fan speed is one step lower than SA
0002: SA (Medium) < EA (High) or SA (Low) < EA (Medium) - EA: Fan speed follows the remote controller setting
- SA: Fan speed is one step lower than EA
24-hour ventilation 0001: Invalid 0002: Valid
Factory default 0002: 2500 H 00Un: Unfixed 0001: No.1 unit 00Un: Unfixed 0000:
Invalid 0000: Invalid 0002: Low fan
speed
0000: Normal
0001: Invalid
Note Adjusting this setting is necessary for the header unit.
The maximum number of addresses that can be set (64 or 128) depends on the
communication type (TCC-Link or TU2C-Link). The maximum number of addresses
that can be set (64 or 128) depends on the communication type (TCCLink or
TU2C-Link). 5 6
1
Setting change is necessary for the header unit of Air conditioners. 2
Setting change is necessary for all the Heat recovery ventilation unit in the
group. 3
Setting change is necessary for all the Heat recovery ventilation unit in the
group. 3, 4
Setting change is necessary for all the Heat recovery ventilation unit in the
group. 3
Code
4B
4C 4D 4E 5D EA EB
Description Delayed operation
Quick-ventilation control
Nighttime heat purge
Setting of the exhausting fan operation below -20°C (OA)
SET DATA and description
Factory default
0000: Invalid
0000: Invalid
0001 – 0006: [Setting value] × 10 minutes
delay
- Delaying the Heat recovery ventilation unit operation to reduce the airconditioning load when starting running the air conditioner
After starting operation, the fan speed is fixed at “High” for the following
setting time.
(Regardless of the remote controller fan speed setting.)
0000: Invalid
0007: 15 minutes running “High” fan speed
0008: 30 minutes running “High” fan speed
0007: 60 minutes running “High” fan speed
- “High” may be “Extra-High”
0000: Invalid
0000: Invalid
0001 – 0048: Start after [Setting value] × 1 hour(s)
- Setting for the time before the nighttime heat purge operation starts
0000: Nighttime heat purge OFF
0000: Exhausting fan run
0001: Exhausting fan stop
- The supplying fan stops when the temperature is below -20°C (OA)
0000: Exhausting fan run
Setting of the linked operation with external devices
0000: ON/OFF linked
0001: ON linked
0002: OFF linked
- Specifies whether the ON/OFF operation of the Heat recovery ventilation unit is linked with the external device operation
0000: ON/OFF linked
Max fan speed selection
0000: High 0001: Extra High
0001: Extra High
Changing the ventilation mode
Changing the ventilation Fan speed
0001: Bypass mode
0003: Automatic
0002: Heat Exchange mode
mode
0003: Automatic mode
- Compatible with systems without a remote controller and RBC-ASCU1 and RBC-AMTU3
0002: High 0003: Medium
0004: Unbalanced (High) 0011: Low 0012: Unbalanced (Medium) “High” may be
“Extra High” Compatible with remote controller less
systems or when using remote controller “RBC-ASCU1 and RBC-AMTU3”.
0002: High
Note Setting change is necessary for all the Heat recovery ventilation unit in
the group. 2, 3
Setting change is necessary for all the Heat recovery ventilation unit in the
group. 3
Setting change is necessary for all the Heat recovery ventilation unit in the
group. 2, 3 Setting change is necessary for all the Heat recovery
ventilation unit in the group. 3 Setting change is necessary for a Heat
recovery ventilation unit to which an adapter for remote ON/OFF control (sold
separately) is connected.
Setting change is necessary for all the Heat recovery ventilation unit in the
group. 6 1
*1
61-EN
62-EN
Code ED EE FC 701 702 703 745 747 748 74E
Description
SET DATA and description
Factory default
Note
Changing the operation output
0000: ON during normal operation
0001: ON during normal operation, 24hour ventilation, or nighttime heat purge
operation
0002: ON during 24-hour ventilation or nighttime heat purge operation
0003: ON when SA fan is running
0004: ON when EA fan is running
0000: ON during normal operation
Setting change is necessary for a Heat recovery ventilation unit which transfers the operation output.
Changing the abnormal signal / Bypass mode signal output
0000: ON when an abnormal signal is detected
0001: ON when the Bypass mode signal is detected
0000: ON when an abnormal signal is detected
Setting change is necessary for a Heat recovery ventilation unit which transfers the operation output.
Communication type
0000: TCC-Link 0004: TU2C-Link
0004: TU2C-Link
Setting change is necessary for all the Heat recovery ventilation unit in the
group.
*3
- For details, refer to “6. Electrical connection Remote controller wiring”.
Remote controller 0000: No correction
display value
-0010 – 0010: Add the value × 1°C to the
correction for
displayed value
“Outdoor
temperature (TOA)”
0000: No correction The displayed value is the value detected at the intake
port (OA) of the Heat recovery ventilation unit.
*1
Remote controller 0000: No correction
display value
-0010 – 0010: Add the value × 1°C to the
correction for
displayed value
“Indoor temperature
(TRA)”
0000: No correction The displayed value is the value detected at the intake
port (RA) of the Heat recovery ventilation unit.
*1
Remote controller display value correction for “Indoor humidity”
0000: No correction
-0020 – 0020: Add the value × 1% to the displayed value
0000: No correction The displayed value is the value detected at the intake
port (RA) of the Heat recovery ventilation unit.
*1
Forced stop due to humidity at Nighttime heat purge
0000: Invalid 0001 – 0100: Humidity (%)
0000: Invalid
· When the humidity exceeds the set humidity, it will be forced to stop.
· The humidity value is the value detected at the intake port (RA) of the Heat
recovery ventilation unit.
Operation pattern and ventilation fan speed at Nighttime heat purge
0000: Medium fan speed (continuous) 0001: “Before stop” fan speed
(continuous) 0002: Low fan speed (continuous) * “High” may be “Extra High”
0002: Low fan speed
Setting change is necessary for all the Heat recovery ventilation unit in the
group.
2, 3
Unbalanced Fan speed ventilation
(Sub setting)
0000: Not fixed
0001: Fixed the low airflow side at Low fan speed SA > EA (Low) or SA (Low) <
EA
0000: Not fixed
· This setting is invalid if DN code [48] is not set.
· Setting change is necessary for all the Heat recovery ventilation unit in
the group.
*3
Fan control
0000: Constant input power control 0001: Constant air volume control
0000: Constant input power control
Setting change is necessary for all the Heat recovery ventilation unit in the
group.
*3
Code
Description
“High” fan speed power setting of supply air (SA) and exhaust air (EA)
- “High” may be “Extra-High”
750, 754
SET DATA and description
Factory default
· If you want to use “High setting”, it must be set to “DN code [5D] = 0000”
· Percentages below are for “Extra-High (100%)”
· You can set the data from 40% to 100% by the 1%.
As shown in the table on the left
- Max.: 0100 * Min.: 0040
DN code Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[750] SA power 0067: 67% 0066: 66% 0051: 51% 0054: 54% 0050: 50% 0054: 54% 0050: 50% [754] EA power 0060: 60% 0066: 66% 0050: 50% 0053: 53% 0048: 48% 0055: 55% 0052: 52%
Note
· These setting are for “Constant input power control”. (for supply air and
exhaust air fan motor power)
· Setting change is necessary for all the Heat recovery ventilation unit in
the group.
*3
751, 755
“Medium” fan speed power setting of supply air (SA) and exhaust air (EA)
· Percentages below is for “Extra-High (100%)”
· You can set the data from 20% to 50% by the 1%.
DN code Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[751] SA power 0042: 42% 0033: 33% 0023: 23% 0024: 24% 0024: 24% 0028: 28% 0023: 23% [755] EA power 0040: 40% 0033: 33% 0023: 23% 0022: 22% 0021: 21% 0028: 28% 0025: 25%
As shown in the table on the left
- Max.: 0050 * Min.: 0020
“Low” fan speed power setting of supply air (SA) and exhaust air (EA)
752, 756
· Percentages below is for “Extra-High (100%)”
· You can set the data from 5% to 25% by the 1%.
DN code Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[752] SA power 0025: 25% 0017: 17% 0007: 7% 0018: 18% 0007: 7% 0012: 12% 0009: 9% [756] EA power 0020: 20% 0015: 15% 0008: 8% 0016: 16% 0006: 6% 0012: 12% 0010: 10%
As shown in the table on the left
- Max.: 0025 * Min.: 0005
63-EN
32
64-EN
33
Code
Description
SET DATA and description
Factory default
“High” fan speed air volume setting of supply air (SA) and exhaust air (EA) *
“High” may be
“Extra-High”
759, 75D
· If you want to use “High setting”, it must be set to “DN code [5D] = 0000”
· Percentages below are for “Extra-High (100%)”
· You can set the data from 71% to 120% by the 1%.
DN code
Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[759] SA air volume [75D] EA air volume
0080: 80% 0080: 80%
As shown in the table on the left
- Max.: 0120 * Min.: 0071
Note
· These setting are for “Constant air volume control”. (for supply air and
exhaust air)
· Setting change is necessary for all the Heat recovery ventilation unit in
the group.
*3
75A, 75E
“Medium” fan speed air volume setting of supply air (SA) and exhaust air (EA)
· Percentages below is for “Extra-High (100%)”
· You can set the data from 51% to 70% by the 1%.
DN code
Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[75A] SA air volume [75E] EA air volume
0060: 60% 0060: 60%
As shown in the table on the left
- Max.: 0070 * Min.: 0051
“Low” fan speed air volume setting of supply air (SA) and exhaust air (EA)
75B, 75F
· Percentages below is for “Extra-High (100%)”
· You can set the data from 30(35)% to 50% by the 1%.
DN code
Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[75B] SA air volume [75F] EA air volume
0040: 40% 0040: 40%
As shown in the table on the left
- Max.: 0050 Min.: 0030 (SA) Min.: 0035 (EA)
1 Setting change is necessary for the header unit when installing the system with the Heat recovery ventilation unit only, or the smallest indoor unit address number of Heat recovery ventilation unit when using the system linked with Air conditioners.
2 This setting is for the system linked with Air conditioners system. 3 Setting change apply only to the unit that changed the data. 4 If you want to set the fan speed difference in 2 steps, for example SA = High and EA = Low, you also need
to set DN code [748]. 5 DN and DIP SW settings are given priority to later
operations. 6 DN setting is possible only when DIP SW is “OFF” (factory
default).
Changing the time before the Filter Sign lights up
· Setting change is necessary for all the header unit of Heat recovery ventilation unit when installing the system with the Heat recovery ventilation unit only.
- Refer to the “DN setting” section for how to set the DN code. (Same for the following setting items)
Code 01
SET DATA
Time before the Filter Sign lights up
0000 None
0001 150 H
0002
2500 H (Factory default)
0003 5000 H
0004 10000 H
Setting of auto recovery from a power failure
· Setting change is necessary for the header unit when installing the system with the Heat recovery ventilation unit only, or the smallest indoor unit address number of Heat recovery ventilation unit when using the system linked with Air conditioners.
Code 28
SET DATA
Auto recovery from a power failure
0000
Invalid (Factory default)
0001 Valid
65-EN
66-EN
Setting of the Heat recovery ventilation unit single operation (Setting for the header air conditioner)
· Setting change is necessary for the header unit of Air conditioners.
- This setting is for the system linked with Air conditioners system. * There are two ways to operate the remote controller (on the main screen or in the menu “11. Ventilation”). For
details on operation, refer to the following.
Code 31
SET DATA Single operation of the fan
0000
Invalid (Factory default)
0001 Valid
Setting from the main screen
(1) on the main screen will change to (2) after 5 seconds.
Setting from the “Menu”
In “Menu”, select “Ventilation”.
(*1)
Push [ ] button.
Select item and push [ ] button.
(*2)
Select item and push [ ] button.
REQUIREMENT This setting is invalid when the operation is linked by a signal from an external device or remotely controlled on and off.
Setting of the unbalanced ventilation Fan speed
· SA / EA unbalanced operation of the Heat recovery ventilation unit is
possible.
· Setting change is necessary for all the Heat recovery ventilation unit in
the group.
- Setting change apply only to the unit that changed the data. * If you want to set the fan speed difference in 2 steps, for example SA = High and EA = Low, you also need to
set DN code [748].
Code 48
SET DATA
Umbalanced ventilation fan speed (Main setting)
0000
Normal (Factory default)
0001
SA (High) > EA (Medium) or
SA (Medium) > EA (Low)
0002
SA (Medium) < EA (High) or
SA (Low) < EA (Medium)
Setting of 24-hour ventilation
· Setting change is necessary for all the Heat recovery ventilation unit in the group. * Setting change apply only to the unit that changed the data.
Code 49
SET DATA 24-hour ventilation
0000
Invalid (Factory default)
0001 Valid
Setting of delayed operation
· The operation of the Heat recovery ventilation unit is delayed by [Setting
value] × 10 minutes (10 to 60 minutes) when the [ON/OFF] button is pressed.
(Available when the operation of the Heat recovery ventilation unit is linked
with that of Air conditioners.)
· Setting change is necessary for all the Heat recovery ventilation unit in
the group.
- Setting change apply only to the unit that changed the data. * This setting is for the system linked with Air conditioners system.
Code 4B
SET DATA Delayed operation
0000
Invalid (Factory default)
0001 to 0006 [Setting value] × 10 minutes delay
Nighttime heat purge setting
· Nighttime heat purge exhausts hot air in the room by bypass mode and reduces
the cooling load in the morning. Monitoring operation starts after [Setting
value] × 1 hour(s). (1 to 48 hours)
· Setting change is necessary for all the Heat recovery ventilation unit in
the group. Setting change apply only to the unit that changed the data.
This setting is for the system linked with Air conditioners system.
Code 4C
SET DATA Nighttime heat purge
0000
Invalid (Factory default)
0001 to 0048
Start after [Setting value] × 1 hour(s)
67-EN
34
68-EN
35
Setting for operation of the exhausting fan below -20°C
· Stops the exhausting fan when the outdoor temperature falls below -20°C. · Setting change is necessary for all the Heat recovery ventilation unit in the group.
- Setting change apply only to the unit that changed the data. The air supplying fan stops regardless of this setting. When the indoor temperature is over 21°C, the exhausting fan stops even when the outdoor temperature is
higher than -20°C.
Code 4D
SET DATA
Exhausting fan operation below -20°C
0000
Exhausting fan runs (Factory default)
0001 Exhausting fan stops
Setting for linked operation with external devices
· Specifies the operation of the Heat recovery ventilation unit linked with the on/off operation of external devices.
- Setting change is necessary for a Heat recovery ventilation unit to which an adapter for remote ON/OFF control (sold separately) is connected.
Code 4E
SET DATA
Linked operation with external devices
0000
ON/OFF linked (Factory default)
0001 ON linked
0002 OFF linked
0000: The Heat recovery ventilation unit starts / stops together with the
starting / stopping of an external device. (The latter operation of the remote
controller or the switch of the external device overrides the former.)
0001: The Heat recovery ventilation unit starts together with the starting of
an external device. Use the remote controller to stop operation.
0002: The Heat recovery ventilation unit stops together with the stopping of
an external device. Use the remote controller to start operation.
Ventilation mode setting
· The setting of the ventilation mode can be changed when the remote
controller for Air conditioners RBC-ASCU1 and RBC-AMTU3 or a system without
a remote controller is used.
· Setting change is necessary for the header unit when installing the system
with the Heat recovery ventilation unit only, or the smallest indoor unit
address number of Heat recovery ventilation unit when using the system linked
with Air conditioners.
- When the remote controller RBC-AW(M)SU5* is installed, this setting is invalid. (Because the remote controller can be used for operation.)
Code EA
SET DATA Changing the ventilation mode
0000 Bypass mode
0001 Heat Exchange mode
0002
Automatic mode (Factory default)
Ventilation Fan speed setting
· The setting of the ventilation Fan speed can be changed when the remote
controller for Air conditioners RBC-ASCU1 and RBC-AMTU3 or the system
without the remote controller is used.
· Setting change is necessary for the header unit when installing the system
with the Heat recovery ventilation unit only, or the smallest indoor unit
address number of Heat recovery ventilation unit when using the system linked
with Air conditioners.
- When the remote controller RBC-AW(M)SU5* is installed, this setting is invalid. (Because the remote controller can be used for operation.)
Code EB
SET DATA
Changing ventilation fan speed
0002
High (Factory default)
0003 Medium
0004
Unbalanced (High)
0011 Low
0012
Unbalanced (Medium)
- When [0004] or [0012] is selected, adjust setting of the unbalanced ventilation Fan speed (Code: [48]).
Setting for changing the operation output
· This operation output can be used to connect an auxiliary fan or operate an external device. (You can select the output pattern from the table below.)
- Setting change is nesessary for the Heat recovery ventilation unit to which an external device is connected.
Code
SET DATA
Changing the
ED
operation
output
0000
ON during normal
operation (Factory default)
0001
0002
ON during normal
operation, 24hour ventilation,
or nighttime heat purge operation
ON during 24hour ventilation
or nighttime heat purge operation
0003
ON when SA fan is running
0004
ON when EA fan is running
0000: Contact is on only during normal operation. Contact is off during
24-hour ventilation or nighttime heat purge operation. Contact is off during
cold mode (while the temperature is below -10°C).
0001: Contact is on during normal operation, 24-hour ventilation, or nighttime
heat purge operation. Contact is on when 24-hour ventilation is stopped
intermittently. Contact is off when nighttime heat purge operation is on
standby. (paused before the monitoring operation of the nighttime heat purge
operation starts) Contact is off during cold mode (while the temperature is
below -10°C).
0002: Contact is on during 24-hour ventilation or nighttime heat purge
operation. Contact is on when 24-hour ventilation is stopped intermittently.
- Contact is off during normal operation or when the nighttime heat purge
operation is on standby. (paused before the monitoring operation of the
nighttime heat purge operation starts) Contact is off during cold mode
(while the temperature is below -10°C).
0003: Contact is on only when SA fan is running. Contact is off when 24-hour ventilation is stopped intermittently, so do not connect an auxiliary fan.
0004: Contact is on only when EA fan is running. * Contact is off when 24-hour ventilation is stopped intermittently, so do not connect an auxiliary fan. - Contact is off during delayed operation, when switching the damper (Heat exchange mode / Bypass mode), regardless of the selected value.
69-EN
70-EN
Abnormal signal / bypass mode signal output setting
· External output can be used to detect an abnormal signal / bypass mode signal output. Output signal to be detected can be selected.
- Setting change is nesessary for the Heat recovery ventilation unit to which an external output is connected. * When [0000] is selected, contact is on If there is any trouble on the connected Heat recovery ventilation unit.
Code EE
SET DATA
Changing the abnormal signal / bypass mode signal output
0000
ON when an abnormal signal is detected
(Factory default)
0001
ON when the bypass mode signal is detected
0000: Contact is on when an abnormal signal output is detected. 0001: Contact is on when the bypass mode signal output is detected.
- Contact is on during nighttime heat purge operation. Contact is off when the nighttime heat purge operation is on standby. (paused before the monitoring operation
of the nighttime heat purge operation starts) Even when is displayed on the remote controller, contact is off during the Heat exchange mode.
Select of fan control type
· There are two types of fan control, so you can select one according to the local installation requirements. · Setting change is necessary for all the Heat recovery ventilation unit in the group. * Setting change apply only to the unit that changed the data.
Code 74E
SET DATA Fan control type
0000
Constant input power control (Factory default)
0001 Constant air volume control
Adjust for Constant input power control
· These setting are for “Constant input power control”. (for supply air and
exhaust air fan motor power) · This power setting can be adjusted when the
duct length is significantly different between the supply air and the
exhaust air. · All percentages can be set as a ratio to Extra-High mode
(100%). In case of “Extra-High”, the air volume will be fixed at 100%.
(Therefore, the power percentage cannot be changed in “Extra-High” mode.)
Must change for “DN code [5D] = 0000” when changing the power percentage for
“High” fan speed. · Do not set the power of each fan speed to be High < Medium
or Medium < Low. · Setting change is necessary for all the Heat recovery
ventilation unit in the group. * Setting change apply only to the unit that
changed the data. · When adjusting the data in the table, refer to the P-Q
graph below.
Code
SET DATA
(Factory default)
· If you want to use “High setting”, it must be set to “DN code [5D] = 0000”
· You can set the data from 40% to 100% by the 1%. * Max.: 0100, Min.: 0040
750, 754
“High” fan speed power setting of supply air (SA) and exhaust air (EA)
- “High” may be “Extra-High”
DN code Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[750] SA power 0067: 67% 0066: 66% 0051: 51% 0054: 54% 0050: 50% 0054: 54% 0050: 50% [754] EA power 0060: 60% 0066: 66% 0050: 50% 0053: 53% 0048: 48% 0055: 55% 0052: 52%
· You can set the data from 20% to 50% by the 1%. * Max.: 0050, Min.: 0020
“Medium” fan speed power setting 751, 755 of supply air (SA) and exhaust air
(EA)
DN code Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[751] SA power 0042: 42% 0033: 33% 0023: 23% 0024: 24% 0024: 24% 0028: 28% 0023: 23% [755] EA power 0040: 40% 0033: 33% 0023: 23% 0022: 22% 0021: 21% 0028: 28% 0025: 25%
· You can set the data from 5% to 25% by the 1%. * Max.: 0025, Min.: 0005
“Low” fan speed power setting of 752, 756 supply air (SA) and exhaust air
(EA)
DN code Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[752] SA power 0025: 25% 0017: 17% 0007: 7% 0018: 18% 0007: 7% 0012: 12% 0009: 9% [756] EA power 0020: 20% 0015: 15% 0008: 8% 0016: 16% 0006: 6% 0012: 12% 0010: 10%
71-EN
36
72-EN
37
Adjust for Constant air volume control
· These setting are for “Constant air volume control”. (for supply air and
exhaust air) · This setting can keep the rated air volume even if the pressure
loss varies depending on the duct. · All percentages can be set as a ratio to
Extra-High mode (100%). * In case of “Extra-High”, the air volume will be
fixed at 100%.
(Therefore, the air volume percentage cannot be changed in “Extra-High” mode.)
- Must change for “DN code [5D] = 0000” when changing the air volume percentage for “High” fan speed. · Do not set the air volume of each fan speed to be High < Medium or Medium < Low. · Setting change is necessary for all the Heat recovery ventilation unit in the group. * Setting change apply only to the unit that changed the data. · When adjusting the data in the table, refer to the P-Q graph below.
Code
SET DATA
(Factory default)
· If you want to use “High setting”, it must be set to “DN code [5D] = 0000”
· You can set the data from 71% to 120% by the 1%. * Max.: 0120, Min.: 0071
759, 75D
“High” fan speed air volume setting of supply air (SA) and exhaust air (EA)
- “High” may be “Extra-High”
DN code Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[759] SA air volume [75D] EA air volume
0080: 80%
0080: 80%
· You can set the data from 51% to 70% by the 1%. * Max.: 0070, Min.: 0051
“Medium” fan speed air volume 75A, 75E setting of supply air (SA) and
exhaust air (EA)
DN code Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[75A] SA air volume [75E] EA air volume
0060: 60%
0060: 60%
· You can set the data from 30(35)% to 50% by the 1%. * Max.: 0050, Min.: 0030(SA) / 0035(EA)
“Low” fan speed air volume 75B, 75F setting of supply air (SA) and
exhaust air (EA)
DN code Class
150 m³/h 250 m³/h 350 m³/h 500 m³/h 650 m³/h 800 m³/h 1000 m³/h
[75B] SA air volume [75F] EA air volume
0040: 40%
0040: 40%
P-Q graph
Use the graph below as a guide for adjusting the data.
150 m³/h
250
P-Q Curve * When friction coefficient of pipe (duct): = 0.02
250 m³/h
300
External static pressure (Pa)
Equivalent pipe length
External static pressure (Pa)
200
90%
Extra High 100%
80% 150
70%
60%
50%
100 40%
30%
50
60%
30 m 20 m 10 m
Low 25%
0 0
40% 50
80%
Extra High 100%
100
150
200
250
Air Volume (m³/h)
250
Extra High
100%
90%
80% 200
70%
100 m
Equivalent pipe length
60%
150
50%
80 m
40%
60 m
100
30%
20%
60%
50
Low 16%
40%
0
0
50 100 150
80% 200
40 m
20 m Extra High 100% 250 300 350
Air Volume (m³/h)
External static pressure (Pa)
Equivalent pipe length
External static pressure (Pa)
350 m³/h
500
450
400
Extra High
100%
350
90% 80%
70% 300
60%
250
50%
40%
200 30%
150
20% 60%
100
50 Low 8%
0
0
40% 100
80%
200
300
Air Volume (m³/h)
100 m 80 m 60 m 40 m
20 m
Extra High 100%
400
500
500 m³/h
500
450
400
Extra High
90%
100%
80% 350
70%
300
60%
50%
250
40%
200
30%
E10x0tr%a HigEhquivalelenngtthpip1e00 m
150
25%
80%
80 m
60%
100
Low
23%
50
40%
60 m 40 m 20 m
0 0 100 200 300 400 500 600 700
Air Volume (m³/h)
73-EN
74-EN
650 m³/h
500
450
External static pressure (Pa)
400
Extra High
350
70%
100%
100 m
60%
300
50%
250
40%
80 m
80%
30%
200
90%
60 m
20%
150
14%
60% 80%
40 m
100 Low
50 12% 40%
0
20 m
Extra High 100%
0 100 200 300 400 500 600 700 800 900
Air Volume (m³/h)
Equivalent pipe length
External static pressure (Pa)
P-Q Curve * When friction coefficient of pipe (duct): = 0.02
800 m³/h
500
450
400
Extra High
350
90% 100%
80% 300
70%
250
60%
50%
200
40%
30% 150
20%
Extra High 100% Equivalelenngtthpip1e00 m
80 m
100
60% 80%
60 m
Low
40 m
50 11% 40%
20 m
0
0
200
400
600
800 1000 1200
Air Volume (m³/h)
1000 m³/h
700
600
External static pressure (Pa)
500 90%
80%
400
70%
40%
60%
300
30%
50%
20%
200 15%
100
Low 9% 40%
0
0
200 400
60% 600
Extra High 100%
80%
E10x0tr%a HEiqguhivalelenng1tt0hp0ipem 80 m 60 m 40 m 20 m
800 1000 1200 1400
Air Volume (m³/h)
Remote controller switch monitoring function
This function is available to call the service monitor mode from the remote controller during a test run to acquire temperatures of sensors of indoor unit (Heat recovery ventilation unit).
1 Push [ Menu] to open the “Menu”
2 Push and hold [ Menu] and [
open “Field setting menu”
Push and hold 4 seconds.
] at the same time to
3 In the “Field setting menu” screen, push [ ] and
[ ] to select “Monitor function”, and then push [ Set/Fix] Push [ ] and [ ] to
change the code and then check the data. In a group connection, after a
selection in the unit selection screen,
move to the “Monitor function” screen.
4 Push [ Return] Return to the “Field setting menu” screen.
CODE No.
Indoor unit data (Heat recovery ventilation unit) Data name
02
Return air temperature (TRA)
07
Supply air actual fan speed (× 1 rpm)
ED
Relative humidity (× 1%)
EE
Trouble sub-code
- For example “P12” trouble
Sub-code 0000 0001 0002
Description Normal SA motor trouble EA mot
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>