Beghelli Pluraluce Extreme Extreme LED Emergency Instruction Manual

June 4, 2024
Beghelli

Lungalargaluce Extreme LED AT Opticom
Instruction Manual

www.beghelli.com

|
---|---
6m installation on the work surface| 6m installation on the work surface| 6m installation on the work surface
---|---|---

2m installation on the work surface| 2m installation on the work surface
---|---

Beghelli Pluraluce Extreme Extreme LED Emergency - 7| Beghelli Pluraluce Extreme Extreme LED Emergency -
8
---|---

Attention:
For the use of the device in ATEX environments, it is essential to apply the ATEX-certified cable gland supplied

Beghelli Pluraluce Extreme Extreme LED Emergency - 9

Setting at the date of purchase

Opticom

Setting at the date of purchase
+ moduli LG – LG FM – DALI (cod. 15036 – 15047 – 15038)
LG – LG FM – DALI

To activate the functions use the relative module and consult the manual
LG LG FM DALI

Opticom function activation:
A*- Remove the jumper from the circuit to enable Opticom functions and proceed to program the lamp as shown in the App tutorial.
B- Open App Opticom technology (available for download on the App Store and Google Play). The list of smartphones compatible with the App is available on option.beghelli.it
C- Make login with user and password (at the first use you must register as a new user).
POSITION LAMP FOR COVER ENSURE THE PROGRAM (eg. a lot of light – less distance)

4- LED status:

STEADY RED Opticom NOT working – Battery disconnected
ORANGE FIXED Opticom enabled – Configuration NOT complete – Lock code NOT

included
ORANGE FLASHING| Communication Opticom active (time window about 3 minutes)

LG – LG FM – DALI

Beghelli Pluraluce Extreme Extreme LED Emergency - 12

It is important to stick these labels as follows:
1 -the little label should be positioned on the plant drawing for easy tracing of the luminaire (picture B); 2 -the medium and large labels should be positioned on the luminaire where the radio device is mounted in a way to be visible when the luminaire is installed (picture B1).
Install the radio circuit far from surfaces capable of creating radio jamming (metal surfaces, etc).
AUTOMATIC TESTS PERIODICITY:
FUNCTIONAL TEST (30 sec)= every 28 days
AUTONOMY TEST (1h)= every 26 weeks
Even lamps carry out the autonomy test 1 week after the odd lamps. (0,2,…,8,A,C,E)= even; (1,3,…,9,B,D,F)= odd.
LED SIGNALS

STEADY RED| OPTICOM NOT WORKING (battery disconnected – LED Module Disconnected)
---|---
ORANGE FLASHING| OPTICOM ENABLED – Configuration NOT complete – lock code NOT included
ORANGE FIXED| COMMUNICATION OPTICOM ACTIVE
GREEN FIXED| BATTERY CHARGED
FLASHING GREEN| BATTERY CHARGING
ONE RED FLASH| ERROR BATTERY/IES

IMPORTANT:
Installation must be carried out by qualified personnel in accordance with
EN60079-17 and following the indications of Standard EN60079-14.

ATEX APPLICATIONS

GAS ENVIRONMENTS:

  • ZONE 2
  • GROUP II PRODUCT (may only be installed above ground)
  • CATEGORY: 3G (with GAS and normal explosion risk level)
  • PROTECTION METHOD: Ex nA (non-sparking equipment)
  • GAS GROUP: IIB
  • TEMPERATURE CLASS: T4 (135°C) – Maximum internal and external sur- face temperature of the main components at an atmospheric temperature of 40°C.

DUST ENVIRONMENTS:

  • ZONE 22
  • GROUP II PRODUCT (may only be installed above ground)
  • CATEGORY: 3D (with DUST and normal explosion risk level)
  • PROTECTION METHOD: Ex tc (electrical equipment protected by casing)
  • SECURITY LEVEL: IIIC (IP6x)
  • TEMPERATURE CLASS: T80 (80°C) – Maximum surface temperature of the main components at an atmospheric temperature of 40°C.

CONDITIONS FOR SAFE USE:

  • Operating temperature range: 0÷40°C
    X Do not open when energized.
    X Clean the outside of the product using a damp cloth, in order to avoid electric shocks.

  • Disconnect the device from the mains before starting to clean or service it.

  • Tighten the head fixing screw with a torque of 0.6Nm to install the product in ATEX classified areas.

  • The device is NOT equipped with a terminal for an equipotential connection.

Beghelli S.p.A. declares that the products Lungalargaluce Extreme LED are classified “II 3G Ex nA IIB T4 Gc” and “II 3D Ex tc IIIC T80°C Dc” and comply with the requisites of Directives 2014/34/UE (ATEX) and 2014/30/UE (EMC).
STANDARDS:
CEO EN 60079-0: 2018
CEI EN 60079-15: 2010
CEO EN 60079-31: 2014
CEO EN 55015: 2013
CEO EN 61000-3-2: 2014
CEO EN 61000-3-3: 2013
CEO EN 61547: 2009
WARNINGS – GUARANTEE

  • This device shall be used exclusively for the purpose for which it has been designed. Any other use is considered improper and therefore dangerous.
  • Rechargeable batteries and LED sources are non-replaceable types.
  • Contact an authorized technical service center for any repairs possibly required to use only original spare parts. The lacked respect of for the above conditions may compromise the safety of the device.

BEGHELLI S.p.A.
Via Mozzeghine 13/15
località Monteveglio 40053 Valsamoggia (BO) ITALY

Tel. +39 051 9660411
Fax +39 051 9660444
N° Verde 800 626626
www.beghelli.com

ta -20÷45°C 230V-50Hz
IK09 IP65

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Beghelli User Manuals

Related Manuals