Beghelli Formula 65 LED CT GL LED Emergency Light Instruction Manual
- June 12, 2024
- Beghelli
Table of Contents
Beghelli Formula 65 LED CT GL LED Emergency Light
INFO
Features
Dimension
Basic setting (1h-3h) without using App
Wiring with Infinity mode deactivated
- For the functioning please refer to the instruction manuals either of the Central CableCom Connect cod. 201517
- For the Central configuration the batteries must be sufficiently charged.
- Be careful NOT to invert the phase and neutral polarity. Maximum connectable lamps 32.
- Do not connect other types of devices on the power cable / BUS L + N-.
Wiring with Infinity mode activated
- Wiring 2.1 The appliance goes into emergency conditions for absence of general emergency electricity (CableCom); absence of a local lighting
- Wiring 2.2 The appliance goes into emergency conditions in the absence of general emergency electricity (CableCom).
Caution:
- SA luminaires can be set SE only through the App (with smartphone flash on the lamp or with wi-fi with Central CableCom Connect).
- With Infinity mode on N2 L2 must be connected like wiring 2.1 or 2.2.
BATTERY INSTALLATION
- For autonomy management refer to the table
- With Infinity mode activated and lamp wired as scheme 2.1 the autonomy is infinite with Cablecom network present (N-L+)
Expansion with LG
available option
CONFIGURATION AND COMMANDS| AT (without APP and without Central)| AT + APP| AT **+ CENTRALE CABLECOM CONNECT (cod. 20151)
- APP
---|---|---|---
CONFIGURAZIONI – CONFIGURATION| Autonomia- Duration 1h| • Default| • Default| • Default
Autonomia- Duration 1,5h| | •| •
Autonomia- Duration 2h| | •| •
Autonomia- Duration 3h| • con jumper| •| •
Autonomia- Duration 8h| | •| •
Maintained (only on Maintained Luminaire)| | •| •
Setting even odd AT| • Preset by the ID of the QR code. Cannot be modified| •| •
Test duration 1h or autonomy set| Test duration 1h| •| •
Settaggio Infinity mode / Setting Infinity mode| • Infinity mode disabled by default| | •
Rest Mode| | | •
Manufacturer data reset| | •| •
COMANDI E FUNZIONI –**| Start/Stop Functional Test| | •| •
Stop duration Test| | | •
Sync automatic Test| | •| With a configurable delayed start
Scheduling automatic Test| | | With change periodicity
Remotizzazione error Failure report from a remote place| | | • By LED on Central; the APP indicates which lamp is in error
Luminaire tracking| | | •
Type of luminaire identification| | | •
LOGBOOK| | | •
Use App B.connect
- A- Open App B.connect (available for download on the App Store and Google Play).
- B- The configuration of the lamp can be accessed through the “luminaire” menu.
LAMP RESPONSE:
- 1 high brightness flash= function performed
- 5 low light flashes= function NOT enabled
- No flashing= command NOT received
- N.B. With CableCom Connect control unit cod 20151 all configurations and commands can be sent remotely via the “nuBe” cloud.
- POSITION LAMP FOR COVER ENSURE THE PROGRAM (eg. a lot of light – less distance)
AUTOMATIC TESTS PERIODICITY:
- FUNCTIONAL TEST (30 sec)= every 28 days
- AUTONOMY TEST (1h)= every 26 weeks
- Even lamps carry out the autonomy test 1 week after the odd lamps.(0,2,…,8,A,C,E)= even; (1,3,…,9,B,D,F)= odd.
LED SIGNALS
- FIXED GREEN BATTERY CHARGED
- FLASHING GREEN BATTERY CHARGING
- ONE RED FLASH BATTERY ERROR DURATION
- TWO RED FLASHES LIGHTING LED ERROR
- THREE RED FLASHES BATTERY DISCONNECTED
- OPENING THE COMMUNICATION FROM APP: Remove and reset the network for less than 3 seconds.
- The communication remains possible for 2 hours and for 1 min the LED flashes orange to signal the communication opening.
- The Functional Test and the Functional STOP Test are controlled by the B.Connect App at any time without having to open communication with the device.
WARNINGS – GUARANTEE
- This device shall be used exclusively for the purpose for which it has been designed. Any other use is considered improper and the therefore dangerous.
- Rechargeable battery and LED source are non-replaceable type.
- Contact an authorised technical service centre for any repairs possibly required use only original spare parts.
- The lacked respect of the above conditions may compromise the safety of the device.
- Caution: electric shock
- www.beghelli.com
Documents / Resources
|
Beghelli Formula 65 LED CT GL LED Emergency
Light
[pdf] Instruction Manual
334900784, 334.902.191, Formula 65 LED CT GL, LED Emergency Light, Formula 65
LED CT GL LED Emergency Light, Emergency Light, Light
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>