Beghelli 334900784 Stile In Led 10L Wall Mounted Ceiling Emergency Light Instruction Manual
- May 15, 2024
- Beghelli
Table of Contents
COMPLETA LED AT
Instruction Manual
334900784 Stile In Led 10L Wall Mounted Ceiling Emergency Light
For further information and updates, scan the QR code on the product 334.902.244C
| 230V
50Hz| COS q)| LED| |
---|---|---|---|---|---
4210 | 180mA| 0.047| 24 LED| LiFe 3,2V 0,5Ah| 1h 1,5h 2h 3h 8h
4211 | 180mA| 0.047| 24 LED| LiFe 3,2V 1,5Ah
4212 | 180mA| 0.047| 24 LED| 2x LiFe 3,2V 1,5Ah
4213 | 180mA| 0.095| 24 LED| LiFe 3,2V 1,5Ah
4214 | 180mA| 0.095| 24 LED| 2x LiFe 3,2V 1,5Ah
- For autonomy management refer to the table
*The selection of autonomy from the App has priority over cutting the jumper on the circuit.
By setting “Factory reset” on the App you go back to the setting made on the circuit (1-3h).
• available option
| Local action on a single device
---|---
CONFIGURATION AND COMMANDS| without APP| • Default
CONFIGURATION| Duration 1h| • Default| •
Duration 1,5h| | •
Duration 2h| | •
Duration 3h| • con jumper| •
Duration 8h| | •
Settaggio SE/SA (solo su lampade SA)
Setting Non-maintained/Maintained (only on Maintained Luminaire)| | •
Setting even/odd AT| • Preset by ID of QR code. Cannot be modified| •
Test duration 1h or autonomy set| • Test duration 1h| •
Manufacturer data reset| | •
COMMANDS AND FUNCTIONS| Start/Stop functional Test| | con APP
Sync automatic Test| | •
Use with App B.connect
A- Open App B.connect (available for download on the App Store and Google
Play).
B- The “luminaire” menu is used to access the settings: Autonomy time, Mode,
Even/odd, Test duration, Sync luminaire, Factory reset. Using the icon:
Test emergency: functional Test; stop Test
LAMP RESPONSE:
1 high brightness flash= function performed
5 low light flashes= function NOT enabled
No flashing= command NOT received
POSITION LAMP FOR COVER ENSURE THE PROGRAM (eg. a lot of light – less
distance) OPTIONAL: to put the appliance in “rest mode”, use the accessory
cod. 15048 and the Inibit remote control (code 2730).
AUTOMATIC TESTS PERIODICITY:
FUNCTIONAL TEST (30 sec)= every 28 days
AUTONOMY TEST (1h)= every 26 weeks
Even lamps carry out the autonomy test 1 week after the odd lamps.
(0,2,…,8,A,C,E)= even; (1,3,…,9,B,D,F)= odd.
LED SIGNALS
FIXED GREEN | BATTERY CHARGED |
---|---|
FLASHING GREEN | BATTERY CHARGING |
ONE RED FLASH | BATTERY ERROR DURATION |
TWO RED FLASHES | LIGHTING LED ERROR |
THREE RED FLASHES | BATTERY DISCONNECTED |
OPENING THE COMMUNICATION FROM APP:
Remove and reset the network for less than 3 seconds.
The communication remains possible for 2 hours and for 1 min the LED flashes
orange to signal the communication opening.
The Functional Test and the Functional STOP Test are controlled by the
B.Connect App at any time without having to open communication with the
device.
WARNINGS – GUARANTEE
– This device shall be used exclusively for the purpose for which it has been
designed. Any other use is con- sidered improper and therefore dangerous.
– Rechargeable battery and LED source are non-replaceable type. Contact an
authorised technical service centre for any repairs possibly required use only
original spare parts.
The lacked respect of the above conditions may compromise the safety of the
device.
* Caution:** electric shock
www.beghelli.com
BEGHELLI S.p.A
Via Mozzeghine 13/15
località Monteveglio 40053 Valsamoggia (BO) ITALY
Tel. +39 051 9660411
Fax +39 051 9660444
N° Verde 800 626626
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>