INSTALLATION

INSTALLATION
INSTALLATION
INSTALLATION
INSTALLATION
INSTALLATION

AUTOMATIC TESTS PERIODICITY:

FUNCTIONAL TEST (30 sec)= every 28 daysAUTONOMY TEST (1h)= every 26 weeks

Even lamps carry out the autonomy test 1 week after the odd lamps. (0,2,…,8,A,C,E)= even; (1,3,…,9,B,D,F)= odd. To perform the functions shown on the diagrams turn on and off the power when the red LED is lit.

LED SIGNALS

FIXED GREEN: BATTERY CHARGED
FLASHING GREEN: BATTERY CHARGING
ONE RED FLASH: BATTERY ERROR DURATION