CHAUVIN ARNOUX C.A 6131 Electrical Installation Tester Owner’s Manual
- October 30, 2023
- CHAUVIN ARNOUX
Table of Contents
Electrical installation testers
C.A 6131 – C.A 6133
Owner’s Manual
Test the electrical safety of your installations
- Earth measurement by stake and loop methods
- Continuity measurement at 0.2A
- Insulation testing
- RCD testing: current and trip time
- Automatic test sequences
- Storage of test results
- ANDROID application for report generation
- Power supply by mains-rechargeable batteries, USB socket or vehicle cigarette lighter
ERGONOMICS AND FUNCTIONS
Designed for checking safety on electrical installations, the C.A 6131 and C.A
6133 can be used to test a new installation before powering it up, check an
existing installation, whether in operation or not, and to troubleshoot a
dysfunction.
For inspection organizations, these portable instruments are simple, effective
and, above all, compliant with the applicable standards.
Functions
Continuity| Compliant with the IEC 61557-4standard. If the buzzer is
active,users are informed by a beep ifthe measurement is below thethreshold,
so they do not have to look at the screen.
---|---
Earth| This function allows you to measure an earthy resistance using
the stake method when the electrical installation to be tested is not powered
up (new installation, for example). It is only available on the C.A 6133.
Loop| Loop measurement is performed in Trip or No Trip mode. On a TN or
TT installation, loopimpedance measurement can be used to size the protective
systems for the installation (fuses or RCDs), particularly in terms of
breaking capacity. Ona TT installation, this measurement serves to determine
the value of the earth resistance without setting up any stakes and without
having to power down the installation.
Insulation| The user selects the test voltage and chooses the set of
alarm thresholds. A visual indication instantaneously shows whether the test
is OK or not: if the measurement is higher than the threshold, the V LED
lights up. If the measurement is lower than the threshold, the X LED lights
up.
RCD| The comprehensive RCD test can be used with type A and AC RCDs. 3
types of test are available:
– No Trip test,
– Trip test in pulse mode,
– Trip test in ramp mode.
CHECK THE COMPLIANCE OF ELECTRICAL INSTALLATIONS WITH A SINGLE INSTRUMENT
COMPLEMENTARY FUNCTIONS AVAILABLE ON THE C.A 6133
Automatic test sequence
Save time! The AUTO-RCD automatic test sequence performs the following
operations:
- the No-Trip test, the Trip test at 1 x IΔn and the Trip test at 5 x IΔn,
- if necessary, the Trip test in ramp mode. A single press on the backup buttons saves all the tests performed.
Another automatic test sequence is also available which performs the following
tests, successively:
LOOP – RCD – INSULATION Current measurement
The MN73A clamp is recognized automatically when it is connected, as is the
measurement calibre. Data storage The data storage function can be used to
store your measurement results: up to 99 tests per site on up to 30 sites!
Bluetooth communication for Android IT-Report application
The ANDROID IT-Report application can be used to transfer the test results
stored in the C.A 6133 onto a tablet or smartphone via Bluetooth. Test reports
are then generated and sent automatically by email or simply stored for
processing later on.
Technical Specifications
| C.A 6131| C.A 6133
---|---|---
Range / Resolution / Accuracy| 0.00 to 9.99 Ω — Compensation of cables up to 5
Ω; I ⩾ 200 mA / 0.01 Ω / ± (2 % R* + 2 cts)
Resistance
Range / Resolution / Accuracy| 1 to 9,999 Ω — 10.00 to 99.99 kΩ / 1 Ω — 10 Ω /
± (1 % R + 5 cts)
Insulation
Test voltage| 250 V / 500 V| 250 V / 500 V / 1 000 V
Range / Resolution / Accuracy| 0.01 to 999.9 MΩ / 10 kΩ or 100 kΩ / ± (3 % R +
3 cts)
Earth resistance – 3P method
Range| –| 0.50 to 99.99 Ω| 100.0 to 999.9 Ω| 1,000 to 2,000 Ω
Resolution| –| 0.01 Ω| 0.1 Ω| 1 Ω
Accuracy| –| ±(2 % R + 10 cts)| ±(2 % R + 5 cts)| ±(2 % R + 5 cts)
Measurement frequency| –| 128 Hz
Earth loop (Zs) measurement
No Trip (12 mA)
Range / Resolution / Accuracy| 1 to 19 Ω — 20 to 39 Ω — 40 to 2,000 Ω / 1 Ω /
± (2 cts) — ±(15 % R + 3 < cts) — ± (5 % R + 2 cts)
Calculation of Ik| 1 to 999 A
With Trip (300 mA)
Range / Resolution / Accuracy| 0.1 to 0.9 Ω — 1.0 to 399.9 Ω / 0.1 Ω / ±(2
cts) — ±(5 % R + 2 cts)
Calculation of Ik| 1 to 9,999 A
Fault loop (Zi) measurement
Type of connection| Banana cables
Range / Resolution / Accuracy| 300 mA measurement current: 0.1 to 0.9 Ω — 1.0
to 399.9 Ω / 0.1 Ω / ± (2 cts) — ± (5% R + 2 cts)
Calculation of Ik| 1 to 9,999 A
RCD test
Installation voltage| 90 to 450 V; 45 to 65 Hz
Types and calibres| AC and A; 30 mA – 100 mA – 300 mA – 500 mA – 650 mA
Trip time| 0.5 x I ΔN ; 1 x I ΔN ; 5 x I ΔN / 5.0 to 300 ms
Trip current| 30 mA: 0 .. +(7%R +3.3% I ΔN + 2 mA)
Fault voltage: Range / Resolution / Accuracy| 1.0 to 25.0 V — 25.0 to 70.0 V /
0.1 V / ± (15% R + 3 cts) — ± (5% R + 2 cts)
Automatic test sequences| No| RCD, Loop-RCD-Insulation
Voltage & Frequency
Voltage: Range / Resolution / Accuracy| 2.0 to 550.0 VAC – 0.0 to 800.0 VDC /
0.1 V / ± (1%R+2cts)
Frequency: Range / Resolution / Accuracy| –| 30.0 to 999.9 Hz / 0.1 Hz / ±(0.1
% R + 1 ct) – Voltage > 2V
Phase rotation| 45 to 550 V — 45 to 65 Hz
Current
| Via clamp with voltage output using the voltage sensor function (AUX)| Via
MN73A clamp with 2A calibre: 10.0 mA to 2,400 mA, 200 A calibre: 1.00 to 200 A
AUX sensor function (C.A 6131)
AC+DC range: Range / Resolution / Accuracy| 2.0 to 999.9 mV / 1.000 to 1.2000
V / 0.1 mV — 1 mV / ±(1 % R + 2 cts)|
DC range / Resolution / Accuracy| ±(0.0 to 999.9 mV) — ±(1.000 to 2.000 V) /
0.1 mV — 1 mV / ±(1 % R + 2 cts)|
General Specifications
Display | Custom 231-segment LCD with blue backlighting |
---|---|
Data storage | – |
Communication | – |
Software | – |
Power supply | 6 x LR 6 or AA batteries |
charging < 6 hrs , USB or vehicle cigarette lighter
Battery life| > 1,900 continuity measurements at 1 Ω| > 1,700 continuity
measurements at 1 Ω
Dimensions / weight| 223 x 1 26 x 70 mm / 700 g approx.
Environment| Use: 0 to 40 °C / Storage: – 10 to 70 °C (RH 80%)
Protection| IP 54 (IEC 60 529) ; IK 04 (IEC 50102)
Standards / Electrical safety| EMV: IEC 61326-1 ; IEC 61010-1 ; IEC
61010-2-030 ; IEC 61010-2-034, 600V CAT III, 300V CAT II on charger input
Compliance with IEC 61557| Parts 1, 2, 3, 4, 6, 7 and 10| Parts 1, 2, 3, 4, 5,
6, 7 and 10
State at delivery and references
C.A 6131 | P01146011 |
---|
Low-voltage installation tester delivered in a cardboard box containing:
- 1 carrying bag
- 1 neck strap
- 1 EURO mains 3-pole cable
- 3 x 1.5m/4 mm safety cables (red/black/green),
- 3 crocodile clips (red/black/green),
- 1 black test probe, 6 x LR6 1.5V batteries,
- 1 User’s manual on CD-ROM (5 languages),
- 1 quick startup guide on paper,
- 1 safety datasheet,
- 1 test report with measurement report
C.A 6133 | P01146013 |
---|
Low-voltage installation tester delivered in a cardboard box containing:
- 1 carrying bag
- 1 neck strap
- 1 EURO mains 3-pole cable
- 3 x 1.5m/4 mm safety cables (red/black/green),
- 3 crocodile clips (red/black/green),
- 1 black test probe,
- 6 x NiMH batteries,
- 1 x 2A USB power supply,
- 1 razor-type USB power cable,
- 1 User’s manual on CD-ROM (5 languages),
- 1 quick startup guide on paper,
- 1 safety datasheet,
- 1 test report with measurement report
- 1 battery information sheet
Accessories
- Remote-control probe: P01102157
- MN 73A 2A/200A bi-calibre current clamp with 4-point connectors (C.A 6133): P01120439
- MN 73 2A/200A bi-calibre current clamp with banana connections (C.A 6131): P01120421
- Continuity rod P01102084A
FRANCE
Chauvin Arnoux
190, rue Championnet
75876 PARIS Cedex 18
Tel: +33 1 44 85 44 38
Fax: +33 1 46 27 95 59
export@chauvin-arnoux.fr
www.chauvin-arnoux.com| UNITED KINGDOM
Chauvin Arnoux LTD
Unit 1 Nelson Ct, Flagship Sq, Shaw Cross Business Pk
Dewsbury, West Yorkshire – WF12 7TH
Tel: +44 1924 460 494
Fax: +44 1924 455 328
info@chauvin-arnoux.co.uk
www.chauvin-arnoux.com| MIDDLE EAST
CHAUVIN ARNOUX MIDDLE EAST
P.O. BOX 60-154
1241 2020 JAL EL DIB – LEBANON
Tel: +961 1 890 425
Fax: +961 1 890 424
camie@chauvin-arnoux.com
www.chauvin-arnoux.com
---|---|---