Beghelli Rti X5 LG 230 Infinita LED Luminaires Instruction Manual
infinita LED Rti X5 LG 230
EMERGENCY LUMINAIRE FOR EXIT SIGNS
AND ESCAPE ROUTES
The luminaire allows a centralised switching as well as dia- gnostic
functions.
The luminaire is equipped with a rotary switch for manual addressing (Fig.
F1). Alternatively the addressing can be done automatically over the central
by read-in of the ID (Fig. F2).
(Fig. G) WIRING DIAGRAM:
-
Consider mains connections (L/+; N/-) and polarity.
-
Connections of the LSSA input: L; N (voltage 198 V to 254 V~) (Fig. G1-G2).
The light flux in normal operation and emergency operation is the same, except of deviating performance of the control gear.
OPERATION WITH LOCAL LSSA COMMAND:
(Fig. G1) For a function as local light switch, put DIP switch “LSSA” to “ON”
and DIP switch “UV” to “LS-T” – the devi- ce will be switched on in normal
operation with present voltage on the local input. (Fig. G2) For a function as
local sub-distribution monito- ring, put DIP switch “LSSA” to “ON” and DIP
switch “UV” to “LS-F” – the device will be switched on in emergency ope-
ration with absent voltage on the local input. (Fig. G2) For a function as
local inverted light switch, put DIP switch “LSSA” to “ON” and DIP switch “UV”
to “LS-F” – the device will be switched on in normal mode with absent vol-
tage on the local input. To activate this function consult the operating
manual of the central.
The device must be programmed to non-maintained mode over the central.
OPERATION WITHOUT LOCAL LSSA COMMAND:
(Fig. G3) Put DIP switch in position “OFF”. The device will be switched by the programming on the central.
CALIBRATION OF THE CONNECTION LOAD:
Factory-set DIP switch.
If the illuminant is defective the current consumption of the control gear
must be smaller than “WFAIL” (Fig. D).
CODING
Addresses: from 1 to 16: (Fig. F1). Addresses: from 17 to 32: (Fig. F1).
WARNINGS – GUARANTEE
- This device shall be used exclusively for the purpose for which it has been Any other use is considered improper and therefore dangerous.
- Contact an authorised technical service centre for repairs possibly required use only original spare parts. The lacked respect of the above conditions may compromise the safety of the
- For details regarding warranty services, contact an autho- rized