CHADHA POWER 0610446606 Solar Hybrid Home Industrial UPS Inverter User Manual

June 11, 2024
CHADHA POWER

CHADHA POWER 0610446606 Solar Hybrid Home Industrial UPS

CHADHA-POWER-0610446606-Solar-Hybrid-Home-Industrial-UPS-
product

Dear Customer,
Congratulations! You are now a proud owner of Pure Sine Wave Solar Hybrid UPS with the world’s latest MOSFET-based technology.
Please do spare some time to read this manual. This manual will provide you a thorough understanding of your Pure Sine Wave Solar Hybrid UPS for its optimum use. Please take note of installation and operating instructions in this manual carefully before installing and using your Pure Sine Wave Solar Hybrid UPS. Pay special attention to the section under precaution. In this section the manual lists out conditions and or practices which can not only result in damage to your Solar Hybrid UPS or to the other equipment but may result in personal injury or loss of life also.

  • Hope you shall be fully satisfied with the product for years to come.
  • We value your relationship with us.
  • With best wishes and warm regards
  • Management Team
  • Chadha Power

About Pure Sine Wave Solar Hybrid UPS

Let’s begin the journey to explore our Solar Hybrid UPS. Solar Hybrid UPS transforms Direct Current (DC) to Alternating Current (AC). The preliminary source will be Solar Power and Mains will be treated as a secondary source. The Battery Bank acts as a reservoir to ensure a continuous supply of power whenever a mains supply from utility power is not available.

Front Panel of the Pure Sine Wave Solar Hybrid UPSCHADHA-POWER-0610446606
-Solar-Hybrid-Home-Industrial-UPS-fig- \(1\)

Description of Switches & LEDs on Front Panel CHADHA-POWER-0610446606
-Solar-Hybrid-Home-Industrial-UPS-fig- 5

**Details of LCD

CHADHA-POWER-0610446606-Solar-Hybrid-Home-Industrial-
UPS-fig- \(2\)**

About LCD DlaplayCHADHA-POWER-0610446606-Solar-Hybrid-Home-Industrial-
UPS-fig- 6 CHADHA-
POWER-0610446606-Solar-Hybrid-Home-Industrial-UPS-fig- 7

About Backlit Indication

CHADHA-POWER-0610446606-Solar-Hybrid-Home-
Industrial-UPS-fig- 8

Rear Panel of the UPS

CHADHA-POWER-0610446606-Solar-Hybrid-Home-
Industrial-UPS-fig- \(3\)

Description of Rear Panel

CHADHA-POWER-0610446606-Solar-Hybrid-Home-
Industrial-UPS-fig- 9

Some Safety Measures

Important Precautions

Our Solar Hybrid UPS has two Battery terminals {Red and Black or Terminal Block (HTJ ), AC Fuse, DC MCB, AC Input, and AC Output socket are also at the back panel of the Solar Hybrid UPS. The red wire has to be connected to the +ve terminate of the Battery & the Black wire has to be connected to the -ve terminal only. Never reverse the battery connections it will trip off the battery fuse/ DC MCB.
Caution : Ensure that the incoming phase is connected to ‘L’. Neutral is connected to ‘N’ and earth is connected through OUTPUT socket of the Solar Hybrid UPS.

General Precautions:

  • Read all instructions & caution markings on the Solar Hybrid UPS before using.
  • Do not expose any kind of chemicals to Solar Hybrid UPS.
  • Disassembling the Solar Hybrid UPS without experienced service personnel may cause electric shock or fire hazards.
  • Always inform the authorized persons or take it to an authorized service center. Disconnect all wiring before cleaning to prevent risk of electric shock. Avoid exposing your solar hybrid UPS or batteries to any type of explosive gases (in the vicinity, as batteries generate explosive gases during normal operations). Provide proper ventilation to the battery compartment. The battery enclosure should be designed to prevent the accumulation and concentration by Hydrogen gas in the pocket at the top of the Compartment.
  • Vent the battery compartment from the highest point. A sloped lit can also be used to direct the flow to the vent opening location to reduce the risk of battery explosion, follow all the instructions of the battery manufacturer or any other equipment you intend to use in the vicinity of batteries. Always use the correct toots to make AC/DC wiring connections. Never install the Solar Hybrid UPS near highly flammable objects.

Caution:

  • The Solar Hybrid UPS connections should be properly grounded through a permanent wiring system.
  • Installation should ensure that the UPS AC output should not be connected to AC input mains.
  1. Before installing, connecting any wiring, or using the UPS, read all instructions of this instruction manual.

  2. Never disconnect the battery cables while the UPS is delivering power or the battery charger is operating. Always turn the switch OFF first and tum OFF AC mains input.

  3. Do not install or connect batteries unless instructed to do so. Failing to comply with this instruction can cause damage or complete failure of the unit.

  4. To reduce Msk of injury, use only deep cycle lead acid battery.

  5. Do not expose the system to rain, snow or liquids of any type. Do not disassemble the system; take it to a nearby authorized service center when service or repair is required. Incorrect re-assembly may result ina risk of electric shock or fire.

  6. To reduce risk of electric shock, disconnect all wiring from the system before attempting any maintenance or cleaning. Turning off the system will not reduce this risk.

  7. Be extra cautious when working with metal tools on, or around ba-. The potential exists to drop a tool and short-circuit the -or other electrical parts resulting in sparks that could cause an explosion.

  8. Baking soda neutralizes lead acid battery electrolytes. Keep a supply on hand in the area of the batteries.

Personal Precautions

  1. Someone should be within range of your voice to come to your aid when you work near batteries.
  2. If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eyes, immediately flood eyes with running cool water for at least 15 minutes and get medical attention immediately.
  3. Never attempt to charge a frozen battery.
  4. Before touching the battery terminal make sure that the system front switch is OFF and AC mains to the UPS is also OFF.
  5. Never smoke or allow a spark or flame in the vicinity of the ba-.
  6. If it is necessary to remove any battery, always remove the grounded terminal from the battery first. Make sure all the accessories are off, so as not to cause arcing.
  7. Clean battery terminals. Be careful not to allow corrosion to come in contact with eyes.
  8. Add only distilled water in each cell until acid reaches level specified by the battery manufacturer. This helps purge excess gas from cells. Do not overfill. For a battery without caps, carefully follow the manufacturer’s recharging instructions.

Getting Started

Environment & Location

Pure Sine Wave Solar Hybrid UPS should be installed as close as possible to the battery bank to keep the battery wires short in length. Never place the Solar Hybrid UPS in the same compartment because batteries generate gases that are very corrosive to electronic equipment. As it is a sophisticated device it should be kept in a non-condensing, well-ventilated, and moisture-free environment.

Important precautions

Never connect the output wiring of the UPS to the incoming Utility wiring. This situation is worse than short circuit, however, if the Solar Hybrid UPS survives this situation the system will shut down automatically until corrective action is taken. We suggest independent circuit breakers (MCB/MCCB) for 1/P, O/P & Solar circuits as per the capacity of the Solar Hybrid UPS.

Connecting Cable Requirements-CHADHA-POWER-0610446606-Solar-Hybrid-Home-
Industrial-UPS-fig- 10

  • Secure the wiring with ties or other non-conductive fasteners to prevent damage.
  • NOTE: There is no back feed current toward PV array.
  • WARNING: When sunlight is exposed on the photovoltaic array, so it starts to supply DC Voltage to Solar Hybrid UPS.

Installation of Solar Hybrid UPS

Where to Install

The system should be installed in a location that is near to Distribution Box and meets the following requirements•

  • Dry- do nol allow waler lo drip or splash on lhe UPS.
  • Cool – The ambient temp. near the system should be in between cfc and 45° C (32 F and 113 F), the cooler environment is better for the system.
  • Ventilated – Allow at least 6 Inches (15 cm) of clearance around the system for air flow.
  • Safe – Do nol inslall lhe UPS along wilh battery in any closed compartment without venlilation. Also, do not install the battery near to storage of inflammable gas/ liquid.
  • Distance from the Battery- Install the system at a safe distance from the battery as any electric spark on UPS fuse or output’ input connection may get in touch with the explosive gases of the battery which may cause fire. Chadha Power will not be responsible for any damage due to this.

CAUTION! TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT INSTALL THE SYSTEM IN A ZERO-CLEARANCE COMPARTMENT. OVER HEATING MAY RESULT.

How to install

DC Cabling

  1. Ensure that the ON/OFF switch on the front panel of the UPS is in the OFF mode before you begin the inslallation.
  2. Connect the (-ve) terminal of lhe battery to lhe Black wire (-ve) of lhe system and lhen connect lhe (+ve) terminal of the battery to the Red wire {+ve} of the system. It is advised not to use any other extra cable for batteries olher than lhose supplied by the company.
  3. Connect +ve and -ve wires from Solar Panel to +ve and -ve terminals respectively available on the back panel of UPS.

AC Cabling

Plug in the power cord to the mains socket on the wall. The cabling should have proper earthing. Connect AC input supply lo lhe 3 way terminal of lhe system such that the line is connected to ‘L’, neutral is connected to ‘N’ and earth is connected to ‘E’. AC input supply should remain ON once the system is inslalled. Take output from 6/16A output socket or tenminal block available at back panel

Start Operation

Once the AC and DC wiring have been completed and connected, take a moment to re-examine all the connections and make sure they are secured and in the proper terminals.

  1. Switch ON the UPS. The system should run a load without AC input (battery only). Place a load on the system and make sure it works.
  2. To charge the batteries, connect mains cord to the mains socket & check the connection of wires from Solar PV panel and tum it ON. Battery BAR running upward on LCD indicates the charger is working properly. AC load connected to the UPS should also work at this time since the AC power fed to the load is passed lhrough the UPS in both (Nonnal and High) modes.
  3. Disconnect the AC power. The UPS will transfer the supply to the load from Mains to Battery mode immediately. This will be indicated by Battery BAR running downward on LCD with clicking sounds as the internal relay changes its connection. The system will begin to take power from the batteries and use n to power the load uninterruptedly.

The above steps will complete a functional test of the UPS. If all steps pass the system is ready for use. If any steps fail, figure out the reason before proceeding and contact the service support.

Note:-
Fuses and disconnects must be sized to protect the wiring in the system. The fuse has to be blown before the wire reaches ns maximum current carrying capacity.

Applications

  • Power Backup for House Hold as well as Computers
  • Emergency Power Systems
  • Small Water Pumps and all motor-based applications
  • TV Sets, Fans, Tube Lights, CFL etc.

Conditions Apply

Installation Diagram

CHADHA-POWER-0610446606-Solar-Hybrid-Home-
Industrial-UPS-fig- \(4\)

Technical Specifications

CHADHA-POWER-0610446606-Solar-Hybrid-Home-
Industrial-UPS-fig- 11 CHADHA-POWER-0610446606-Solar-Hybrid-Home-Industrial-UPS-fig-
12

Trouble Shooting

CHADHA-POWER-0610446606-Solar-Hybrid-Home-Industrial-
UPS-fig-13 CHADHA-
POWER-0610446606-Solar-Hybrid-Home-Industrial-UPS-fig-14

Buzzer will sound only when the UPS switch is in ON condition.

SAFETY MEASURES

DO NOT MIX WITH OTHER WASTES FOR DISPOSAL
To prevent possible harm to the environment or human health this product should not be disposed with other waste. Household users should contact either their retail seller or local government office for safe recycling. Business users should contact their supplier and check the terms and conditions of the purchase contract for proper disposal.

INDIA CHADHA POWER LLP F-Block, Ground Floor
The Mira Corporate Suites 1 & 2, Old Ishwar Nagar, Mathura Road New Delhi – 110065, India
Tel: ÷ 91 11 26910057
Website: www.chadhapower.com
Email: [email protected]

SOUTH AFRICA CHADHA POWER (SAI (PTY) LTD
Unit 30, Bridgeway Business Park 496 Pinnacle Street, Tunney Germiston, 1401 South Africa
Website: www.chadhapower.co.za
Email: [email protected]

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CHADHA POWER User Manuals

Related Manuals