DESCRIPTION
Wattstopper’s UT-300 Series Ultrasonic Ceiling Sensors automatically turn
lighting on and off based on occupancy.
The sensors mount on the ceiling with a flat, unobtrusiveappearance and
provides 360° coverage.
OPERATION
UT-300 Series Sensors operate on 24 VDC, VAC or halfwave rectified. They use 40 kHz high frequency ultrasound to sense occupancy and automatically turn lighting on. When no occupancy is detected for the length of the time delay, lighting automatically turns off. For manual-on operation, the units work with a low-voltage momentary switch.
TIME DELAY OPTIONS
The UT-300 is factory set for a 20 minute time delay, ideal for both energy
savings and user satisfaction in most applications.
Installers can quickly select other fixed time delays (5, 10, 15 or 30
minutes) via DIP switches. Fixed time delays eliminate the occupant
dissatisfaction associated with an automatically adjusted time delay option,
and reduce callbacks. Walk-through mode may be enabled for added energy
savings in spaces with frequent transient traffic.
APPLICATIONS
UT-300 Series Sensors offer excellent control of lighting for many spaces, including restrooms, large offices, open office areas and hallways. They can control large partitioned office spaces when configured in zone patterns. Unit performance combined with ease of installation will provide fast payback and many years of energy savings.
FEATURES
-
Advanced control logic based on RISC micro-controller provides:
– Advanced Signal Processing eliminates false triggers and provides immunity to RFI and EMI
– Walk-through mode turns lights off three minutes after the area is initially occupied – ideal for brief visits such as mail delivery -
LED indicates occupancy detection
-
Coverage 500-2,000 square feet
-
Available with isolated relay for integration with BAS or HVAC
-
DIP switch simplifies sensor adjustments
-
Patented ultrasonic diffusion technology spreads coverage to a wider area
-
UT-300 Series Sensors work with low-voltage momentary switches for manual control
-
Clip mounting system makes ceiling tile installation simple
-
Uses plug terminal wiring system for quick and easy installation
-
BAA/TAA-compliant models available
-
Sensor coverage tested to NEMA Guide Publication WD 7-2000
SPECIFICATIONS
- 24 VDC/VAC
- Time delays: 5, 10, 15, 20 or 30 minutes, Walk-through/ Test Modes
- Sensitivity adjustment: variable with trimpot
- Ultrasonic frequency: 40 kHz
- UT-300 contains isolated relay with N/O and N/C outputs; rated for 1 Amp at 30 VDC/VAC
- Mounting options: ceiling tile; 4” square junction box with double-gang mud ring
- Max. UT-300s per BZ power pack: 5 Max. UT-305s per BZ power pack: 5
- Dimensions: 4.5” x 1” (114.3mm x 25.9mm) diameter x depth
- UL and cUL listed
- Five year warranty
WIRING & MOUNTING
CONTROLS & SETTINGS
Product Controls
Feature| Switch#| |
---|---|---|---
Time Delay| 1| 2| 3
Test Mode/20 min| | |
30 seconds| | |
5 minutes| | |
10 minutes| | |
15 minutes| | |
20 minutes| | |
25 minutes| | |
30 minutes| | |
Walk-Through| 4
---|---
Enabled|
Disabled|
Service| 5
---|---
Service|
Normal|
= Factory Setting
= ON
= OFF
COVERAGE & PLACEMENT
Coverage Patterns
Coverages shown represent half-step walking motion when sensor is mounted 8’-10’ high. Actual coverage can vary for each application depending on the shape and use of space and the obstacles present.
Placement
Typical layout for open office space would be to place UT-300-3 sensors so they control zones that overlap. For partitioned spaces, a typical zone is about 25’ x 25’ with an overlap on the coverage up to 30’ x 30’.
ORDERING INFORMATION
Catalog # | Voltage | Current | Coverage | Features |
---|---|---|---|---|
UT-300-1 | 24VDC/VAC | 40 mA | 2 up to 500 ft 2 (46.5 m | Isolated relay |
UT-300-1-U | ||||
UT-300-2 | 24VDC/VAC | 40 mA | 2 up to 1000 ft 2 (92.9 m | Isolated relay |
UT-300-2-U | ||||
UT-300-3 | 24VDC/VAC | 45 mA | 2 up to 2000 ft 2 (185.8 m | Isolated relay |
UT-300-3-U | ||||
UT-305-1 | 24VDC/VAC | 30 mA | 2 up to 500 ft 2 (46.5 m | |
UT-305-2 | 24VDC/VAC | 30 mA | 2 up to 1000 ft 2 (92.9 m | |
UT-305-3 | 24VDC/VAC | 35 mA | 2 up to 2000 ft 2 (185.8 m |
All units are white and use Wattstopper power packs. Current consumption can
be slightly higher when only one sensor per power pack is used.
-U = BAA/TAA compliant; product is compliant with Buy American Act and Trade Agreement Act
27334r2 Rev 08/2021
WWW.LEGRAND.US/WATTSTOPPER
designed to be better.
Documents / Resources
|
legrand UT-300 SERIES Ultrasonic Low Voltage Ceiling
Sensors
[pdf] Owner's Manual
UT-300 SERIES, Ultrasonic Low Voltage Ceiling Sensors, UT-300 SERIES
Ultrasonic Low Voltage Ceiling Sensors, Low Voltage Ceiling Sensors, Voltage
Ceiling Sensors, Ceiling Sensors, Sensors
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>