APC JGNY-B4Q6G4 EN Smart-UPS SRT 192V 5kVA and 6kVA RM Battery Pack Instruction Manual

June 9, 2024
APC

APC JGNY-B4Q6G4 EN Smart-UPS SRT 192V 5kVA and 6kVA RM Battery Pack

Important Safety Instructions

  • This Safety Guide contains important instructions that should be followed during the installation and maintenance of the APCTM by Schneider Electric equipment.
  • It is intended for APC by Schneider Electric customers who set up, install, relocate, or maintain APC by Schneider Electric equipment. Refer to the product manual for more information.
  • Read, understand, and follow ALL safety instructions contained in this guide. Failure to follow safety instructions and warnings could result in equipment damage, serious injury, or death.
  • Changes and modifications to this unit not expressly approved by Schneider Electric IT Corporation could void the warranty.
Product Handling Guidelines

APC-JGNY-B4Q6G4-EN-Smart-UPS-SRT-192V-5kVA-and-6kVA-RM-Battery-Pack-
fig-1

  • Do not work alone under hazardous conditions.
  • The equipment is intended for indoor use only.
  • Do not operate the unit in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
  • Be sure the air vents on the UPS are not blocked.
  • Allow adequate space for proper ventilation.
  • The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
  • Always install UPS at the bottom in rack-mount configurations.
  • Always install peripheral equipment above the UPS in rack-mount configurations.
Electrical safety
  • Adhere to all national and local electrical codes.
  • Do not handle any metallic connector before the power has been disconnected.
  • For models with a hardwired input, the connection to the branch circuit (mains) must be performed by a qualified electrician.
  • 230 V models only: In order to maintain compliance with the EMC directive for products sold in Europe, output cords attached to the UPS must not exceed 10 meters in length.
  • The protective earth conductor for the UPS carries the leakage current from the load devices (computer equipment). An insulated ground conductor is to be installed as part of the branch circuit that supplies the UPS. The conductor must have the same size and insulation material as the grounded and ungrounded branch circuit supply conductors. The conductor will typically be green, with or without a yellow stripe.
  • Leakage current for a pluggable, Type A UPS may exceed 3.5 mA when a separate ground terminal is used.
  • The UPS input ground conductor must be properly bonded to the protective earth at the service panel.
  • If the UPS input power is supplied by a separately derived system, the ground conductor must be properly bonded at the supply transformer or motor generator set.
Deenergizing safety
  • The UPS may present a shock hazard even when disconnected from AC and DC power.
  • The AC and DC connectors may be energized by remote or automatic control at any time.
  • Before installing or servicing the equipment check that the:
    • The equipment is disconnected from the AC source.
    • Internal batteries are disconnected.

Battery Safety

  • Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
  • The battery typically lasts for five to ten years. Environmental factors impact battery life. Elevated ambient temperatures, poor-quality utility power, and frequent short-duration discharges will shorten battery life.
  • Replace the UPS immediately if the unit indicates battery replacement is necessary.
  • Replace the UPS once the batteries have reached the end of their service life even if the UPS has not indicated that battery replacement is necessary.
  • The batteries may be user replaceable. Under normal operating conditions, there is no need for replacement. If attempting to replace batteries,
    • Use only APC by Schneider Electric battery modules.
    • Do not use third-party batteries as replacements.
    • Replace with the same number and type of batteries as originally installed in the equipment.
  • APC by Schneider Electric uses Lithium Ion batteries. Under normal use and handling, there is no contact with the internal components of the battery.
  • Do not drive nails into the battery pack.
  • Do not strike the battery pack with a hammer.
  • Do not stand on the battery pack.
  • Do not short-circuit the battery pack.
  • Do not place or use the battery pack near heat or fire.
  • Do not use a dropped, damaged, or deformed battery pack.
  • Do not use the battery pack to power other equipment.
  • CAUTION: A battery can present a risk of electric shock and burns by high short-circuit current. The following precautions should be observed when working on batteries:
    • Disconnect the charging source prior to connecting or disconnecting battery terminals.
    • Do not wear any metal objects including watches and rings.
    • Do not lay tools or metal parts on top of batteries.
    • Use tools with insulated handles.
    • Wear rubber gloves and boots.
    • Determine if the battery is either intentionally or inadvertently grounded. Contact with any part of a grounded battery can result in electric shock and burns by high short-circuit current. The risk of such hazards can be reduced if grounds are removed during installation and maintenance by a skilled person.
  • CAUTION: Before installing or replacing the batteries, remove conductive jewelry such as chains, wristwatches, and rings. High energy through conductive materials could cause severe burns.
  • CAUTION: Do not dispose of the battery packs in a fire. The batteries may explode.
  • CAUTION: Do not open or tamper with the battery enclosure. Doing so will expose the cell terminals which pose an energy hazard.
  • CAUTION: Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
  • CAUTION: Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.

General information

  • The model and serial numbers are located on a small, rear panel label. For some models, an additional label is located on the chassis under the front bezel.
  • Always recycle used batteries.
  • Recycle the packing materials or save them for reuse.

© 2022 APC by Schneider Electric. APC and the APC logo are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are the property of their respective owners.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

APC User Manuals

Related Manuals