Chapter 1 System overview
1. Model description
System Model
MINI
MINI: mini system, high Power density
Rectifier Model 30120
30: Power, Unit is hundred, that is 3000W
120: Output voltage 120Vdc
Monitor Model
M30
M: Monitor
30: match with 30120 module etc.
2. System structure
The system configuration is flexible. All the functional modules are easy to
embed into the system.
3.
System Feature
MINI embedded DC power systems advanced modular design makes the whole system
are small, but it can provide enough power to meet the requirements of
communication systems, consistent with the characteristics of the rack-
mounted. The system is suitable for all sizes of exchange room, base stations,
satellite communications, data communications, railways and power systems.
MINI DC power system is easy to operate, install and maintain. Module subrack
adopts inset-box installation for flexible expansion capacity and replacement
controller.
Features:
-
With active power factor compensation technology power factor of rectifier is up to 0.99
-
Standard height 2U,the weight of each module is 2.6kg and output current is Max 20A , with high power density.
★ Rectifier modules adopted soft switch technology. When load rate is 10%, efficiency can be 91%; 50% load rate ,the efficiency can be above 95% -
Complete battery protection and load disconnect management. It has LVD function, which maximizes to protect battery.
-
Rectifier and monitor modules adopt hot swap technology, Plug and play;
-
Standard RS232 communication interface; 3-class alarm dry contact: Emergency alarm, main alarm and minor alarm.
-
Complete fault protection, alarm function;
-
Low radicalization: Advanced EMC rectifier design can meet the communication power rectifier equipment electromagnetic compatibility limits and measurement methods in the PRC telecommunications industry and standard YD/T983 conducted and radiated interference requirements.
-
System configuration is flexible and easy to expand; N +1 redundant power supply. It can be configured according to customer demand;
★ Products have passed the inspection of the Ministry of Information Industry Quality Supervision and Inspection Center.
Chapter 2 Rectifier Modules
1. Introduction
Our rectifier modules adopt pure resonant soft-switching technology and Plug
and play.
Each module is equipped with advanced microprocessors. On the front panel,
each rectifier modules has 3 Led indicators: power supply indicator,
communication indicator and failure indicator.
Indicators | Normal state | Abnormal states | Reasons |
---|---|---|---|
Power supply Indicators | On | Off | No AC input or input fuse is damaged |
Communication Indicators | Off | Twinkling | Communication fail |
Failure Indicators | Off | On | There is a damage inside the module |
2.Functions:
●Soft switch
Rectifier power circuit is divided into active PFC and DC to DC converter
which can make the wide input voltage range (75V-300V) and high efficiency
(above 97%). High power density has reached the international advanced level.
Efficiency curve is shown as below.
-
Forced wind cooling
Advanced design of Circuit makes for low-heating with heat sink. -
Hot swappable
The monitoring module is hot-pluggable. When the module is plugged into the system, it will not cause the system output voltage fluctuations. Damaged modules can be replaced in less than 1min without stopping the system operation. -
Protection & failure alarm
In different protection / fault types rectifier has different reaction / action mode. -
Auto equalized output in low-gap voltage of modules
Adopted auto equalized output in low-gap voltage of modules technology. When the monitor module or individual rectifier is failure the other modules can maintain current sharing. -
Stepless limiting technology
With stepless limiting technology, it can be continuously adjusted between rated current 0~110% -
Monitor
Monitor has built-in CPU, monitoring the operation status of modules, and is responsible for the communication. The rectifier module receive ON/OFF current limit point and voltage setting sending by monitor through RS485, and send back the voltage, current,
temperature limiting point ON/OFF status and alarm in real time to the monitor module. -
Fan control and dust-proof
Stepless temperature control fan speed, and change with the output power of module, which minimize noise and extend fan life.
3. Specification
-
Environment
Work temperature: -25℃ ~ 45℃
Storage temperature: -40℃ ~ 70℃
Relative humidity:≤97%RH
Height above sea level:≤3000m -
Input properties
Input 75~175Vac ,output power:1500W,output current:10A
Input 175~300Vac ,output power:3000W,output current:20A -
Output properties
120VDC output,maximum output power 3000W
DC output voltage 90V ~ 150V, It can be continuously adjusted by monitoring module
DC output current 0A ~ 20A
Voltage regulation precision: ≤ 0.6%
Load regulation:≤ 0.5%
Voltage regulation:≤ 0.1% -
Output current-limiting properties
In the range of 0 ~ 110% rated current can be continuously adjusted. -
Power factor: ≥ 0.99
-
Efficiency: ≥ 95%
-
equalized-current imbalance: ≤ 3%
-
Temperature compensation coefficient:Can be set manually,unit (mV/℃)
-
Dc output noise:
Peak noise voltage:≤200mV 0 ~ 20MHz
Weighted psophometric noise voltage: ≤ 2mV
Wide frequency noise voltage: ≤50mV 3.4kHz ~ 150kHz
≤20mV 0.15 MHz 30MHz
Discrete noise voltage: ≤5mV 3.4kHz ~ 150kHz
≤3mV 150kHz ~ 200kHz
≤2mV 200kHz ~ 500kHz
≤1mV 0.5MHz ~ 30MHz -
Noise:≤45dB(A)
-
Alarm & Protection
1)Over-current protection
Over-current protection of input (use fuse)
Over-current protection of output (use fuse)
Over-current protection of PFC (use diverter)
Short circuit protection (reduce input current to protect)
2)Over-voltage & low-voltage protection (The following parameters can be adjusted by hardware.)
Input low-voltage protection: 75±5V, hysteresis:10V ~ 20V
Input over-voltage protection: 300±5V,hysteresis:5 ~ 20V
Output over-voltage protection:155 ±1V
- Other protection
Over- temperature protection (default value 80℃, hysteresis:10℃)
-
Size of the module:
88mm(H)×103mm(W)×261mm(D) -
Weight:≤2.6Kg
Chapter3 Monitor module
1. Appearance
M16 monitoring module has LCD screen (128*64 Blue background white text), key
and indicators. It can display data of the system in real time and setup by
keys.
Indicators | Normal | Abnormal | Reasons |
---|---|---|---|
Power supply indicator | On | Off | No AC input or input fuse is damaged |
Equalized & float charging indicator | Off | On | Equalized charging(On) |
Float charging(Off)
Failure indicators| Off| On| There is a damage inside the system
Advanced microprocessors make accurate, reliable and fast.
It has local control and remote monitoring, truly intelligent system.
2. Features and Functions
2.1. Input specification
Rating DC input voltage:120VDC
Range of voltage: 90V~150VDC
Work temperature: -25℃~ 45℃
2.2. Display and setting
Monitor module will display: operating parameter, states, warning, setting
parameter and control parameters.
Key Description: There are 4 bottoms on the monitor panel: “ ”, “↑”, “↓”, “┛”.
Press“┛” to change the parameter. Press “↑”, “↓” to change its data, and “┛”
to save. keys: “ ” “↑” “↓” “┛ ”. Press the keys to change the data, and save
the change.
Operation process and instruction
-
Screensaver:
Display the current time and date.
Press “ ┛ ” to enter system information menu. -
System information menu: Display the current system voltage (online voltage), load current, battery current and module current.
Press “┛” to enter the password menu . -
System information menu
Display AC input voltage, AC input current and AC input frequency.
Press “┛” to enter the password input menu -
System information menu
Display LVD Status.
Press “┛” to enter the password input menu -
System information menu:
Display battery temperature, charge mode (Equalized/Float charging) and the alarms event.
Press“┛”to view more alarms content -
Modules information:
Display module 1-N info。
Press “↑” “↓” to check the other modules information. Press “┛” to enter the password input menu -
Input password:
The default password is 0000. The user can enter the system menu to change your password. -
Main menu:
Press “↑” “↓” to choose the item, and press “┛” to view the details. -
Main menu:
Press “↑” “↓” to choose the item, and press “┛” to view the details. -
Main menu:
Press “↑” “↓” to choose the item, and press “┛” to view the details. -
System voltage setup:
Set System float voltage.
Press “↑” “↓” to change the value, and press “┛” to confirm. -
Charge management:
Press “↑” “↓” to choose the item, and press “┛” to view the details. -
Charge management:
Press “↑” “↓” to choose the item, and press “┛” to view the details. -
Charge management:
Press “↑” “↓” to choose the item, and press “┛” to view the details. -
Battery charge current limit value:
Set battery charge limit value -
Value of Equalized Charging voltage:
Set value of Equalized Charging -
Value of Equalized charge time:
Value of Equalized charging time -
Value of Equalized charge period
Value of Equalized charge interval -
Equalized charging in specified time:
Set the specified charging time. When the time reaches the specified time, the charging status will change to Equalized charge, and the output of system is also Equalized voltage
-
Manual set Equalized /Float charging:
The user can change the charging model manually.
When set OK, the charge time will start from 0. -
Temperature compensates:
It can set compensation coefficient the starting point. For example, the coefficient is 2mV, and the starting point 40℃, the output voltage should minus 20mV at 50℃. -
Set alarm limit value:
Here, it can set the values of battery high/low voltage and AC over voltage alarm value. -
Set alarm limit value:
Set AC under voltage value, AC over current value and AC frequency range value -
Set alarm limit value
Set battery temperature alarm value and alarm sound control (ON/OFF). -
Set over voltage alarm value:
Set overvoltage value. When the system voltage exceeds this value, the system will shut down the module and not recoverable. -
Set under voltage alarm value:
Set under voltage alarm value. When the system voltage is below this value, the system will sound single audible alarms.
-
Set AC over voltage alarm value
AC overvoltage setting. When the AC voltage is higher than this value, the system will sound single audible alarms. -
Set AC under voltage alarm value
AC under voltage setting. When AC voltage is below this value, the system will sound single audible alarms. -
Set AC over current value
AC over current setting. When AC current is over this value, the system will sound single audible alarms. -
Set AC frequency range
AC frequency range setting. When AC frequency is over this range, the system will sound single audible alarms. -
Set temperature alarm value
Set the battery temperature alarm value. When the battery temperature is over this value, the system will sound single audible alarms. -
Audible alarm setting
The user can set if the system will sound alarm or not. The default is ON. -
Low voltage disconnection set
2-class LVD.
press “┛” to view the details. -
LVD 1
Low voltage disconnection 1 connects the main load. When the battery voltage is shortage, the main load disconnected.
When the battery voltage is recovery to the working voltage, it will automatically work. -
LVD 2
-
Set time
Set system time and date. -
Reset password
Here to change the new password. Input new password, and press “┛”. -
Language
Select the language. -
Version
Monitor device version. -
System Set configuration
Configure the number of modules of the current system.
2.3 Control functions
The MINI System can release control signals according to the operation of the
system.
Monitor module supports both automatic and manual battery management. Manual
mode includes: equalized/float charging of battery groups, adjust rectifier
modules voltage (it can change the system voltage), and set battery charging
time. In automatic mode, the device will automatically complete the battery
charge management according to charge interval and the specified date. When
the system works, it can also change the charge mode (equalized or float
charging). That is manual mode. In manual mode, all timing starts from zero,
and continue to timing by the automatic mode, which can effectively prevent
human operational errors to result in losses.
2.4 Complete communication functions
Host can monitor and control all the parameters, the status of the lower
machine. At the same time, for safety and reliable, the host and the lower
machine not only install the communication protocol to constrain each other,
but also must know the monitor password of the lower machine, and sent it to
the lower machine, when the host wanted to get the all parameters of the lower
machines or monitor the lower machine. After the lower machine checked
correctly, it can monitor and control. This is to ensure the stability of the
power and avoid unnecessary losses caused by human.
2.5 Alarm & Record
Monitoring module has sound and light alarm function according to collect data
and a corresponding action. The main alarms are emergency, main and minor.
2.6 Automatic battery management
Monitor module can implement various conservation measures to protect the
battery, such as charging current limit, temperature compensation according to
user set data, and charging current limit, average and float charge conversion
time, average and float charge
voltage etc. battery charging methods.
2.7 Communication
Monitor module has the host and the lower device communication functions. It
communicates with the host by RS232; communication with the lower device by
RS485.
2.8 Dry contact output
There are 3 dry contact outputs.
Emergency dry contact: Mains failure, LVD1, LVD2, over-voltage module, module
fan failure.
Main dry contact: Battery fuse alarm, MCB alarm.
Minor dry contact: battery temperature alarm, communication failure.
Chapter4 Rack system
1. Front panel
5pcs 110v 20A rectifier modules, 1pcs monitor (From left to right place)
2 Back panel
3. Communication Dry Contact
The communication interface and dry contact interface sketch map as below:
1.About dry contact:
Level 1:line lack of phase、low-vol break away、modules over-vol、failure
of modules fan
Level 2:loads switch alarm、batteries switch alarm
Level 3:batteries over-tem,modules communications
2. The LVD interface specification:
Above picture, from top to bottom: 2-3: LVD1; 4-5: LVD2. 1, 2, used for system
extension.
Two coil control signal lines of contactor, connected to 2 and 3 hole
(contactor signal lines irrespective of positive or negative) it can achieve
the first level LVD,
If connect to 4 and 5 hole, it can achieve the second level LVD, 1 and 6 hole
designed for the realization of the function extension.
Warranty Card
To ensure good quality product, the MINI power supply system was thoroughly checked before leaving the factory. The manufacturer guarantees to the user that the system is in good condition. The manufacturer provides 2-years warranty service from date of delivery to the original purchaser Please refer to the warranty statement.
User’s Information
User Company:………….. Contact person:…………….
Address:…………………………. Phone:………………..
Dealer company:……………… Post code:…………….
Model:……………………… Serial number:………………..
Purchase date:……………….Hand ing person: ……………..
Repair Record
Date | Record | Abstract | Technician | Signature |
---|---|---|---|---|