legrand DPX3 630 S10 Power Circuit Breaker Instruction Manual
- October 30, 2023
- Legrand
Table of Contents
- legrand DPX3 630 S10 Power Circuit Breaker
- Product Information
- Product Usage Instructions
- Product Parts
- BATTERIES INSERTION
- PARAMETRAGE DES PROTECTIONS
- PARAMETRAGE PAR BOUTONS
- SERVICE SIGNALS
- SETTINGS BY USB
- DISPLAY BACKLIGHT
- INDICATIONS LED
- DESCRIPTION OF EMBEDDED MEASUREMENT FUNCTIONS
- Safety instructions
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
legrand DPX3 630 S10 Power Circuit Breaker
Product Information
The DPX3 630 S10 (LE12999AA) is a device that provides protection status indication, navigation, setting, mechanical trip, and battery compartment for power supply. It has a display LCD, mini USB port (type B), logic selectivity port, and serial communication port RS485/EMS and auxiliary power supply. The device uses 2 CR1616 3V batteries (4 210 82) and has the capability to add a low battery report. It also complies with the EU directive 2006/66 CE on batteries, accumulators, and relative wastes.
Product Usage Instructions
- Insert the 2 CR1616 3V batteries into the battery compartment.
- Press the navigation button (2) to navigate through the device options.
- Use the setting button (3) to change the device settings.
- Press the mechanical trip button (4) to perform a mechanical trip test.
- If there is a low battery, the device will add a report.
- At the end of the device’s life cycle, recycle the included batteries according to the EU directive 2006/66 CE.
Product Parts
- Indications led for protection status
- Navigation button
- Setting button
- Mechanical trip button
- Battery compartment
- Display LCD
- Mini USB port (type B)
- Logic selectivity port (4 210 78)
- Serial communication port RS485/EMS and auxiliary power supply (4 210 75 – 4 238 90 – 4 210 83)
BATTERIES INSERTION
If battery powered the display switch off after 10 s if not used.
In case of low battery it add this report
At the end of life cycle, process the included batteries according to the EU directive 2006/66 CE about the batteries, accumulators and relative wastes.
PARAMETRAGE DES PROTECTIONS
Factory settings
r| tr| MemT| sd| tsd| i| g| tg| N
1ln| 3s| OFF| 10Ir| 400ms (t=k)| OFF| 1ln| 80ms| 100%
PARAMETRAGE PAR BOUTONS
- Isd=xln if Ir=OFF
- 50% not possible if Ir<0,4% In or Ir=OFF
- 150% not possible if Ir>66,7% In or Ir=OFF
- 200% not possible if Ir>50% In or Ir=OFF
For additional functions, as diagnostic test, advanced protection setting,
intervention curve visualization and report download, it’s necessary connect
via USB with PC
(download software Power Control Station from e-catalog) or with dongle-key
bluetooth (0 283 10).
SERVICE SIGNALS
It appears every time you change a threshold for intervention. The writing is flashing and disappears after 4s last time you pressed a button control (+ / -).
It appears every time you store a new threshold for intervention.
Setting and navigation possible.
Only navigation possible. The mechanical seal on transparent cover does not prevent the setting by Software/app.
SETTINGS BY USB
- Isd=xln if Ir=OFF
- 50% not possible if Ir<0,4% In or Ir=OFF
- 150% not possible if Ir>66,7% In or Ir=OFF
- 200% not possible if Ir>50% In or Ir=OFF
The protections could be enabled by Software PCS (refer to the user guide). Once the parameters have been set, password is required.
- A further setting it’s allowed only by SW or app using the password.
Protection unit trip test
DISPLAY BACKLIGHT
In service – Self-feeding with TA
Out of service – Power supply with battery
With external power supply USB (PC, dongle, powerbank)
DESCRIPTIONS OF PROTECTIONS AND ADDITIONAL FUNCTIONS RELATED TO THE PROTECTION UNIT SUPPLY STATUS. IN CASE OF SELF-SUPPLY, ALL PROTECTION FUNCTIONS ARE ACTIVE EVEN IF THE GREEN LED IS OFF.
- Thermal memory
- Logic selectivity
- Active function
- Function in stand-by if I<35%In, activates for higher currents
INDICATIONS LED
Led Bicolore
Signal – Indication : Event : Priority
-
LED : Setting in process :1
-
LED rouge clignotante :I > 1,05 Ir : 2
-
Red led on : I > 0,9 Ir: 3
-
Green and Red alternately blinking : T > 90°C:4
-
Green led on: Protection unit switched on:5
If more events were at the same time, the signal would be the one with highest priority. The highest priority is 1.
DESCRIPTION OF EMBEDDED MEASUREMENT FUNCTIONS
I1 I2 I3 | A | Current phase L1 / L2 / L3 |
---|---|---|
IN (4P) | A | Current of neutral |
IG | A | Earth fault current |
U12 U23 U31 (3P) | V | Phase to Phase Voltage |
V1N V2N V3N (4P) | V | Phase voltages |
Freq | Hz | Frequency |
PTot | kW | Three-phase active power (Ptot>0 if A → B) by default (you can |
reset the direction via sw) /
QTot| kvar| Three-phase reactive power
PF| | Power Factor
Ep| kWh| Energie Active A→ B
Ep| kWh| Energie Active B → A
Eq| kvar h| Reactive Energy A → B
Eq| kvar h| Reactive Energy A → B
THDU12 THDU23 (3P) THDU31|
%
|
Chained Voltage THD
THDV1N THDV2N (4P) THDV3N|
%
| THD Phase Voltages
THDI THDI2 THDI3 THDIN| %| Current THD
| A – °C| Cause of the last intervention and its value. (Tst indicates that
the last intervention took place for Diagnostic test)
PMD Characteristics
Type of characteristic| Ejemplo de posible valor característico Esempio possibili valori della caratteristica Valor do recurso
| Other complementary characteristics
Classification of PMD according to 4.3| PMD-x (*)| –
Classification of PMD according to 4.4| DD|
Temperature| K 55| –
Altitude Humidity| Conditions standard Standard conditions|
–
Active power or active energy function (if function available) performance class
| 1| –
Characteristics of functions
Function symbols| Function performance class according to IEC 61557-12
(2013-11) )| Measurement range| Other complementary
characteristics
DPX 3 630A| I max PMD
In| | 250A| 320A| 400A| 500A| 630A| 250A|
320A| 400A| 500A| 630A
P| 2| 0.3kW
360kW
| 0.3kW
460kW
| 0.3kW
580kW
| 0.3kW
720kW
| 0.3kW
900kW
| 300A| 380A| 480A| 600A| 750A
Ib=250A, Un=400V, fn=50Hz
Q V| 2| 0.6kvar 360kvar| 0.6kvar 460kvar| 0.6kvar 580kvar| 0.6kvar
720kvar| 0.6kvar 900kvar| 300A| 380A| 480A| 600A| 750A
Ib=250A, Un=400V, fn=50Hz
S A| –| –| –
E a| 2| 0…9999 GW/h| 300A| 380A| 480A| 600A| 750A
Ib=250A, Un=400V, fn=50Hz
E rV| 2| 0…9999 Gvar/h| 300A| 380A| 480A| 600A| 750A
Ib=250A, Un=400V, fn=50Hz
E apA , E apV| –| –| –
f| 0.02| 50…60 Hz| –
I| 2| 12.5A
300A
| 12.5A
380A
| 12.5A
480A
| 12.5A
600A
| 12.5A
750A
| 300A| 380A| 480A| 600A| 750A
Ib=250A, Un=400V, fn=50Hz
I N| 2| 12.5A
300A
| 12.5A
380A
| 12.5A
480A
| 12.5A
600A
| 12.5A
750A
| 300A| 380A| 480A| 600A| 750A
Ib=250A, Un=400V, fn=50Hz
U(3P), V(4P)| 0.5| 88…690V| –
P FA| 0.5| | 300A| 380A| 480A| 600A| 750A
Ib=250A, Un=400V, fn=50Hz
P st| –| –| –
P lt| –| –| –
U dip , V dip| –| –| –
U swl , V swl| –| –| –
U tr , V tr| –| –| –
U int , V int| –| –| –
U nba , V nba| –| –| –
U nb| –| –| –
U h , V h| –| –| –
THD u (3P), THD v (4P)| 5| 110…690V| –
THD-R u (3P), THD-R v (4P)| –| –| –
I h| –| –| –
THD i| 5| 250A 250A 250A 250A 250A
250A 320A 400A 500A 630A| –
THD-R i| –| –| –
Safety instructions
This product should be installed in compliance with installation rules, preferably by a qualified electrician. Incorrect installation and use can lead to risk of electric shock or fire. Before carrying out the installation, read the instructions and take account of the product’s specific mounting location. Do not open up, dismantle, alter or modify the device except where specifically required to do so by the instructions. All Legrand products must be opened and repaired exclusively by personnel trained and approved by Legrand. Any unauthorized opening or repair completely cancels all liabilities and the rights to replacement and guarantees. Use only Legrand brand accessories.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>