Beghelli CT Formula 65 LED Instruction Manual
Installation Instruction
Basic setting
Connect the battery AFTER cutting the wire for autonomy selection The selection of the autonomy of the lamp made by the App has priority over the settings on the circuit.
Wiring with Infinity mode deactivated
For the functioning please refer to the instruction manuals either of the Central CableCom Connect (cod. 20151).
For the Central configuration the batteries must be sufficiently charged.
Be careful NOT to invert the phase and neutral polarity. Maximum connectable lamps 32. Do not connect other types of devices on the power cable / BU
Wiring 2.1 The appliance goes into emergency conditions for:
- absence of a general emergency electricity (CableCom);
- absence of a local lighting
Caution
SA luminaires can be set SE only through the App (with smartphone flash on the lamp or with wi-fi with Central CableCom Connect). With Infinity mode on N2 L2 must be connected like wiring 2.1 or 2.2.
| 230V
50Hz
| COS j| | | ***
---|---|---|---|---|---
19290 SE**| 180mA| 0.07| 32 LED| Life 6,4V 1,5Ah|
1h 1,5h 2h 3h 8h
¥ **
19291 SE| 180mA| 0.07| 32 LED| Life 6,4V 1,5Ah
19292 SE| 180mA| 0.07| 32 LED| 2x Life 6,4V 1,5Ah
19293 SE| 180mA| 0.07| 32 LED| 2x Life 6,4V 1,5Ah
19294 SA| 180mA| 0.115| 32 LED| Life 6,4V 1,5Ah
19295 SA| 180mA| 0.115| 32 LED| 2x Life 6,4V 1,5Ah
19296 SA| 180mA| 0.115| 32 LED| 2x Life 6,4V 1,5Ah
Expansion with LG • LGFM • DALI module
CONFIGURATION AND COMMANDS
|
AT (without APP and without Central)
| AT + APP| AT + CENTRALE CABLECOM CONNECT (cod. 20151) + APP
---|---|---|---
– CONFIGURATION| Autonomia- Duration 1h| • Default| • Default| •
Default
Autonomia- Duration 1,5h| | •| •
Autonomia- Duration 2h| | •| •
Autonomia- Duration 3h| • con jumper| •| •
Autonomia- Duration 8h| | •| •
SA (solo su lampade SA)
(only on Maintained Luminaire)
| | •| •
| | •| •
Test duration 1h or autonomy set| • Test duration 1h| •| •
Setting Infinity mode| Infinity mode disabled by default| | •
Rest Mode| | | •
Manufacturer data reset| | •| •
E FUNZIONI –| Start/Stop functional Test| | •| •
Start/Stop duration Test| | | •
Sync automatic Test| | •| • Con partenza ritardata configurabile • With
configurable delayed start
Scheduling automatic Test| | | With change periodicity
Remotizzazione errore Failure report from remote place| | | By LED on
Central; the APP indicates which lamp is in error
Luminaire tracking| | | •
Type of luminaire identification| | | •
LOGBOOK| | | •
Use with App B.connect
A- Open App B.connect (available for download on the App Store and
Google Play).
B- The configuration of the lamp can be accessed through the
“luminaire” menu.
LAMP RESPONSE:
1 high brightness flash= function performed 5 low light flashes= function NOT enabled No flashing= command NOT received
N.B. With CableCom Connect control unit cod 20151 all configurations and commands can be sent remotely via the “nuBe” cloud.
POSITION LAMP FOR COVER ENSURE THE PROGRAM (eg. a lot of light – less distance)
AUTOMATIC TESTS PERIODICITY:
FUNCTIONAL TEST (30 sec)= every 28 days AUTONOMY TEST (1h)= every 26 weeks Even lamps carry out the autonomy test 1 week after the odd lamps. (0,2,…,8,A,C,E)= even; (1,3,…,9,B,D,F)= odd
FIXED GREEN: BATTERY CHARGED
FLASHING GREEN: BATTERY CHARGING
ONE RED FLASH: BATTERY ERROR DURATION
TWO RED FLASHES: LIGHTING LED ERROR THREE RED FLASHES
BATTERY DISCONNECTED
The communication remains possible for 2 hours and for 1 min the LED flashes orange to signal the communication opening.The Functional Test and the Functional STOP Test are controlled by the B.Connect App at any time without having to open communi- cation with the device.
WARNINGS – GUARANTEE
- This device shall be used exclusively for the purpose for which it has been Any other use is considered improper and the-refore dangerous.
- Rechargeable battery and LED source are non-replaceable type. Contact an authorised technical service centre for any repairs pos- sibly required use only original spare
The lacked respect of the above conditions may compromise the safety of the
device.
* Caution** : electric shock