Beghelli LG230 Infinita LED X5 Instruction Manual
- June 3, 2024
- Beghelli
Table of Contents
Beghelli LG230 Infinita LED X5
Infinita LED X5 LG230
www.beghelli.com
BEGHELLI S.p.A. – ITALY – Tel. +39 051 9660411 – Fax +39 051 9660444 – N°
Verde 800 626626
Sostituzione lente – Lens replacement
EMERGENCY LUMINAIRE FOR EXIT SIGNS AND ESCAPE ROUTES
The luminaire allows a centralised switching as well as dia-gnostic functions.
The luminaire is equipped with a rotary switch for manual addressing (Fig.
F1). Alternatively the addressing can be done automatically over the central
by read-in of the ID (Fig. F2).
(Fig. G) WIRING DIAGRAM:
- Consider mains connections (L/+; N/-) and polarity.
- Connections of the LSSA input: L; N (voltage 198 V to 254 V~) (Fig. G1-G2).
The light flux in normal operation and emergency operation is the same, except of deviating performance of the control gear.
OPERATION WITH LOCAL LSSA COMMAND:
(Fig. G1) For a function as local light switch, put DIP switch “LSSA” to “ON”
and DIP switch “UV” to “LS-T” – the devi-ce will be switched on in normal
operation with present voltage on the local input.
(Fig. G2) For a function as local sub-distribution monito-ring, put DIP switch
“LSSA” to “ON” and DIP switch “UV” to “LS-F” – the device will be switched on
in emergency operation with absent voltage on the local input.
(Fig. G2) For a function as local inverted light switch, put DIP switch “LSSA”
to “ON” and DIP switch “UV” to “LS-F” – the device will be switched on in
normal mode with absent vol-tage on the local input. To activate this function
consult the operating manual of the central.
The device must be programmed to non-maintained mode over the central.
OPERATION WITHOUT LOCAL LSSA COMMAND:
(Fig. G3) Put DIP switch in position “OFF”. The device will be switched by the programming on the central.
CALIBRATION OF THE CONNECTION LOAD:
Factory-set DIP switch.
If the illuminant is defective the current consumption of the control gear
must be smaller than “WFAIL”.
CODING
- Addresses: from 1 to 16: (Fig. F1).
- Addresses: from 17 to 32: (Fig. F1).
WARNINGS – GUARANTEE
- This device shall be used exclusively for the purpose for which it has been designed. Any other use is considered improper and therefore dangerous.
- Contact an authorized technical service Centre for repairs possibly required use only original spare parts. The lacked respect of the above conditions may compromise the safety of the device.
- For details regarding warranty services, contact an authorized dealer.
- Risk Group 0 to 300 cm
- Caution: electric shock