VYNCO VMC51 Combined Meter Board Instruction Manual

June 11, 2024
VYNCO

VYNCO logo VMC51 / VMC51BK – 51 WAY COMBINED METER BOARD
INSTALLATION INSTRUCTIONS

SPECIFICATIONS

Rated Operational Voltage 415V AC maximum, 50Hz
Maximum Current 100A
Rated Insulation Voltage 1000V
Short Circuit Withstand 10kA

DIMENSIONS

Cover Assembly 800 x 402 x 35mm
Base Box Dimensions 754 x 355 x 106mm

WARRANTY
This product is covered by a 1 Year Vynco Warranty – proof of purchase is required. Please contact Vynco for details of returns procedure.
NOTE: This product contains NO user serviceable parts.

SAFETY

This product complies in full with AS/NZS 61439.3.
This product should be installed by a suitably qualified person in accordance with Australian and New Zealand wiring rules.

INSTALLATION PROCEDURE

This product is designed to be installed inside a wall cavity with a minimum stud size of 90mm and a minimum plaster board/wall covering of 10mm.
For surface mounting use VMCC surface mount enclosure in conjunction with this board.
The metal wall enclosure must be earthed. Fold out tags (x6) on the side walls of the enclosure can be folded out to set the correct height onto the studs.
Door hinge pins are easily removable and the door can be reversed so that it swings either left or right.
This product is designed to be used with New Zealand and Australia’s MEN system.
DO NOT install a link between the neutral bars and earth bar on circuits dedicated to RCDs.
Please ensure circuits and protective devices are adequately identified during installation.

EARTH AND NEUTRAL BUSBAR LAYOUT

| Material| Number of Bars| Double Screw Tunnels| Single Screw Tunnels
---|---|---|---|---
Earth Bar| Brass with steel screws| 1| 3| 40
Neutral Bar| Brass with steel screws| 1| 4| 22
RCD Neutral Bar| Brass with steel screws| 8| 1| 3

VYNCO VMC51 Combined Meter Board - REMOVING DOOR REMOVING DOOR
STEP 1
Rotate top pin 90°.
STEP 2
Slide pin down to release door. There is no need to remove pin completely.
STEP 3
Lift and remove door.
FITTING DIAGRAM
VYNCO VMC51 Combined Meter Board - FITTING DIAGRAM To fit into wall cavity, fold out tabs to set height of enclosure onto studs.

VYNCO INDUSTRIES (NZ) LIMITED CHRISTCHURCH
388 Tuam Street, Phillipstown, Christchurch, 8011
PO Box 9022, Tower Junction, Christchurch 8149
New Zealand
P +64 3 379 9283
E sales@vynco.co.nz
VYNCO.CO.NZ
AUCKLAND
9 Levene Place, Mount Wellington
PO Box 12 249, Penrose, Auckland 1061
New Zealand
P +64 9 525 6051
INSV0058

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals