Roth 466210.218 Shunting Of Underfloor Heating Distributor Shunt Installation Guide

June 10, 2024
Roth

Roth Shunt
Living full of energy

Installation Shunt
Roth 466210.218 Shunting Of Underfloor Heating Distributor Shunt
-

Technical data

Roth shunt, 3-way valve HVAC no. 7466210218
Max. operating temperature 80 ºC
Max. differential pressure 15 – 20 kPa
Max. operating pressure 6 bar
Pump Wilo Para 15-130/6-43/SC-12
Regulation range 20-60°C (+/- 5°C)
Primary side connection EURO ¾” external
Union for manifold 1” internal
Material Brass CW614
Gasket EPDM
Medium Water containing up to 50% glycol
Electrical connection 230V with earthing

Roth 466210.218 Shunting Of Underfloor Heating Distributor Shunt - Flow,
floor heating

The shunt is mounted directly on the manifold by tightening the two 1” unions. Remember to use the gaskets supplied.

Roth 466210.218 Shunting Of Underfloor Heating Distributor Shunt - gaskets
supplied

The shunt is mounted on the left, but it can be reversed by undoing all unions and rotating the pump.Roth 466210.218 Shunting Of Underfloor Heating
Distributor Shunt - can be reversed

Mount the thermostat on the supply valve and the sensor in the sensor pocket. Set the thermostat to the preferred supply temperature.
Lock the thermostat to an appropriate regulation range by pressing the white locking catches on the sensor ele ment. See the scale in Figure 4.Roth
466210.218 Shunting Of Underfloor Heating Distributor Shunt - thermostat on
the supply

Venting and flushing the installation of air must be done one circuit at the time. Connect the filling hose to the upper manifold valve and the discharge hose from the lower manifold valve and flush to the drain. Refill the installation to desired pressure when all air has been removed.Roth
466210.218 Shunting Of Underfloor Heating Distributor Shunt - flushing the
installation

The pump is set to I, II or III depending on the size of the system and heat loss in the building.Roth 466210.218 Shunting Of Underfloor Heating
Distributor Shunt - depending on the size

Faults that may prevent the pump operating (such as blockages) are indicated by the red LED showing.
If the fault is indicated, rectify the fault and wait for the pump to restart automatically.Roth 466210.218 Shunting Of Underfloor Heating Distributor
Shunt - prevent the pump operating

Accessories:
Control: Roth weather compensation
HVAC no. 7466210827

ROTH UK Ltd
1a Berkeley Business Park
Wainwright Road
Worcester WR4 9FA
Phone +44 (0) 1905 453424
E-Mail enquiries@roth-uk.com
technical@roth-uk.com
orders@roth-uk.com
accounts@roth-uk.com
roth-uk.com

ROTH DANMARK A/S
Centervej 5
3600 Frederikssund
Tlf. +45 4738 0121
E-mail: service@roth-danmark.dk
roth-danmark.dk| ROTH SVERIGE AB
Höjdrodergatan 22
212 39 Malmö
Tel. +46 40534090
Fax +46 40534099
E-mail: service@roth-sverige.se
roth-sverige.se
---|---
ROTH NORGE AS
Billingstadsletta 19
1396 Billingstad
Tel. +47 67 57 54 00
E-mail: service@roth-norge.no
roth-norge.no
facebook.com/RothNorge| ROTH FINLAND OY
Raaseporintie 9 (Talo 2)
10600 Tammisaari
Puh. +358 (0)19 440 330
S-posti: service@roth-finland.fi
roth-finland.fi
facebook.com/RothFinland

RN1000.218_Installation Roth 3-vejs shunt_20220706

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Roth User Manuals

Related Manuals