ENCELIUM DALI HF LS LI Luminaire Integrated Light and Presence Sensor and DALI Coupler Instruction Manual

September 29, 2024
ENCELIUM

ENCELIUM DALI HF LS LI Luminaire Integrated Light and Presence Sensor and

DALI Coupler

OVERVIEW

The DALI HF LS LI is a High-Frequency Light Sensing Luminaire Integrated Sensor and Coupler designed to incorporate light and presence sensing control of your DALI luminaire into the Encelium X Lighting Control System. For more information on product specifications and design tools visit encelium.com

PRODUCT SAFETY

READ THESE INSTRUCTIONS BEFORE USING THE PRODUCT
When using electrical equipment, basic safety precautions should always be followed, including the following:

  • Do not mount near gas or electric heaters or let power supply cords touch hot surfaces.
  • Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
  • The use of accessory equipment is not recommended by Encelium as it may cause an unsafe condition.
  • All DALI channels are internally connected together to the control unit. Make sure to consider this when installing.
  • Do not use this equipment for other than the intended use.

WIRED SYSTEM OVERVIEW

Encelium X enables you to control DALI devices. With any Encelium wired design, you get a reliable, lighting control system that can be installed quickly and easily.

STEP 1

The DALI HF LS LI Coupler is intended for luminaire integration which enables the luminaire to be controlled wirelessly and the Sensor is designed specifically for luminaire integration and requires direct connection to the DALI HF LS LI Coupler. Secure the DALI HF LS LI Coupler and the HF LS LI Sensor to the luminaire using screws (not included). Make sure they are mounted close enough so the included sensor cable can be connected. The DALI HF LS LI is to be installed in dry, indoor locations ONLY. Recommended input voltage is 220 to 240 V, 50/60 Hz. Maximum of 300 m (984 ft) total wire length for DALI and third-party sensor interface.

Note : Once the DALI HF LS LI Coupler is connected to power, press the SELECT button to switch on the LED Indicator. Another short press to the SELECT button will switch off the LED Indicator, otherwise the LED Indicator will switch off after 30 seconds.
Proceed to Step 2 if you are not using Luminaire Integration.

STEP 2
INDEPENDENT CEILING INTEGRATION (OPTIONAL)

Independent Ceiling Integration is possible with installation of the ECO CI KIT (ordered separately), a strain relief housing kit. The DALI HF LS LI Coupler requires the installation of an ECO CI KIT to ensure protection from electrical contact. The DALI HF LS LI Coupler is to be installed in dry, indoor locations ONLY. Recommended input voltage is 220 to 240 V, 50/60 Hz. Maximum of 300 m (984 ft) total wire length for DALI and third-party sensor interface.
Note : Once the DALI HF LS LI Coupler is connected to power, press the SELECT button to switch on the LED Indicator. Another short press to the SELECT button will switch off the LED Indicator, otherwise the LED Indicator will switch off after 30 seconds.

Proceed to DALI HF LS LI Coupler Features if you are not using Independent Ceiling Integration.

STEP 3
INDEPENDENT CEILING INTEGRATION

Remove cable guards from the ECO CI KIT bases and place ECO CI KIT bases onto the DALI HF LS LI Coupler. Push the center of the cable guard down and bend, enabling the cable guard to wrap around the cable.

STEP 4

Install the cable guards on the LINE IN, DALI, and SENSOR cables then connect the wires into the DALI HF LS LI Coupler ports. Place the ECO CI KIT covers onto the DALI HF LS LI Coupler and tighten the screws. Connect the HF LS LI Sensor via the 4-pol RJ10 socket (4P4C) marked as ‘Sensor’ on the housing top. Only one HF LS LI Sensor should be connected to the DALI HF LS LI Coupler.

DALI LS LI COUPLER FEATURES

DALI HF LS LI Coupler features a SELECT Button and LED Indicator. The SELECT Button enables you to identify a device and reset to factory default settings. The LED Indicator displays green or red lights (see the DALI HF LS LI Coupler LED Indicator details below).

DALI HF LS LI Coupler LED Indicator Lights

  • Green LED Indicator Flashes: Indicates motion detection.
  • Red LED Indicator: Indicates a user has entered OSRAM proprietary mode.

HF LS LI SENSOR FEATURES

HF LS LI Sensor features a Light Sensor and an LED Indicator that displays green or red light (see the HF LS LI Sensor LED Indicator details below).

HF LS LI Sensor LED Indicator Lights

  • Green LED Indicator Flashes: Motion is detected.
  • Green LED Indicator Illuminates Continuously: Motion detection is temporarily deactivated.
  • Red LED Indicator Flashes 3 Times: IR Signal of remote control has been received.
  • Red LED Indicator Flashes 1 Time: Vibration has been detected.
  • Red LED Indicator Illuminates Continuously: 100h burn-in is active.

FACTORY DEFAULT SETTINGS

With the power connected to the DALI HF LS LI, press and hold the SELECT Button for about 10 seconds until the LED Indicator blinks red for 4 seconds. The DALI HF LS LI is then reset to the factory default settings.
Note : Resetting to factory default settings will delete the DALI short address and require the device to be re-commissioned.

SENSOR DETECTION RANGE
The detection range of the HF LS LI Sensor must be set before it can detect motion.

Sensor Detection Range

© Copyright 2024 Legrand All Rights Reserved.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>