Chauvin Arnoux CA 8345 Three-phase electrical networks analyser User Guide
- June 5, 2024
- CHAUVIN ARNOUX
Table of Contents
- Power and energy quality analyzer
- Functions & Measurements
- Standard verification campaigns
- The CA 8345: a diagnostic tool
- Monitoring
- Communication
- Applications
- Power and energy quality analyzers
- Magnetized mounting system
- Power supply accessories
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Arnoux CA 8345 Three-phase electrical networks analyzer
User Guide
Recording
Hundreds of parameters are stored in memory every 10/12 periods.
Alarms
The parameters are monitored within configurable limits.
Transients
Fast events are captured and their characteristics are stored in memory.
TrueInrush
Studying loads during startup is now much simpler.
The Qualistar moves up a grade
- Voltage quality diagnostics
- Full compliance with IEC 61000-4-30 Class A
- Highly communicating instrument
- Qualistar range of easy-to-use products
Power and energy quality analyzer
Intended for inspection and maintenance teams on industrial or tertiary
installations, the Qualistars give you a snapshot of the main electrical
network quality features.
Comfortable to handle and equipped with an intuitive GUI, these analyzers
offer high measurement accuracy.
They also feature numerous calculated values and several processing functions.
Functions & Measurements
General
- Portable energy quality analysis
- Instrument compliant with IEC 61000-4-30 edition 3.0 Class A for all functions
- Measurements on all installation types: three-phase, Aron connection, etc.
- Electrical network monitoring with the setting of alarms
- IP54 casing 55 mm thick with stand
- IEC 61010 CAT IV 1000 V
- Parameterization with software for EN 50160 reports
Measurements
- All DC components are taken into account
- Harmonics (amplitude and phase shift) from DC to the 63rd order
- Inter-harmonic subgroups from 0 to the 62nd order
- 2 carrier current frequencies monitored
- Measurement of P, N, Q1, S, and D power values (total and per phase)
- Measurement of energy values (total and per phase) with Energy valuation
- Internal GPS for precise UTC synchronization (NTP possible too)
Communication
-
USB 2.0 external flash drive supported (host devices)
-
USB 2.0 connection with a PC
-
Ethernet 100 Mbps communication
-
Wi-Fi 802.11b/g communication
-
Webserver for a remote user interface with Android,
Microsoft and iOS applications -
Backup and recording of screenshots (image and data)
-
Recording and export to a PC
-
Software for real-time data recovery and communication with a PC
Ergonomics
- Wide 7-inch color LCD touch screen (WVGA)
- Real-time display of waveforms (4 voltage and 4 current)
- DC current sensor power supply
- 5 x 50 Hz/60 Hz AC/DC voltage inputs
- User-friendly, multilingual GUI
- Intuitive use
- User profiles
- Fully multi-task instrument
- Automatic recognition of different current sensors
- Display of phasor diagrams
- Waveforms at 512 samples per cycle, with Min/Max 2.5µs
- Real-time waveforms displayed from 1 cycle to 10/12 cycles
Calculations
- Calculation of K factor & FHL
- Calculation of distorting voltages and currents
- Calculation of Displacement Power Factor (PDF) and Power Factor (PF)
- Calcul of Pst & Plt flicker and the sliding Pst
- Calculation of unbalance (current and voltage)
- Waveform Inrush with a duration of 10 minutes
- RMS and Peak Inrush for up to 30 minutes
- The capture of hundreds of 2.5 µs transients
- Capture shockwaves up to 12kV with a resoluton of 500ns
- Recording of trends
- Trend recording period from 200 ms to 2 hrs
Standard verification campaigns
IEC 61000-4-30
Definition of the measurement methods
The International Electrotechnical Commission (IEC) has drawn up the IEC
61000-4-30 standard. This standard defines:
- the methods for measuring the quality parameters for the supply of power to electrical power networks
- in the form of alternating current at a stated fundamental frequency
- and how to interpret the results.
The measurement parameters are described for each applicable parameter in terms that provide reliable, repeatable results, however, the method is implemented.
IEC 61000-4-7
Harmonics and interharmonics
The IEC 61000-4-7 standard defines the measurement methods for voltage quality
analyzers so that they remain compliant with the emission levels stipulated in
certain standards (e.g. the harmonic current limits specified by IEC
61000-3-2) and for the measurement of harmonic currents and voltages on the
power networks themselves.
|
---|---
Homogeneous tolerances
The EN 50160 standard characterizes the quality of the voltage supplied. It
presents the different types of disturbances that may affect the voltage on a
network. It lists the parameters to be monitored and defines how long the
parameters should be monitored.
With the PAT3 software, the Monitoring mode can be used to set up a simplified
configuration of all the limits to be monitored and the parameters to be
recorded.
IEC 61000-4-15
Short or long-term flicker
This is caused by mains voltage modulation. When it affects lighting, it gives
an impression of unstable vision due to a light stimulus whose luminance or
spectral distribution fluctuates over time.
There are 2 parameters calculated from the mains voltage.
- Pst which is a short-term assessment based on a 10-minute observation period
- Plt which is a long-term assessment, usually over a period of 2 hours
The CA 8345: a diagnostic tool
Viewing the signal and its components
The CA 8345 is an easy-to-use analytical tool. After connection, the CA 8345
immediately and totally automatically displays the voltages up to 1,000 V AC
and DC and the currents, thanks to a function that automatically recognizes
the sensor connected.
A large number of sensors are compatible with the Qualistar range.
|
---|---
The Waveform mode automatically provides an oscillogram showing
the voltage and/or current waveforms.| It is very simple to measure harmonics
and inter harmonics with the CA 8345, which is very easy to use as an
analytical tool.
|
The CA8345 can be used to monitor all the power values (P, Q, D, etc.) in
real-time over periods of varying durations. Measurement and analysis of all
the power values measured enable you to perform a full power survey in
compliance with the standards.| The phase relation between the voltages and
currents is displayed with a vectorial diagram. The vectorial representation
allows you to confirm that the instrument is connected to the mains.
With a simplified configuration
Energy valuation
The Qualistar Class A offers users all the measurements required to
successfully implement energy efficiency projects and monitor electricity
distribution.![Chauvin Arnoux CA 8345 Three-phase electrical networks analyser
- figure 11](https://manuals.plus/wp-content/uploads/2022/07/Chauvin-Arnoux- CA-8345-Three-phase-electrical-networks-analyser-figure-11.jpg)
Shockwaves
Usually caused by lightning, shockwaves are spectacular instantaneous
electrical voltage surges. They also propagate in the digital network. The
Qualistar Class A can withstand shockwaves up to 12 kV which are sampled every
500 ns.
Carrier currents
In the harmonic analysis function, there is also a mode for monitoring carrier
currents. After defining their frequency in the instrument, the command
signals will then be measured.
Interharmonics
The Qualistar Class A models can be used to measure and display the
interharmonics, as requested in IEC 61000-4-7, for very precise analysis of
all the disturbances on an electrical network.
Monitoring
Trend
The trend graph shows the variations of the parameters measured over time
every200ms.
Alarms
Alarms for parameterizing the threshold overruns to be monitored, which are
then recorded and time-stamped with the duration and extreme values.
Users can be informed directly by email when an alarm is triggered.
Transients
Transients correspond to peaks in the voltage or current waveform. Shockwaves
are extremely fast transients with even greater possible amplitude
TrueInrush
For tests when starting uploads, these instruments can record ½-period values
covering more than half an hour and the waveform of the signal (three-phase
voltages and currents).
Communication
Software![Chauvin Arnoux CA 8345 Three-phase electrical networks analyser
- figure 19](https://manuals.plus/wp-content/uploads/2022/07/Chauvin-Arnoux- CA-8345-Three-phase-electrical-networks-analyser-figure-19.jpg)
The Power Analyzer Transfer software processes the measurements made with the Qualistar Class A.
- Configuration of the instrument: setup, recording, alarms
- Real-time display
- Processing of all the recorded data
- Transfer of screenshots and transients
- Data exported into a spreadsheet (Excel, CSV)
- Data export in graphic form in Windows™
The web server
The Qualistar Class A models are equipped with firmware for remote access. It
can be controlled via VNC. which controls a remote machine while displaying
its desktop. It can be activated from any browser (Chrome, Edge, Firefox,
Qwant, etc,).![Chauvin Arnoux CA 8345 Three-phase electrical networks analyser
- figure 20](https://manuals.plus/wp-content/uploads/2022/07/Chauvin-Arnoux- CA-8345-Three-phase-electrical-networks-analyser-figure-20.jpg)
Communication
In addition to using media such as SD cards and USB keys, it is possible to
recover the measurements and communicate with the instrument remotely via USB,
remote links, Wifi (direct or via server), or RJ45.
There is no limit to the accessibility of the measurements.
IRD Server
All our IT networks are protected against external attacks.
Thanks to the provision of access to our IRD server, a single authorized IP
output address allows you to transmit your measurements all over the world.
SCPI commands
With an integrated interfacing software layer, it is possible to control your
instrument via its own software application. SCPI commands are available for
all the instrument’s functions.
Data files in JSON format
Saved in JSON format, all the recordings are accessible and can be processed
with a third-party and/or proprietary application.
Applications
Tertiary and industrial
Today, electrical distribution networks are judged according to their ability
to power loads causing disturbances and loads sensitive to disturbances. The
latter may take multiple forms.
A voltage quality analyzer can be used to detect and qualify each one: outage,
dip, voltage swell, flicker, THD, voltage variations, etc.
Energy efficiency
For energy diagnostics on a site, a logger must be set up to record the
electrical power and energy consumed. Once all the measurements have been
taken, the billing data are compared with the actual measurements. The study
determines whether corrective action needs to be taken. This action may take
different forms: resizing of a transformer, implementation of filtering
systems, replacement of faulty equipment, etc. This analysis helps you to act
in the right place at the right time to provide the best solution.
Electrical maintenance
The spread of electronic power supplies in industrial processes has led to an
increase in harmonic disturbances on the electrical network which have a
direct impact on the quality of the energy distribution. In the short or
medium term, these disturbances may cause failures across all the electrical
devices connected to the network in question.
Harmonic currents have negative effects on nearly all the components in the
electrical system, creating new dielectric, thermal and/or mechanical
stresses.
Power and energy quality analyzers
Current accessories
Model
| MN93| MN93A| MA194| PAC 93| A193-800 A193-450| C193| E3N / E21|
I 193
---|---|---|---|---|---|---|---|---
Measurement
range| 500 mA
to 200 Aac| 0.005 Aac
to 100 Aac| 100 mA to 10 ka| 1 A to 1,000 Aac 1 A to 1,300 Adc| 100 mA to 10
ka| 1 A to 1,000 Aac| 50 mA to 10 Aac/dc 100 mA to 100 Aac/dc| 50 A to 3,500
Aac 50 A to 5,000 Adc
Clamping
diam. /length| 20 mm| 20 mm|
170mm/ 250mm
0100m/350mm
I 300mm /1,000mm
|
lx 1 39 mm
1x 0 25 mm
| 0 140mm/450mm
0 250 mm/800 mm| 52 mm| 11.8 mm| 72 mm
IEC 61010| 600 V CAT III / 300 V CAT IV| 1000 V CAT III /
600 V CAT IV| 600 V CAT III /300 V CAT IV| 1000 V CAT III /
600 V CAT IV| 600 V CAT IV| 600 V CAT III /
300 V CAT IV| 600 V CAT III /300 V CAT IV
Essailec unit
A cable with an ESSAILEC plug can be used to perform tests without disturbing
or interrupting the power supply circuit on the meters and the protection
relays installed in the secondary circuits of current or voltage transformers.
The main advantage is that it speeds up and simplifies measurement while
ensuring maximum user safety.
Reeling Box
This practical magnetized reeling box equipped with the MultiFix system lets
you adjust the lengths of your cables. The reeling box can be opened to
install banana cables for voltage measurements or MiniFlex MA194 sensors for
current measurements, as required. It also makes it simple to stow your
cables.
Shoulder bag
All-terrain bag with watertight base and shoulder strap (380 x 280 x 200 mm)
with internal compartment
Compartmented internal bag for storage.
Magnetized mounting system
Power supply accessories
PA40W-2
The PA40W power supply with a charger can power the instrument when it is used
over long periods so that you can work without draining the internal battery.
It can also be used to recharge the battery.
PA32ER
The PA32ER power supply/charger can also be used to connect directly to a
1,000 AC or DC electrical network, between phases or phase-neutral with banana
leads.
| PA40W-2| PA32ER
---|---|---
Rated voltage and
overvoltage category| 600 V CAT III| 1000 V CAT IV
Input voltage| 100 to 260 V| 100 to 1,000 Vac / 150 to 1,000 Vdc
Input frequency| 0 to 440Hz| DC, 40 to 70 Hz, 340 to 440Hz
Output power| 40 W max| 30 W max
Dimensions| 160 x 80 x 57 mm| 220 x 112 x 53 mm
Weight| 460 g approx| 900 g approx.
CA8345
Inputs | Voltage/current, isolated |
---|---|
Voltage | 5 V to 1,000 Vac and Vdc |
IEC 61000-4-30 (Ed 3) | Class A (Full) |
Screen | 7″ colour LCD touch screen: 800 x 480 (WVGA) |
Clock / GPS | Yes, built-in |
Real-time mode | Yes |
Sampling rate | Voltage 400 kSps / Current 200 kSps / Surge 2 MSps |
Power mode | Yes |
Energy mode | Yes |
Unbalance mode | Composite |
Harmonics mode | DC to 63rd order |
Interharmonics mode | 0 to 62nd order |
Trend recording | > 900 parameters |
Alarm mode (types / number) | 52 / 20,000 |
Carrier current detection mode | Yes |
Inrush capture (number) | 100 |
2.5 µs transients (number) | No maximum (SD card) |
Shockwaves | Up to 12 kV sampled every 500ns |
EN50160 monitoring mode | With PAT3 software |
USB communication | Yes |
SD card | Accessible, external |
Ethernet | Yes |
Wifi | Yes |
Web server | Yes |
USB key port (Type A) | Yes |
Battery cartridge | Li-ion – 5800 Ah |
IEC 61010 safety | CAT IV 1000V |
Protection | IP54 |
Operating temperature | [+0 °C; +40 °C] |
Environmental compliance | IEC 61557-12 & IEC 62586 |
Dimensions (H x L x D) | 200x285x55 mm / 1.9 kg |
Warranty | 3 years |
CA 8345 delivered with
• Safety datasheet | • Set of identification inserts and rings |
---|---|
• 5 reeling boxes | • Verification certificate |
• Shoulder bag | • Removable wrist strap |
• USB A/B cable 1.80 m long | • Magnetic hook |
• Multilingual Quick Start Guide | • SD memory card |
• Set of 5 banana leads and crocodile clips |
CA 8345 standard…………P01160657
- PA40W-2 mains power supply/charger
CA 8345-1000……………P01160658
- PA32ER mains power supply/charger
• 1000V STD PA32ER power supply………….. | P01103076 |
---|---|
• PA40W-2 mains adapter…………………………. | P01102155 |
• C8 adapter………………………………………………….. | P01103077 |
• Bag………………………………………………………………. | P01298083 |
• SD card……………………………………………………….. | P01103078 |
• Magnetized hook………………………………………… | P01103079 |
• Wrist strap………………………………………………….. | HX0122 |
• External battery charger support……………… | P01102130 |
• Li-ion battery………………………………………………. | P01296047 |
• C193 clamp………………………………………………… | P01120323B |
• MN93 clamp………………………………………………. | P01120425B |
• MN93A clamp…………………………………………….. | P01120434B |
• E27 clamp…………………………………………………… | P01120027 |
• E3N/E27 adapter………………………………………… | P01102081 |
• PAC93 clamp……………………………………………… | P01120079B |
• J93 clamp……………………………………………………. | P01120110 |
• In-vehicle charger………………………………………. | HX0061 |
• AmpFlex | P01120556B |
® | P01120531B |
A193-450 mm clamp……………… | P01120593 |
• AmpFlex | P01120592 |
® | P01120594 |
A193-800 mm clamp……………… | P01101959 |
• MiniFlex MA194-250 mm clamp……………… | P01102131 |
• MiniFlex MA194-350 mm clamp……………… | P01101967 |
• MiniFlex MA194-1000 mm clamp…………… | P01102149 |
• 5 A casing……………………………………………………. | P01295483 |
• ESSAILEC casing…………………………………………. | P01295174 |
• PAC 93 mains adapter……………………………….. | P01120596 |
• Reeling box………………………………………………….
• Kit of banana leads with crocodile clips x5| P01120596
• C7 mains power cable…………………………………| P01120591
UNITED KINGDOM
Chauvin Arnoux Ltd
Unit 1 Nelson Ct, Flagship Sq, Shaw Cross
Business Pk Dewsbury, West Yorkshire
WF12 7TH
Tel: +44 1924 460 494
Fax: +44 1924 455 328
info@chauvin-arnoux.co.ukr
www.chauvin-arnoux.com
MIDDLE EAST
Chauvin Arnoux Middle East
P.O. BOX 60-154
1241 2020 JAL EL DIB – LEBANON
Tel: +961 1 890 425
Fax: +961 1 890 424
camie@chauvin-arnoux.com
www.chauvin-arnoux.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>