Schreder Briteline Gen2 1 Integrated Version Instruction Manual
- June 12, 2024
- Schreder
Table of Contents
BRITELINE
GEN2 1
Integrated version
INSTALLATION INSTRUCTIONS
PRODUCT OVERVIEW
BRITELINE GEN2 1 with Integrated driver
A| B| C|
609mm
23.97in| 351mm
13.81in| 436mm
1716in| 21.5kg
47.391bs
EPA – Effective Projected Area
| a = 0°| a = 30°| a = 45°| a = 70°| a = 90°
---|---|---|---|---|---
| S(m2)| CxS
(m2)| EPA
(ft2)| S
S(m2)
(m| CxS
(m2)| EPA (ft2)| S(m
S(m2)| CxS
(m2)| EPA
(ft2)| S(m2)| CxS
(m2)| EPA
(ft2)| S(m2)| CxS
(m2)| EPA
(ft2)
Si| 0.0753| 1| 0.98| 0.1333| 0.16| 2.| 0.1434| 0.18| 2.| 0.1405| 0.17| 2.|
0.1408| 0.17| 2.
S2| 0.1408| 0.17| 2.| 0.1450| 0.18| 2.| 0.1435| 18| 2.| 0.1212| 0.15| 2.|
0.0753| 0.1| 0.98
S3| 0.0398| 0.05| 0.52| 0.0398| 0.05| 0.52| 0.0398| 0.05| 0.52| 0.0398| 0.05|
0.52| 0.0398| 0.05| 0.52
MOUNTING
Screws and washers are not included inthe package!
Minimum screw requirement:
Vibration standard | IEC 0.5g / ANSI 1.5g |
---|---|
Minimum fastener requirement | 1x M20 8.8 or A2-70 DIN9021 large plain washer |
Tightening torques | 1xM20: 200 Nm 2xM20: 140 Nm |
Recommended to use anti-seizing agent (Tikal Tef-Gel®) !
-
1xM20 with large plain washer
or -
2xM20 with large plain washer
Mounting dimensions
D1 | D2 | D3 | D4 | D5 |
---|---|---|---|---|
min 250mm min 9.84in | 70mm 2.75in | 150mm 5.9in | 320mm 12,6in | 460mm 15.98in |
Minimum Surface Contact Area for screw fixation 250mm/9.84in
Fasteners are not included in the package!
Remark: the hatched area always need to be supported by a flat planar mounting
surface as minimum.
Wider surface contact is recommended, smaller is not allowed!
ANGLE ADJUSTMENT
-
Loosen the clamp screws
-
Adjust tilting angle
Separate scale for adjusting the distance of the optical block from the luminaire holder 50mm
The swing arm inclination is adjustable in 10 degree increments relative to fork base.
ALLOWED tilt angle is between -10° to 90° -
Tighten the clamp screws
Do not exceed the proposed torque levels, as it may result in fraction of the parts!
ALLOWED POSITIONING
Suspended installation
SAFETY CABLE
Steel safety cable should pass through the holes shown in the drawing in
sequence.
Then connect the two ends with the lock buckle and tighten the lock bolt by
hand.
For installations over 3m height: secondary safety system application is
mandatory, which is appropriated for the luminaire load (e.g. safety cable)
1500mm/59.05in safety cable is supplied with the luminaire.
ELECTRICAL CONNECTION
-
Remove the R-type buckles from the junction box
-
Open junction box
-
Make the electrical connection
0-10V/DALI
Connection ID| Cable ID
PE/| Protective
Earth
L| Line
N| Neutral
D+| Dim +
D-| Dim –
DMX
Connection ID| Cable ID
PE/| Protective
Earth
L| Line
N| Neutral
D+| Data +
D-| Data –
Sh| Shield
Cable gland parameters
When using a larger external diameter cable, the plug and the smaller inner
diameter seal hasto be removed.
When using a smaller external diameter cable, simply remove the plug.
Connection | Cable gland | Recommended cable type |
---|---|---|
AC INPUT | PG20(Ø6-Ø10/Ø10-Ø14) | H05RN-F , 5 x 1.0mm2 |
H07RN-F , 5 x 1.5mm2
5. Close the junction box
Close junction box cover, lock the buckle and insert R-type buckles back in
RECOMMENDATIONS
-
Surrounding distances
At least 1 meter distance should be kept from surrounding walls, floor, and ceiling for all types of mounting/inclination. -
Maximum number of luminaires per MCB
Product| Driver| MCB B type
---|---|---
B10| B13| B16| B20| B25| B32| B40
BRITELINE GEN2 1 ©220V| EUM-680MG/BG| 1| 2| 2| 3| 4| 5| 6
BRITELINE GEN2 1 ©480V| ESM-680MG/BG| 2| 2| 3| 4| 5| 6| 7
Product| Driver| MCB C type
C10| 13| 16| C20| C25| C32| C40
BRITELINE GEN2 1 ©220V| EUM-680MG/BG| 1| 2| 3| 3| 4| 5| 6
BRITELINE GEN2 1 ©480V| ESM-680MG/BG| 3| 4| 5| 7| 9| 11| 14
AIMING DEVICE
ACCESSORIES – HOOD
SAFETY INSTRUCTIONS
The light source contained in this luminaire shall only be replaced by the
manufacturer or his service agent or a similar qualified person. Always switch
off the power prior to installation, maintenance or repair activities.
RISK GROUP 2 – CAUTION! Hazardous optical radiation may be emitted from this
product. Do not stare at the luminaire when operating as it may be harmful to
the eyes. The luminaire should be positioned so that prolonged staring at the
luminaire at a distance of less than 0.2m is not expected.
This product contains a light source of an energy efficiency class G or
higher.
In case of PVC insulated mains cable, the installer MUST ensure that the WHOLE
cable is protected against climatic conditions, especially UV rays and rain,
by making sure that the cable is contained inside the luminaire and pole
Y-connection: In case of amage to the wire, it has to be replaced only by the
manufacturer, distributor or by an expert, to avoid risks.
www.schreder.com
Rev B | 07-2023
Copyright © Schréder S.A. 2023 – Executive Publisher: Stéphane Halleux –
B-4000 Liége, Rue de Mons 3 (Belgium) – The information, descriptions and
illustrations herein are only of an indicative nature and subject to changes
without notice.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>