CHARGER V3175SP-01 SP Solar Powered Control Valve
Front Cover and Drive Assembly
Drawing No. | Order No. | Description | Quantity |
---|---|---|---|
1 | V3175SP-01 | WS1SP FRONT COVER ASSEMBLY | 1 |
2 | V3107-01 | WS1 MOTOR | 1 |
3 | V3814-01 | WS1 DRIVE BRACKET SOLAR & SPRING CLIP | 1 |
4 | V4072SP-03BOARD | WS1THRU SPPCB AC/DC REPL | 1 |
5 | V3110 | WS1 DRIVE GEAR 12X36 | 3 |
6 | V3109 | WS1 DRIVE GEAR COVER | 1 |
7 | V3835-02 | WS1SP BATTERY PACK CHARGED W/TIE | 1 |
8 | V3842 | WS1SP SOLAR PANEL W/BRKT ASY | 1 |
Not Shown | V3186-06 | WS1 POWER SUPPLY US 15VDC HOCP | 1 |
Not Shown | V3178 | WS1 DRIVE BACK PLATE | 1 |
Refer to Control Valve Service Manual for other drawings and part numbers.
Power Supply | U.S. | International |
---|---|---|
Supply Voltage | 100-120VAC | 100-240 VAC |
Supply Frequency | 50/60 Hz | 50/60 Hz |
Output Voltage | 15 VDC | 15 VDC |
Output Current | 500 mA | 500 mA |
Wiring Diagram
Regeneration and Error Screens
Regen Screen
Displays the time remaining in the current cycle. Pressing REGEN advances to
the next cycle.
Error Screen
Alternated flashing Err and error code every 3 seconds. Clear by disconnecting
the power supply at the PC board and reconnecting, or press NEXT and REGEN
simultaneously for 3 seconds.
In Alternator Systems when a unit is waiting to initiate the first cycle step
of regeneration, “REGEN Pndg” is displayed.
“STbY” is displayed in Alternator Systems when a valve is in Standby state.
Button Operation and Function
Scrolls to the next display.
Pressing once and releasing will schedule a regeneration at the preset delayed
regeneration time.
Pressing again and releasing will cancel the regeneration.
Pressing and holding for 3 seconds will initiate an immediate regeneration
Pressing while in regeneration will advance to the next cycle.
Pressing in the program levels will go backwards to the previous screen
Changes variable being displayed.
Key sequence to lock and unlock program settings.
Holding for 3 seconds initiates a control reset. The software version is
displayed and the piston returns to the home/service position, resynchronizing
the valve.
Used with valve type 1.0 , holding for at least 3 seconds causes a switch in
the tank in Service without cycling the regeneration valve. After tank switch,
days remaining and capacity remaining status is retained for each tank until
the next regeneration.
Regeneration Cycles and Times
Range | |
---|---|
Cycle | Softening |
Backwash
Backwash| 1-120 minutes| 1-120 minutes| 1-120 min.
Regenerant Draw/Slow Rinse (UP or DN)| 1-180 minutes| 1-180 minutes| NA
Fast Rinse| 1-120 minutes| 1-120 minutes| 1-120 min.
Regenerant Refill| 0.1-200.0 lbs.| .05-20.0 Gal.| NA
Regenerant Refill 2.0 or1.5 set toMIN(softeningonly)| 0.1-99.0minutes|
0.1-99.0minutes| NA
Service| 1-480 minutes| NA| NA
If 1.5 or 2.0 is selected in Step 2CS, cycles can be set to “oFF”.
The user can initiate manual regeneration. The user has the option to request the manual regeneration at the delayed regeneration time or to have the regeneration occur immediately:
- Pressing and releasing the REGEN button. “ REGEN TODAY” will flash on the display and the regeneration will occur at the delayed regeneration time. The user can cancel the request by pressing and releasing the REGEN button.
- Pressing and holding the REGEN button for approximately 3 seconds will immediately start the regeneration. The user cannot cancel this request, except by resetting the control by pressing NEXT and REGEN simultaneously for 3 seconds.
User Displays
When the system is operating, one of five displays may be shown. Pressing NEXT will alternate between the displays shown below.
General Operation User 1
Typical user display. Shows volume remaining to regeneration. This screen will not be viewed if the control is set for time-clock operation.
User 2
Displays number of days to next regeneration. Only displayed if control is set
for time-clock operation.
User 3
Flow Rate.
Displays present flow rate.
Not viewed (along with SOFTENING or FILTERING Icon) if ALT A or ALT b is set
in CONFIGURATION 4 and the valve is currently in Standby. When 1.0T is set in
CONFIGURATION 1, the display will indicate the tank currently in Service (“A”
or “b”) in the leftmost digit.
User 4
Displays total volume in gallons since last reset. If a meter is not used this
display will be shown but 0 will be displayed.
PRESS FOR 3 SECONDS TO RESET TO 0.
User 5
Shows current time. When FILL is displayed, the battery pack is being charged.
Setting Time of Day
Push NEXT until time of day screen is displayed. Press and hold until SET
TIME is displayed and the hour flashes once. Press or until the correct
hour is displayed.
Then press NEXT. The minutes will flash. Press or until the correct minute
is displayed.
Press NEXT to return to the User Displays. Time of day should only need to be
set after power outages lasting more than 8 hours, if the battery has been
depleted and a power outage occurs, or when daylight saving time begins or
ends. If a power outage lasting more than 8 hours occurs, the time of day will
flash on and off which indicates the time of day should be reset. If a power
outage lasts less than 8 hours and the time of day flashes on and off, the
time of day should be reset and the battery replaced.
Configuration Settings
Step 1CS – Press NEXT and simultaneously for 5 seconds and release. Press
NEXT and simultaneously for 5 seconds and release. If the screen in Step 2CS
does not appear, the lock on the valve is activated. To unlock, press , NEXT,
and REGEN in sequence, then press NEXT and simultaneously for 5 seconds
and release. Press NEXT and simultaneously for 5 seconds and release.
Step 2CS – Use or to select 1.0 for 1” valve, 1.25 for 1.25” valve, 1.5
for 1.5” valve, 2.0 for 2” valve or 1.0T for twin valve. Press NEXT to go to
Step 3CS. Press REGEN to exit Configuration Settings.
Step 3CS – If 1.5 or 2.0 is selected in Step 2CS, an additional screen will
appear. It is used to select which size flow meter is to be used with the
valve, 1.0r, 1.5, 2.0 or 3.0. Variable meter pulses of 0.1-150.0 PPG can also
be selected. Press NEXT to go to Step 4CS. Press REGEN to return to the
previous step.
Step 4CS – Selecting the use of an outside signal to initiate a regeneration:
Selection only matters if a connection is made to the two pin connector
labeled DP SWITCH located on the printed circuit board. Following is an
explanation of the options:
oFF – feature not used
NOTE: In a twin alternating system each control must have a separate dP
signal or dP switch. One dP signal or one dP switch cannot be used for both
controls.
on0 – If the dP switch is closed for an accumulative time of 2 minutes a
regeneration will be signaled to the unit. In a twin alternating system the
MAV will transition first to switch units so that the signaled unit can start
regeneration. After the MAV has fully transitioned, the regeneration begins
immediately. Note: For WS1 – WS1.5 control valves programmed for twin
alternating: if the dP function “on0” is set, the Delayed Rinse and Fill
feature is not available.
dEL – If the dP switch is closed for an accumulative time of 2 minutes a
regeneration will occur at the scheduled delayed regeneration time. In a twin
alternating system once the dP switch is triggered the PC Board will display
“REGEN TODAY” and when the delayed regen time comes the control will switch
tanks and the triggered unit will then go into regeneration. Note: For WS1 –
WS1.5 control valves programmed for twin alternating: if the dP function “dEL”
is set, the Delayed Rinse and Fill feature is not available.
HoLd – If the dP switch is closed a regeneration will be prevented from
occurring while there is switch closure. In a twin alternating system the
regeneration of a unit can be prevented upon switch closure. If the unit
depletes the capacity down to zero, it will not be allowed to switch tanks to
regenerate until the switch is open. Note: For WS1 – WS1.5 control valves
programmed for twin alternating the Delayed Rinse and Fill feature can be set.
Press NEXT to go to Step 5CS. Press REGEN to return to previous step.
Step 5CS – This display will not appear if 1.0T was selected in Step 2CS. Allows selection of one of the following using or :
- the Control Valve to have no hard water bypass; or
- the Control Valve to have a separate source during the regeneration cycle.
Select OFF when none of these features are used.
Only use Clack No Hard Water Bypass Valves or Clack Motorized Alternating Valves (MAV) with these selections. Clack No Hard Water Bypass Valves (1” or 1.25” V3070FF or V3070FM) are not designed to be used with the alternator or separate source functions.
Configuring the Control Valve for No Hard Water Bypass Operation:
Select nHbP for control operation. For no hard water bypass operation the
three wire communication cable is not used.
Selection requires that a connection to MAV or a Clack No Hard Water Bypass
Valve is made to the two pin connector labeled MAV located on the printed
circuit board. If using a MAV, the A port of the MAV must be plugged and the
valve outlet connected to the B port. When set to nHbP the MAV will be driven
closed before the first regeneration cycle that is not FILL or SOFTENING or
FILTERING, and be driven open after the last regeneration cycle that is not
FILL.
NOTE: If the control valve enters into an error state during regeneration
mode, the no hard water bypass valve will return to the open Position, if not
already there.
Configuring the Control Valve for Separate Source Operation:
Select SEPS for control operation. For separate source operation the three
wire communication cable is not used.
Selection requires that a connection to a Clack Motorized Alternator Valve
(MAV) is made to the two pin connector labeled MAV located on the printed
circuit board. The C port of the MAV must be connected to the valve inlet and
the A port connected to the separate source used during regeneration. The B
port must be connected to the feed water supply.
When set to SEPS the MAV will be driven closed before the first regeneration
cycle, and be driven open after the last regeneration cycle.
NOTE: If the control valve enters into an error state during regeneration
mode, the MAV will return to the open position, if not already there.
1.0T Valve
With 1.0T set, a display will allow the user to set the amount of pre-service
rinse time for the stand by tank just prior to returning to service. Set to
oFF to deactivate this feature.
Step 6CS – Fill Units: If set as a softener, if Step 2CS is set to 1.5, and FILL is part of the Regeneration Cycle Sequence, FILL UNITS of MIN or LBS can be selected. Press NEXT to exit OEM Configuration Setup. Press REGEN to return to previous step.
Step 1S – Press NEXT and simultaneously for 5 seconds and release. If
screen in Step 2S does not appear, the lock on valve programming has been
activated. To unlock press , NEXT, , REGEN in sequence, then press NEXT and
simultaneously for 5 seconds and release.
Step 2S – Choose SOFTENING using or . Press NEXT to go to Step 3S.
Press REGEN to exit OEM Softener System Setup..
Step 3S – Choose Brining Direction using or . This screen is not viewed when Step 2S is set to Filtering. Press NEXT to go to Step 4S. Press REGEN to return to previous step.
Step 4S – Set Refill location using or :
- “PoST” to refill the brine tank after the final rinse; or
- “PrE” to refill the brine tank four hours before the regeneration time set.
This screen is not viewed when Step 2S is set to Filtering.
Press NEXT to go to Step 5S. Press REGEN to return to previous step.
Step 5S – Select the time for the first cycle using or . For valve
types 1.5 and 2.0, “oFF” is also available.
Press NEXT to go to Step 6S. Press REGEN to return to previous step.
Step 6S – Select the time for the second cycle using or . For valve
types 1.5 and 2.0, “oFF” is also available.
NOTE: The display will alternate between the time and brine direction (UP
or dn).
Press NEXT to go to Step 7S. Press REGEN to return to previous step.
Step 7S – Select the time for the third cycle using or . For valve
types 1.5 and 2.0, “oFF” is also available.
Press NEXT to go to Step 8S. Press REGEN to return to previous step.
Step 8S – Select the time for the fourth cycle using or . For valve
types 1.5 and 2.0, “oFF” is also available.
Press NEXT to go to Step 9S. Press REGEN to return to previous step.
Step 9S – Select the pounds for the fifth cycle using or . For valve
types 1.5 and 2.0, “oFF” is also available.
NOTE: if Step 2CS is set to 2.0 or Step 6CS is set to MIN, Fill will be
in minutes.
Press NEXT to go to Step 10S. Press REGEN to return to previous step.
Step 10S – Set System Capacity using or . The System Capacity setting
should be based on the volume of resin and LBS of salt fill set in Step 9S.
Press NEXT to go to Step 11S. Press REGEN to return to previous step.
Step 11S – Set Volume Capacity using or . If value is set to:
- “AUTO” capacity will be automatically calculated and reserve capacity will be automatically estimated;
- “oFF” regeneration will be triggered by the day override setting, or can be set to regenerate on specific days of the week.
- a number, regeneration will be triggered by the value specified (in Gallons).
If “oFF” or a volume is used, the hardness display will not be allowed to be set in Installer Display Settings Step 2I. See Setting Options Table for more detail. Press NEXT to go to Step 12S. Press REGEN to return to previous step.
Step 12S – Set Regeneration Time Options using or . NOTE: This step
will not appear if Step 11S is set to oFF or Step 5CS is set to “SYS”.
If value is set to:
- “NORMAL” means regeneration will occur at the preset time;
- “on 0” means regeneration will occur immediately when the volume capacity reaches 0 (zero); or
- “NORMAL + on 0” means regeneration will occur at one of the following:
- the preset time when the volume capacity falls below the reserve or the specified number of days between regenerations is reached whichever comes first; or
- immediately after 10 minutes of no water usage when the volume capacity reaches 0 (zero).
“on 0” is the default if Step 2CS is set to 1.0T , and “NORMAL + on 0” is not available.
See Setting Options Table for more detail. Press NEXT to exit Softener System Setup. Press REGEN to return to previous step.
Setting Options Table1
System Type| Regeneration Option| Regeneration Type| Day
Override|
---|---|---|---|---
Softening
| ****
Auto
| ****
Delayed
| ****
1-28 days
| Regeneration occurs at the next regeneration time when volume capacity falls
below the reserve capacity, or the specified number of days is reached,
whichever comes first.
Softening| Auto| Delayed| OFF| Regeneration occurs at the next regeneration
time when volume capacity falls below the reserve capacity.
Softening or Filtering| 20 – 1,500,000
Gallons
| ****
Delayed
| ****
1-28 days
| Regeneration occurs at the next regeneration time when volume capacity
reaches 0, or the specified number of days is reached, whichever comes first.
Softening or Filtering| 20 – 1,500,000
Gallons
| Delayed| OFF| Regeneration occurs at the next regeneration time when volume
capacity reaches 0.
Softening or Filtering| ****
OFF
| ****
Delayed
| ****
1-28 days
| Time Clock operation.
Regeneration occurs at the next regeneration time the
specified number of days is reached.
Softening
| Auto or
20 – 1,500,000
Gallons
| ****
Immediate
| ****
1-28 days
| Regeneration occurs immediately when volume capacity reaches 0, or the
specified number of days is reached, whichever comes first.
Softening or Filtering| 20-1,500,000
Gallons
| Immediate| OFF| Regeneration occurs immediately when volume capacity reaches 0.
Softening
| ****
Auto
| ****
Delay + Immediate
| ****
1-28 days
| Regeneration occurs at the next regeneration time when volume capacity falls below the reserve capacity, or the specified number of days is reached, or regeneration occurs after 10 minutes of no water usage when volume capacity reaches 0.
Softening or Filtering
| ****
20 – 1,500,000
Gallons
| ****
Delay + Immediate
| ****
1-28 days
| Regeneration occurs at the next regeneration time the specified number of days is reached or regeneration occurs after 10 minutes of no water usage when volume capacity reaches 0.
Softening
| ****
Auto
| ****
Delay + Immediate
| ****
OFF
| Regeneration occurs at the next regeneration time when volume capacity falls below the reserve capacity, or regeneration occurs after 10 minutes of no water usage when volume capacity reaches 0.
1 Reserve Capacity estimate is based on history of water usage. Reserve Capacity estimate is not available with Twin Tank Valve.
OEM Filter System Setup
Cycle Sequence, Adjustable Default Times (minutes)
Type| Backwash| Draw| Backwash| Rinse| Backwash| Fill
Filtering Backwash| 8| | | 4| |
Filtering Regen| 8| 60| 8| 8| 0:30| .95 GAL
Filtering Regen (2.0”)| 8| 60| 8| 8| 0:30| 6
Cycle is non-adjustable, not shown in cycle sequence programming.
Step 1F – Press NEXT and simultaneously for 5 seconds and release. If screen
in Step 2CS does not appear, the lock on the valve is activated. To unlock
press , NEXT, , REGEN in sequence, then press NEXT and simultaneously for
5 seconds and release.
Step 2F – Choose FILTERING BACKWASH or FILTERING REGEN (see table) using or
. Press NEXT to go to Step 3F. Press REGEN to exit OEM Filter System Setup.
Step 3F – Select the time for the first cycle using or .
Press NEXT to go to Step 4F. Press REGEN to return to previous step
Step 4F – Select the time for the second cycle using or .
If Step 2F is set to FILTERING REGEN, press NEXT to program the rest of the
cycle times. If Step 2F is set to FILTERING BACKWASH, press NEXT to go to Step
5F. Press REGEN to return to previous step.
Step 5F – Set Regeneration trigger using or . If value is set to:
- “oFF” regeneration will be triggered by the day override setting or can be set to regenerate on specific days of the week.
- a number, regeneration will be triggered by the value specified (in gallons).
See Setting Options Table for more detail.
Press NEXT to go to Step 6F. Press REGEN to return to previous step.
Step 6F – Set Regeneration Time Options using or . NOTE: This step will not
appear if Step 5F is set to oFF.
If value is set to:
- “NORMAL” means regeneration will occur at the preset time;
- “on 0” means regeneration will occur immediately when the volume capacity reaches 0 (zero); or
- “NORMAL + on 0” means regeneration will occur at one of the following:
- the preset time when the volume capacity falls below the reserve or the specified number of days between regenerations is reached whichever comes first; or
- immediately after 10 minutes of no water usage when the volume capacity reaches 0 (zero).
“on 0” is the default if Step 2CS is set to 1.0T , and “NORMAL + on 0” is not available.
See Setting Options Table for more detail. Press NEXT to exit Filter System Setup. Press REGEN to return to previous step.
Installer Display Settings
Step 1I – To enter Installer Display press NEXT and simultaneously for about
5 seconds and release.
Step 2I – Hardness: Set the amount of influent hardness using or . This
display will not be viewed if FILTERING BACKWASH or FILTERING REGEN is
selected in Step 2F or if “oFF” or a number was selected in Step 11S.
Press NEXT to go to step 3I. Press REGEN to exit Installer Display Settings.
Step 3I – Day Override: When volume capacity is set to “oFF”, sets the number
of days between regenerations. When volume capacity is set to AUTO or to a
volume, sets the maximum number of days between regenerations. If value set to
“oFF”, regeneration initiation is triggered solely by volume used. If value is
set in days (allowable range from 1 to 28) regeneration initiation will be
called for on that day regardless of actual water usage. Set Day Override
using or :
- number of days between regeneration (1 to 28); or
- “oFF”.
See Setting Options Table for more detail on setup.
Press NEXT to go to step 4I. Press REGEN to return to previous step.
Step 4I – Next Regeneration Time (hour): Set the hour of day for regeneration
using or . The default time is 2:00. This display will show “REGEN on 0
GAL” if “on 0” is selected in Set Regeneration Time Option in OEM Softener
System Setup or OEM Filter System Setup.
Press NEXT to go to step 5I. Press REGEN to return to previous step.
Step 5I – Next Regeneration Time (minutes): Set the minutes of day for
regeneration using or . This display will not be shown if “on 0” is
selected in Set Regeneration Time Option in OEM Softener System Setup or OEM
Filter System Setup.
Press NEXT to exit Installer Display Settings. Press REGEN to return to
previous step.
Diagnostics
Step 1D – Press and simultaneously
for 5 seconds and release. If screen in Step 2D does not appear the lock on
the valve is activated. To unlock press , NEXT, , REGEN in sequence, then
press and simultaneously for 5 seconds and release.
Step 2D – Software Version. Press NEXT to go to Step 3D. Press REGEN to exit
Diagnostics.
Step 3D – Volume, total used since start-up: This display shows the total
gallons treated since startup. This display will equal zero if a water meter
is not installed. Press the NEXT button to go to Step 4D. Press REGEN to
return to previous step.
Step 4D – Days, total since start-up: This display shows the total days since
startup. Press the NEXT button to go to Step 5D. Press REGEN to return to
previous step.
Step 5D – Regenerations, total number since start-up: This display shows the
total number of regenerations that have occurred since startup. Press the NEXT
button to go to Step 6D. Press REGEN to return to previous step.
Step 6D –Step 6D – Error Log: This display shows a history of the last 10
errors generated by the control Error Log: This display shows a history of the
last 10 errors generated by the control during operation. Press during
operation. Press or or to view each recorded error. to view each
recorded error.
Press NEXT to go to Step 7D. Press REGEN to return to previous step.Press NEXT
to go to Step 7D. Press REGEN to return to previous step.
Step 7D – Days, since last regeneration: This display shows the days since the
last regeneration occurred. Press NEXT to go to Step 8D. Press REGEN to return
to previous step.
Step 8D – Volume, since last regeneration: This display shows the volume of
water that has been treated since the last regeneration. This display will
equal zero when a water meter is not installed. Press NEXT to go to Step 9D.
Press REGEN to return to previous step.
Step 9D – Volume, reserve capacity used for last 7 days: If the valve is
set up as a softener, a meter is installed, and Set Volume Capacity is set to
“Auto,” this display shows day 0 (for today) and flashes the reserve capacity.
Pressing will show day 1 (which would be yesterday) and flashes the reserve
capacity used. Pressing again will show day 2 (the day before yesterday) and
the reserve capacity. Keep pressing to show the capacity for days 3, 4, 5
and 6. can be pressed to move backwards in the day series. This display does
not appear if 1.0 is set in Step 2CS, if ALT A or ALT B are selected in Step
5CS, or anytime the reserve capacity is not determined by the control.
Press NEXT at any time to go to Step 10D. Press REGEN to return to previous
step.
Step 10D – Volume, 63-day usage history: This display shows day 0 (for
today) and flashes the volume of water treated today. Pressing will show day
1 (which would be yesterday) and flashes the volume of water treated on that
day. Continue to press to show the maximum volume of water treated for the
last 63 days. If a regeneration occurred on the day the word “REGEN” will also
be displayed. This display will show dashes if a water meter is not installed.
Press NEXT at any time to go to Step 11D. Press REGEN to return to previous
step.
Step 11D – Twin Tank Valve transfer history: only displays when 1.0 was
selected in Step 2CS. Use or to scroll through the last 10 tank transfers.
The first position in the display ranges from 0 to 9 with the lowest number
being the most recent transfer. The second position in the display will be
either “A” or “b”. If “A” then the tank with the valve on it was in service,
if “b” the tank with the in/out head on it was in service. The next three
digits represent the number of hours ago that the transfer occurred. The
display alternates with the volume that was treated before the tank
transferred. Press NEXT at any time to go to Step 12D. Press REGEN to return
to previous step.
Step 12D – MAV Drive History in the direction of retracted piston rod
position. Display will only be shown if 1.0 is selected in Step 2CS, or OFF is
not selected in Step 5CS. Up to a four digit number will appear after the “L”
which stands for latest and “A” which stands for average. Drive time is
measured in 1/100 of a second; i.e., a 17.10 second move is displayed as
“1710”. Press NEXT at any time to go to Step 13D. Press REGEN to return to
previous step.
Press and hold and buttons for 3 seconds while in Step 12D to reset the
MAV drive history in both the retracted and extended piston rod position. To
view the old MAV drive history data for retracted and extended rod position
press and hold REGEN and while in Step 12D. Press NEXT to advance display to
the old MAV drive history.
Step 13D – MAV Drive History in the direction of extended piston rod
position. Display will only be shown if 1.0 is selected in Step 2CS, or OFF is
not selected in Step 4CS. Up to a four digit number
will appear after the “L” which stands for latest and “A” which stands for
average. Drive time is measured in 1/100 of a second; i.e., a 17.15 second
move is displayed as “1715”. Press and hold and for 3 seconds while in
Step 13D to reset the MAV drive history in both the extended and retracted
piston rod position. To view the old MAV drive history data see Step 12D.
Press NEXT at any time exit Diagnostics. Press REGEN to return to previous
step.
Battery Diagnostics
Step 1BD – Press and
simultaneously for 5 seconds and release. Press and simultaneously for 5
seconds and release. If screen in Step 2BD does not appear the lock on the
valve is activated. To unlock press , NEXT, , REGEN in sequence, then press
and simultaneously for 5 seconds (twice) and release.
Step 2BD – Battery Pack Status – Pack Voltage. Displays the daily
measured voltage of the battery pack under load. Press and hold and to
initiate an immediate test of the battery pack .
Press NEXT to go to Step 2BD. Press REGEN to exit Battery Diagnostics.
Step 3BD – Battery Pack Status – Charge Current. Displays the current
measured charge current (in mA) of the control solar panel or AC wall adapter.
A flashing SET indicates that the control is currently determining whether to
activate the charging circuit. A flashing FILL indicates that the charging
circuit is currently activated. Pressing will temporarily turn on the
charging circuit. Pressing will temporarily turn off the charging circuit.
Press NEXT to go to Step 4BD. Press REGEN to return to previous step.
Step 4BD – Battery Pack Charge History. Displays the measure mAhr charge
of the battery pack over the past 63 days. REGEN in the second display
indicates that a regeneration occurred on that day.
Press NEXT to exit Battery Diagnostics. Press REGEN to return to previous
step.
Revision History:
4/3/2020
MAJOR UPDATE – NEW DISPLAYS AND OPERATION
5/8/2020
COVER
Added – Solar Powered
10/27/2020.
PAGE 4:
Modified labels on #4 drawing
Charger Water Treatment Products