Q-TRAN QOMS 60W-750W AC Power Supply Installation Guide

June 10, 2024
Q-TRAN

Q-TRAN logo1

INSTALLATION            QOMS/QOMD


QOMS 60W-750W
1 CONTROL ZONE

Q-TRAN QOMS 60W-750W AC Power Supply a2

  1. Front View

  2. Bottom View

  3. PRIMARY
    Line Voltage

  4. Land Ground

  5. Land Hot

  6. Land Neutral

  7. Chose either tap 1 (switch) or 2 (dimmer; long primary run or low input voltage (115V or less))

  8. *Must test all voltage readings with a True RMS Voltage Meter when controlled by a dimmer. Do not exceed secondary voltage!

  9. SECONDARY
    Low Voltage

  10. If 12V Taps are
    12V, 13V, 14V, 15V

  11. *Up to 5 Sec. Breakers can be used

  12. BKR    COLOR     12V     24V

    5 A       Orange     60w    120w
    10 A     Red          120w    240w
    12.5 A  Yellow      150w    300w
    15 A    Yellow      180w    360w
    20 A    Blue         240w    480w
    25 A    Purple      300w    600w

  13. Step 1.
    Connect line side or “hot” side of the low voltage connection.
    Start with position # 1.
    Step 2.
    Connect common side to one of the low voltage terminal blocks.

  • Repeat step 1 & 2 for every new lead connection. 14. L.V. Secondary feeds go to a 85 AMP rated terminal block. Each terminal is UL listed to have the following capacity:
    6        #14
    4        #12
    4        #10
    2        #8

    1. *For longer runs you may need to go to a higher tap & or larger wire gauge on secondary side.
QOMD 60W-300W
2 CONTROL ZONES

Q-TRAN QOMS 60W-750W AC Power Supply a4

  1. Front View

  2. Bottom View

  3. PRIMARY
    Line Voltage

  4. Land Ground

  5. Land Hot

  6. Land Neutral

  7. Chose either tap 1 (switch) or 2 (dimmer; long primary run or low input voltage (115V or less))

  8. *Must test all voltage readings with a True RMS Voltage Meter when controlled by a dimmer. Do not exceed secondary voltage!

  9. SECONDARY
    Low Voltage

  10. If 12V Taps are
    12V, 13V, 14V, 15V

  11. *Up to 5 Sec. Breakers can be used

  12. BKR    COLOR     12V     24V

    5 A       Orange     60w    120w
    10 A     Red          120w    240w
    12.5 A  Yellow      150w    300w
    15 A    Yellow      180w    360w
    20 A    Blue         240w    480w
    25 A    Purple      300w    600w

  13. Step 1.
    Connect line side or “hot” side of the low voltage connection.
    Start with position # 1.
    Step 2.
    Connect common side to one of the low voltage terminal blocks.

  • Repeat step 1 & 2 for every new lead connection. 14. L.V. Secondary feeds go to a 85 AMP rated terminal block. Each terminal is UL listed to have the following capacity:
    6        #14
    4        #12
    4        #10
    2        #8

    1. *For longer runs you may need to go to a higher tap & or larger wire gauge on secondary side.
Wiring Diagram

120V (60Hz) – 12/24V

PRIMARY                                         SECONDARY
120VAC                                                  12 VAC

Q-TRAN QOMS 60W-750W AC Power Supply a5

*( ) CONNECT TO ANY TAP**

– USE SECONDARY TERMINAL BLOCKS FOR LOAD CONNECTIONS
– DASHED LINES INDICATE ELECTRICAL CONTRACTOR WIRING
– MULTIPLE LOADS CAN BE CONNECTED TO THE SAME OR DIFFERENT TAPS, DEPENDING ON DESIRED OUTPUT VOLTAGE, TO COMPENSATE FOR VARYING LOAD DISTANCES.


230V (50Hz) – 12/24V-CE
277V (60Hz) – 12/24V

PRIMARY                                         SECONDARY
230/277VAC                                              12 VAC

Q-TRAN QOMS 60W-750W AC Power Supply a6

*( )CONNECT TO ANY TAP**

– USE SECONDARY TERMINAL BLOCKS FOR LOAD CONNECTIONS
– DASHED LINES INDICATE ELECTRICAL CONTRACTOR WIRING
– MULTIPLE LOADS CAN BE CONNECTED TO THE SAME OR DIFFERENT TAPS, DEPENDING ON DESIRED OUTPUT VOLTAGE, TO COMPENSATE FOR VARYING LOAD DISTANCES.

Selecting the Right Tap

Q-TRAN QOMS 60W-750W AC Power Supply a7

Conclusion:
With a simple field adjustment, the contractor was able to recover his voltage drop and light output by switching from Tap 12 to Tap 15.

A 12V Lamp Operating at 10V = 50 % Light Output!

Rating|

Excellent

| Good| Poor| Bad| Very Bad
---|---|---|---|---|---

Light Output

| | | | |
Lamp Volts|

24.0V

| 22.8V| 21.6V| 20.4V|

19.2V

Voltage Drop|

0%

| -5%| -10%| -15%|

-20%

Lamp Volts|

12.0V

| 11.4V| 10.8V| 10.2V|

9.6V

Light Output| | | | |

Rating

| Excellent| Good| Poor| Bad|

Very Bad

The Impact of Voltage Drop on Light Output

Q-TRAN QOMS 60W-750W AC Power Supply a18

Q-TRAN QOMS 60W-750W AC Power Supply a19

Q-TRAN QOMS 60W-750W AC Power Supply a20

Q-TRAN QOMS 60W-750W AC Power Supply a21

Q-TRAN QOMS 60W-750W AC Power Supply a22

*For longer runs you may need to go to a higher tap & or larger wire gauge on secondary side.


* Use a True RMS Volt Meter when a dimmer is used.
(RMS = Root Mean Squared)

  1. The “line side” of the load is connected to secondary circuit breakers.
    [4 AMP – 25 AMP]
Warnings

WARNING

FOR CONDUIT CONNECTION
RISK OF ELECTRIC SHOCK.
Install power unit 5 feet (1.5 m) or more from the pool or spa and 10 feet (3.05 m) or more from a fountain. Where the power unit is installed within 10 feet (3.05 m) of a pool or spa, connect unit to GFCI protected branch circuit.

FOR POWER SUPPLY CORD CONNECTION
RISK OF ELECTRIC SHOCK.
Install power unit 5 feet (1.5 m) or more from the pool, spa, or fountain. Where the power unit is installed (a) indoors within 10 feet (3.05 m) of a pool, spa, or fountain or (b) outdoors, connect power unit to a receptacle protected by a GFCI.

RISK OF FIRE. If installation requires running wire through a building structure, special wiring methods are needed. Contact a qualified electrician.

OUTDOOR CORD – connected unit shall be connected to a GFCI protected hooded flush type cover plate recepticle marked “Wet Location.

DO NOT USE EXTENSION CHORDS.

The main Secondary Wiring is intended for shallow burial – less than 6 inches (152 mm) For Supply connections use wire rated for at least 60C.

  • To order additional lengths of wire for connection in the secondary, contact your local distributor or Q-Tran at 203-367-8777 and inquire about Q-Wire.

LISTEDUL Listed symbol 123              5F78

LOW VOLTAGE LIGHTING POWER SUPPLY CENTER

  • LANDSCAPE LIGHTING POWER UNIT
  • SUITABLE FOR WET LOCATION
  • SUITABLE FOR INDOOR/OUTDOOR USE
  • UL 1838 & 2108 LISTED
  • ISOLATION TOROIDAL TRANSFORMER
  • USE DIMMERS RATED FOR MAGNETIC LOW VOLTAGE LOADS
  • 50/60 CYCLE
  • MADE IN THE U.S.A.

For model series:

QOM-60, QOM-100, QOM-150, QOM-300, QOM-500, QOM-600, QOM-750, QOM-2X150, QOM- 2X300 and QOM-150/300, all field installed conductors, both primary and secondary, shall have insulation suitable for the highest voltage potential of the equipment.

WIRE TYPE

| PRI. WIRE COLOR
---|---
HOT
NEU (TAP 1)
NEU (TAP 2)
GROUND|

BLACK
RED
ORANGE
GREEN

BREAKER

| MINIMUM AWG| 12V
---|---|---
5A
10A
15A
20A
25A| 14
14
14
12
10|

60W
120W
180W
240W
300W

| QOM| Q-TRAN QOMS 60W-750W AC Power Supply a24| Q-TRAN QOMS 60W-750W AC Power Supply a24| Q-TRAN QOMS 60W-750W AC Power Supply a24| Q-TRAN QOMS 60W-750W AC Power Supply a24| Q-TRAN QOMS 60W-750W AC Power Supply a24
---|---|---|---|---|---|---
|

Model

| Input Voltage
(V)| Input Current
(A)| Frequency| Nominal Output Voltage
(VDC)|

Max Output Wattage
(W)

| QOM-60
QOM-60X2
QOM-60/100
QOM-60/150
QOM-60/300
QOM-100
QOM-100X2
QOM-100/150
QOM-100/300
QOM-150
QOM-150X2
QOM-150/300
QOM-300
QOM-300X2
QOM-500
QOM-600
QOM-750| 120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277
120 / 277| .56 / .25
1.12 / .49
1.48 / .64
1.93 / .84
3.28 / 1.42
.92 / .40
1.84 / .80
2.29 / .99
3.64 / 1.58
1.37 / .59
2.74 / 1.19
4.09 / 1.77
2.72 / 1.18
5.44 / 2.36
4.48 / 1.94
5.32 / 2.30
6.58 / 2.85| 50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60| 12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24
12/24| 60
60X2
60/100
60/150
60/300
100
100X2
100/150
100/300
150
150X2
150/300
300
300X2
500
600
750
CAUTION: USE ONLY WITH MAXIMUM OUTPUT LOAD PER ABOVE TABLE. This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved.

  • SUITABLE FOR USE WITH SUBMERSIBLE LUMINAIRES OR SUBMERSIBLE PUMPS
  • SUITABLE FOR WET LOCATIONS
  • WALL MOUNT ONLY
  • FOR SUPPLY CONNECTIONS USE WIRE RATED FOR AT LEAST 60 C.
  • SUITABLE FOR INDOOR OR OUTDOOR USE
  • SUITABLE FOR MOUNTING WITHIN 1.2m (4 ft.) OF THE GROUND
  • ISOLATION TOROIDAL TRANSFORMER
  • DIMMER, IF USED, MUST BE A MAGNETIC LOW-VOLTAGE DIMMER.
  • 50/60 CYCLE A.C. ONLY
  • MADE IN THE U.S.A.
  • KEEP ENCLOSURE COVER CLOSED
  • READ INSTALLATION INSTRUCTIONS BEFORE WIRING

LOW VOLTAGE LUMINAIRE POWER SUPPLY CENTER

QOM Series tested to:
UL-2108, UL-1838
CSA C22.2 NO. 250.0-08
CSA C22.2 NO. 250.7-07

CLASS:
120V
3425 01

CLASS:
120V/277V
3425 81
3425 15
3425 95

WARNING: RISK OF FIRE. IF INSTALLATION INVOLVES RUNNING WIRE THROUGH A BUILDING STRUCTURE, SPECIAL WIRING METHODS ARE NEEDED. CONSULT A QUALIFIED ELECTRICIAN.