CHAUVIN ARNOUX ULYS Flex Modbus User Guide

June 10, 2024
CHAUVIN ARNOUX

ULYS FLEX MODBUS
Non intrusive application
QUICK GUIDE

CHAUVIN ARNOUX ULYS Flex Modbus User Guide

For the complete user manual, please contact the Manufacturer.

WARNING!
Device installation and use must be carried out only by qualified staff. SWITCH OFF THE VOLTAGE BEFORE MAKING ANY CONNECTION.

IMPORTANT! ULYS FLEX is provided in 4 versions:

  • KIT 30/3 with reference P01331046
  • KIT 70/3 with reference P01331047
  • KIT 30/10 with reference P01331048
  • KIT 70/10 with reference P01331049

The items make up a kit and they cannot be used separately.

TECHNICAL FEATURES

POWER SUPPLY

Voltage range| 85 … 265 VAC / 110 VDC ±15%
Max consumption (per phase)| 1.6 VA – 1 W
T type fuse (to be mounted externally)| 250 mA
Frequency| 50/60 Hz
VOLTAGE INPUTS
Voltage range| 3×10/17 … 3×285/495 VAC
CURRENT INPUTS
Maximum value, according to the selected scale| 500 A (700 A max)
4 kA (5,6 kA max)
20 kA (28 kA max)
TYPICAL ACCURACY
Voltage| ±0.2% reading, 10% fs…fs
fs=full scale/fondoscala
Current| ±0.4% reading, 5% fs…fs
Power| ±0.5% reading ±0.1% fs (PF=1)
Frequency| 0.1% reading ±1 digit 45…65 Hz
Active energy class 1 according to| IEC / EN 62053-21
Reactive energy class 2 according to| IEC / EN 62053-23
COMMUNICATION PORT
Type| RS485
Protocols| MODBUS RTU/ASCII
Communication speed| 300 … 57600 bps
DIGITAL OUTPUT (DO)
Passive optoisolated|
Maximum value (according to IEC / EN 62053-31)| 27 VDC – 27 mA
Energy pulse length (only for DO in pulse mode)| 50 ±2 ms ON time
Maximum frequency| 8 pulse/s (8 Hz)
Output reaction time (only for DO in alarm mode)| max 1 s
WIRE DIAMETER FOR TERMINALS
Measuring terminals (A&V)| 1.5 … 6 mm
2
Terminals for digital output, AUX input, RS485 port| 0.14 … 2.5 mm
2
SIZE & WEIGHT
Length x Height x Depth – Weight| 72x90x65 mm – max 436 g
ENVIRONMENTAL CONDITIONS
Operating temperature| -25°C … +55°C
Storage temperature| -25°C … +75°C
Humidity (without condensation)| max 80%
Protection degree – front part, terminals| IP51, IP20
INTERNAL USE

GENERAL OVERVIEW

1. RS485 port
2. Digital output
3. AUX power input
4. SET button| 5. UP button
6. ENTER button
7. DOWN button
8. Voltage & current inputs
---|---

DIGITAL OUTPUT CONNECTION

The instrument is provided with a passive optoisolated digital output for pulse emission or alarm.

RS485 PORT CONNECTION

The RS485 port allows to manage the instrument in local or remote mode by MODBUS RTU/ASCII protocol. For instrument network connection, install a terminal resistance (RT=120…150 Ω) on the RS485/USB converter side and another one on the last instrument connected on the line. The maximum recommended distance for a connection is 1200m at 9600 bps. For longer distances, lower communication speed (bps), low-attenuation cables or signal repeaters are needed. Refer to the following scheme.

VOLTAGE & CURRENT INPUTS

For Rogowski coil wiring, connect the yellow coil edge to the terminal (signal), and the white coil edge to the terminal (common). Refer to the following picture.

1. WHITE edge
2. Sheath
3. Shield| 4. BLUE wire
5. WHITE wire
6. YELLOW edge
---|---

POWER SUPPLY

WARNING!
Install a circuit breaker and an over-current device (eg. 250 mA T type fuse) between the instrument power supply and the electrical system.

Before connecting the instrument to the network, check that the network voltage corresponds to the instrument power supply value (85…265 VAC / 110 VDC ±15%).

PRELIMINARY SETUP

To set the preliminary settings, press SET button for at least 4 s. The first Installation setup page (Wiring mode) will be displayed. Scroll pages with or button.

  1. Per effettuare le impostazioni preliminari, premere il tasto SET per almeno 4 s. La prima pagina di Programmazione Installatore (Modalità d’inserzione) sarà visualizzata. Scorrere le pagine con il tasto o .
    WIRING MODE
    3.4.3=3 phases, 4 wires, 3 currents
    3.3.3=3 phases, 3 wires, 3 currents
    3.3.2=3 phases, 3 wires, 2 currents
    1ph=1 phase

  2. Press , the mode will start to blink.

  3. Change the mode with or and
    confirm with .

FSA SETUP MODE
ALL=a single FSA common for all phases
SEP=FSA separated for each phase (1, 2, 3)

  1.  Press , the mode will start to blink.
  2. Change the mode with or and
    confirm with .

The following page for FSA setup changes according to the selected mode. The following example refers to ALL selection mode. In case of SEP mode, FSA will be displayed and programmable for each phase.

CURRENT FULL SCALE (0.5 / 4 / 20 k A)

  1.  Press , the value will start to blink.
  2. Change the value with or and confirm with .

PT PRIMARY (000.001…999.999 kV)

  1. Press , the first value digit will start
    to blink.

  2. Change the value with   or and
    confirm with .

  3.  Proceed in the same way for the following digits. For direct connection, set 000.001.

PT SECONDARY
1 V=direct connection
80…150 V=if PT primary is different from 1

  1. Press   , the first value digit will start to blink.
  2. Change the value with or and confirm with .
  3. Proceed in the same way for the following digits.

COMMUNICATION SPEED
300, 600, 1.2k, 2.4k, 4.8k, 9.6k, 19.2k, 38.4k, 57.6k bps

  1. Press , the value will start to blink.
  2. Change the value with or and confirm with .

MODBUS MODE
8N1=RTU mode
7E2=ASCII mode

  1. Press , the value will start to blink.
  2.  Change the value with or   and confirm with .

MODBUS ADDRESS (1…247)

  1.  Press **** , the first value digit will start to blink.
  2. Change the value with or and confirm with .
  3. Proceed in the same way for the following digits.

ON ANY INSTALLATION SETUP PAGE

EXIT FROM INSTALLATION SETUP

  1. Press or to change the blinking value, YES to exit saving the settings, NO to exit without saving, CONT to  continue scrolling Installation setuppages.
  2. Confirm with .

CONSIDERATIONS ON FULL SCALE CALCULATION

The phase power full scale is the result of a multiplication between PT primary and phase X current full scale (X=1, 2 or 3). If the PT primary and secondary values are set to 1 (direct connection), the phase power full scale is the result of a multiplication between 290V and phase X current full scale (X=1, 2 or 3).
For the current full scale value to be used in the formula, consider the following values according to the selected instrument scale:
Scale 500A >FSA = 700A
Scale 4000A > FSA = 5600A
Scale 20000A > FSA = 28000A

Ex. formula for phase 1 power full scale: FSP1,S1,Q1 = PTpri FSA1 if PTpri=PTsec=1 > FSP1,S1,Q1= 290V FSA1
Ex. formula for system power full scale: FSP∑,S∑,Q∑  = 3 PTpri FSAMAX if PTpri =PTsec =1 > FSP∑,S∑,Q∑ = 3 290V FSAMAX

DIGITAL OUTPUT SETUP

To access User setup loop, on Setup? page press button for at least 3 s. The digital output setup page will be displayed. At first User setup access, the digital output is disabled (NONE) and no parameter is associated. To enable the digital output, press button, the NONE item will start to blink. With or button select the mode:

  • AL H=alarm mode, high threshold or negative active power sign
  • AL L=alarm mode, low threshold or positive active power sign
  • PULS=pulse mode

Confirm with button. For setup description of each digital output mode, refer to the following table.

ALARM MODE SELECTION

  1. The symbols which identify the parameter type (e.g. A1=phase 1 current) will start to blink. With or  button select the parameter to be associated to the digital output and confirm with button.
    Selectable parameters: Real time values, active power sign or DMD values. The Activepower sign parameter can be identified by SIGN displayed on the second row.

  2. In case of real time or DMD parameter selection, the second row will display threshold value. After parameter selection,the threshold first digit will start to blink.
    With or  button select the digit and confirm with button. Repeat the same procedure for the other digits. The value range changes according to the selected parameter.In case of Active power sign parameter selection, the second row will display the SIGN static text instead of the threshold value.

  3. In case of real time or DMD parameter selection, the third row will display hysteresis value. After threshold selection, the hysteresis first digit will start to blink.
    With or  button select the digit and confirm with button. Repeat the same procedure for the other digit. Value range: 0…50%.In case of Active power sign parameter selection, the third row will display the delay value. After parameter selection, the delay first digit will start to blink. With or button select the digit and confirm with button. Repeat the same procedure for the other digit. Value range: 1…60s.

PULSE MODE SELECTION

  1. The symbols which identify the parameter type (e.g. -Wh∑=system exported active energy) will start to blink. With or  button select the parameter to be associated to the digital output and confirm with button. Selectable parameters: Energy counters except balance values.
  2. The pulse value first digit will start to blink. With or  button select the digit and confirm with button. Repeat the same procedure for the other digits. The value range changes according to the selected parameter.

ON ANY USER SETUP PAGE

EXIT FROM USER SETUP

  1. Press or  to change the blinking value, YES to exit saving the settings, NO to exit without saving, CONT to continue scrolling User setup pages.
  2.  Confirm with .

CHAUVIN ARNOUX ENERGY
16, rue Georges Besse
92182 ANTONY Cedex – FRANCE
Tel. : (33) 01 75 60 10 30 • Fax : (33) 01 46 66 62 54

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CHAUVIN ARNOUX User Manuals

Related Manuals