Beghelli Formula 65 LED CT GL LED Emergency Light Instruction Manual

June 12, 2024
Beghelli

Beghelli Formula 65 LED CT GL LED Emergency Light

Beghelli-Formula-65-LED-CT-GL-LED-Emergency-Light-
PRODUCT

INFO

www.beghelli.com

Features

Beghelli-Formula-65-LED-CT-GL-LED-Emergency-Light-
FIG-2

Dimension

Beghelli-Formula-65-LED-CT-GL-LED-Emergency-Light-
FIG-3 Beghelli-Formula-65-LED-CT-GL-LED-
Emergency-Light-FIG-4

Basic setting (1h-3h) without using App

Beghelli-Formula-65-LED-CT-GL-
LED-Emergency-Light-FIG-6

Wiring with Infinity mode deactivated

  • For the functioning please refer to the instruction manuals either of the Central CableCom Connect cod. 201517
  • For the Central configuration the batteries must be sufficiently charged.
  • Be careful NOT to invert the phase and neutral polarity. Maximum connectable lamps 32.
  • Do not connect other types of devices on the power cable / BUS L + N-.

Wiring with Infinity mode activatedBeghelli-Formula-65-LED-CT-GL-LED-
Emergency-Light-FIG-8

  • Wiring 2.1 The appliance goes into emergency conditions for absence of general emergency electricity (CableCom); absence of a local lighting
  • Wiring 2.2 The appliance goes into emergency conditions in the absence of general emergency electricity (CableCom).

Caution:

  • SA luminaires can be set SE only through the App (with smartphone flash on the lamp or with wi-fi with Central CableCom Connect).
  • With Infinity mode on N2 L2 must be connected like wiring 2.1 or 2.2.

BATTERY INSTALLATION

Beghelli-Formula-65-LED-CT-GL-LED-Emergency-Light-
FIG-9

  • For autonomy management refer to the table
    • With Infinity mode activated and lamp wired as scheme 2.1 the autonomy is infinite with Cablecom network present (N-L+)Beghelli-Formula-65-LED-CT-GL-LED-Emergency-Light-FIG-10

Expansion with LG

Beghelli-Formula-65-LED-CT-GL-LED-Emergency-Light-
FIG-11

available option

CONFIGURATION AND COMMANDS| AT (without APP and without Central)| AT + APP| AT **+ CENTRALE CABLECOM CONNECT (cod. 20151)

  • APP
    ---|---|---|---
    CONFIGURAZIONI – CONFIGURATION| Autonomia- Duration 1h| • Default| • Default| • Default
    Autonomia- Duration 1,5h|  | •| •
    Autonomia- Duration 2h|  | •| •
    Autonomia- Duration 3h| • con jumper| •| •
    Autonomia- Duration 8h|  | •| •
    Maintained (only on Maintained Luminaire)|  | •| •
    Setting even odd AT| • Preset by the ID of the QR code. Cannot be modified| •| •
    Test duration 1h or autonomy set| Test duration 1h| •| •
    Settaggio Infinity mode / Setting Infinity mode| • Infinity mode disabled by default|  | •
    Rest Mode|  |  | •
    Manufacturer data reset|  | •| •
    COMANDI E FUNZIONI –**| Start/Stop Functional Test|  | •| •
    Stop duration Test|  |  | •
    Sync automatic Test|  | •| With a configurable delayed start
    Scheduling automatic Test|  |  | With change periodicity
    Remotizzazione error Failure report from a remote place|  |  | • By LED on Central; the APP indicates which lamp is in error
    Luminaire tracking|  |  | •
    Type of luminaire identification|  |  | •
    LOGBOOK|  |  | •

Use App B.connect

  • A- Open App B.connect (available for download on the App Store and Google Play).
  • B- The configuration of the lamp can be accessed through the “luminaire” menu.

LAMP RESPONSE:

  • 1 high brightness flash= function performed
  • 5 low light flashes= function NOT enabled
  • No flashing= command NOT received
  • N.B. With CableCom Connect control unit cod 20151 all configurations and commands can be sent remotely via the “nuBe” cloud.
  • POSITION LAMP FOR COVER ENSURE THE PROGRAM (eg. a lot of light – less distance)

AUTOMATIC TESTS PERIODICITY:

  • FUNCTIONAL TEST (30 sec)= every 28 days
  • AUTONOMY TEST (1h)= every 26 weeks
  • Even lamps carry out the autonomy test 1 week after the odd lamps.(0,2,…,8,A,C,E)= even; (1,3,…,9,B,D,F)= odd.

LED SIGNALS

  • FIXED GREEN BATTERY CHARGED
    • FLASHING GREEN BATTERY CHARGING
  • ONE RED FLASH BATTERY ERROR DURATION
    • TWO RED FLASHES LIGHTING LED ERROR
  • THREE RED FLASHES BATTERY DISCONNECTED
  • OPENING THE COMMUNICATION FROM APP: Remove and reset the network for less than 3 seconds.
  • The communication remains possible for 2 hours and for 1 min the LED flashes orange to signal the communication opening.
  • The Functional Test and the Functional STOP Test are controlled by the B.Connect App at any time without having to open communication with the device.

WARNINGS – GUARANTEE

  • This device shall be used exclusively for the purpose for which it has been designed. Any other use is considered improper and the therefore dangerous.
  • Rechargeable battery and LED source are non-replaceable type.
  • Contact an authorised technical service centre for any repairs possibly required use only original spare parts.
  • The lacked respect of the above conditions may compromise the safety of the device.
  • Caution: electric shock
  • www.beghelli.com

Documents / Resources

| Beghelli Formula 65 LED CT GL LED Emergency Light [pdf] Instruction Manual
334900784, 334.902.191, Formula 65 LED CT GL, LED Emergency Light, Formula 65 LED CT GL LED Emergency Light, Emergency Light, Light
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>