PPI HumiTherm GD Temperature and Humidity Controller with Graphic Display Instruction Manual
- June 11, 2024
- PPI
Table of Contents
PPI HumiTherm GD Temperature and Humidity Controller with Graphic Display
Operation
OPERATOR PAGE PARAMETERS
Parameters| Settings (Default Value)
Temp.
Set Value >>
| SP Low Limit to SP High Limit for Temperature (Default : 25.0)
RH
Set Value >>
| SP Low Limit to SP High Limit for RH (Default : 60.0)
Temp.
LO Deviation >> (Available only if Temp. Low Deviation Alarm is Enabled)
| 0.2 to 99.9
(Default : 2.0)
Temp.
HI Deviation >> (Available only if Temp. High Deviation Alarm is Enabled)
| 0.2 to 99.9 (Default : 2.0)
RH
LO Deviation >> (Available only if RH Low Deviation Alarm is Enabled)|
0.2 to 99.9
(Default : 2.0)
RH
HI Deviation >> (Available only if RH High Deviation Alarm is Enabled)|
0.2 to 99.9 (Default : 2.0)
Change Password >>| 1 to 100
(Default : 0)
SUPERVISORY > SERIAL PARAMETERS
Parameters| Settings (Default Value)
Device ID >>| 1 to 127
(Default : 1)
Baud Rate >>| 2400
4800
| 9600
| 19200
| 38400
| 57600
| (Default : 9600)
Parity >>| None Even Odd
(Default : Even)
Serial Write >>| No Yes
(Default : No)
SUPERVISORY > PV OFFSET
Parameters| Settings (Default Value)
Temp.
Zero Offset >>| -50.0 to 50.0
(Default : 0.0)
RH Zero Offset >>| -50.0 to 50.0
(Default : 0.0)
SUPERVISORY > TEMPERATURE / RH ALARM ENABLE
Parameters| Settings (Default Value)
Temp Low Alarm >> Temp High Alarm >>| Disable Enable
(Default : Enable)
RH Low Alarm >> RH High Alarm >>| Disable Enable
(Default : Enable)
SUPERVISORY > PASSWORD
Parameters| Settings (Default Value)
Change Password >>| 1000 to 1999 (Default : 123)
SUPERVISORY > EXIT
Parameters| Settings (Default Value)
Exit Setup Mode >>| Yes No
(Default : No)
FACTORY > TEMPERATURE > ALARM
Parameters| Settings (Default Value)
Hysteresis >>| 0.1 to 99.9
(Default : 0.2)
Inhibit >>| No Yes
(Default : No)
FACTORY > TEMPERATURE > CONTROL
Parameters| Settings (Default Value)
Tune >>| No Yes
(Default : No)
Setpoint LO Limit >>| 0.0 to Setpoint HI Limit (Default : 10.0)
Setpoint HI Limit >>| Setpoint LO Limit to 99.9
(Default : 99.9)
CONTROL ZONES : DUAL
Parameters| Settings (Default Value)
CZ Prop Band >>| 0.1 to 999.9
(Default : 50.0)
CZ
Integral Time >>
| 0 to 3600 Sec (Default : 100 Sec)
CZ
Derivative Time >>
| 0 to 600 Sec (Default : 16 Sec)
HZ Prop Band >>| 0.1 to 999.9
(Default : 50.0)
HZ
Integral Time >>
| 0 to 3600 Sec (Default : 100 Sec)
HZ
Derivative Time >>
| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
CONTROL ZONES : SINGLE
Parameters| Settings (Default Value)
Proportional Band >>| 0.1 to 999.9
(Default : 50.0)
Integral Time >>| 0 to 3600 Sec (Default : 100 Sec)
Derivative Time >>| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
FACTORY > TEMPERATURE > SENSOR INPUT
Parameters| Settings (Default Value)
Input Type >>| RTD Pt100 0-20mA
4-20mA
0-5V
0-10V
1-5V
(Default : RTD Pt100
Signal LO >> Signal HI >>| | Input Type| Settings| Default
---|---|---
Oto 20mA| 0.00
to 20.00
| 0.00
4 to 20mA| 4.00
to 20.00
| 4.00
0 to 5V| 0.000
to 5.000
| 0.000
0 to 10V| 0.00
to 10.00
| 0.00
1 to 5V| 1.000
to 5.000
| 1.000
Range LO >>| -199.9 to 999.9 Counts
(Default : 0.0)
Range HI >>| -199.9 to 999.9 Counts
(Default : 100.0)
FACTORY > HUMIDITY (RH) > ALARM
Parameters| Settings (Default Value)
Hysteresis >>| 0.1 to 99.9
(Default : 0.2)
Inhibit >>| No Yes
(Default : No)
FACTORY > HUMIDITY (RH) > CONTROL
Parameters| Settings (Default Value)
Tune >>| No Yes
(Default : No)
Setpoint LO Limit >>| 0.0 to Setpoint HI Limit (Default : 10.0)
Setpoint HI Limit >>| Setpoint LO Limit to 99.9
(Default : 99.9)
CONTROL ZONES : DUAL
Parameters| Settings (Default Value)
CZ Prop Band >>| 0.1 to 999.9
(Default : 50.0)
CZ
Integral Time >>
| 0 to 3600 Sec (Default : 100 Sec)
CZ
Derivative Time >>
| 0 to 600 Sec (Default : 16 Sec)
HZ Prop Band >>| 0.1 to 999.9
(Default : 50.0)
HZ
Integral Time >>
| 0 to 3600 Sec (Default : 100 Sec)
HZ
Derivative Time >>
| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
CONTROL ZONES : SINGLE
Parameters| Settings (Default Value)
Proportional Band >>| 0.1 to 999.9
(Default : 50.0)
Integral Time >>| 0 to 3600 Sec (Default : 100 Sec)
Derivative Time >>| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
FACTORY > HUMIDITY (RH) > SENSOR INPUT
Parameters| Settings (Default Value)
Input Type >>| 0-20mA
4-20mA
0-5V
0-10V
1-5V
(Default : 0-5V)
Signal LO >> Signal HI >>| | Input Type| Settings
---|---
0 to 20 mA| 0.00 to 20.00
4 to 20 mA| 4.00 to 20.00
0 to 5 V| 0.000 to 5.000
0 to 10 V| 0.00 to 10.00
1 to 5 V| 1.000 to 5.000
Default : Signal Low 0.000
Signal High 5.000
Range LO >>| -199.9 to 999.9 Counts
(Default : 0.0)
Range HI >>| -199.9 to 999.9 Counts
(Default:100.0)
FACTORY > COMPRESSOR
Control Strategy : Heat + Cool
COMPRESSOR STRATEGY >>| CONT. OFF CONT. ON SP BASED PV BASED
(Default : CONT. ON)
CONT. ON| SP BASED| PV BASED
Time Delay (sec) >>
0 to 1000 Sec (Default : 200 Sec)
| Boundary Set Value >>
0.0 to 100.0
(Default : 45.0)
| Compressor SP >>
0.0 to 100.0
(Default : 2.0)
| Control Zones >>
SINGLE DUAL
(Default : SINGLE)
| Hysteresis >>
0.1 to 99.9
(Default : 2.0)
Time Delay (sec) >>
0 to 1000 Sec
(Default : 200 Sec)
| Time Delay (sec) >>
0 to 1000 Sec
(Default : 200 Sec)
FACTORY > BOILER WATER LEVEL
Parameters| Settings (Default Value)
Enable >>| No Yes
(Default : No)
Water| Single Switch
Level Startegy >>| Dual Switch LO-HI Dual Switch LO-VLO
| (Default : Single Switch)
Switch-1 Logic >>| Open : Water LO Close : Water LO
(Default : Close : Water LO)
Switch-2 Logic >>| Open : Water HI Close : Water HI
(Default : Close : Water HI)
OR
Open : Water VLO Close : Water VLO
(Default : Close : Water VLO)
FACTORY > DOOR OPEN
Parameters| Settings (Default Value)
Enable >>| No Yes
(Default : No)
Switch Logic >>| Open : Door Open Close : Door Open
(Default : Close : Door Open)
Door
Alrm Dly (sec) >>
| 0 to 1000 Sec (Default : 60 Sec)
FACTORY > FACTORY DEFAULT
Parameters| Settings (Default Value)
Set To Default >>| No Yes
(Default : No)
FACTORY > PASSWORD
Parameters| Settings (Default Value)
Change Password >>| 2000 to 2999
(Default : 321)
FACTORY > EXIT
Parameters| Settings (Default Value)
Exit Setup Mode >>| No Yes
(Default : No)
FRONT PANEL KEY
KEYS OPERATION
Symbol | Key | Function |
---|---|---|
Scroll | Press to scroll through various Process Information Screens in |
Normal Operation Mode.
| Alarm Acknowledge| Press to acknowledge and mute (if active) alarm output.
| DOWN| Press to decrease the parameter value. Pressing once decreases the
value by one count; keeping pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the value
by one count; keeping pressed speeds up the change.
| SET-UP| Press to enter or exit set-up mode.
| ENTER| Press to store the set parameter value and to scroll to the next
parameter.
PV ERROR INDICATIONS
Message | Error Type | Cause |
---|
**OPEN**
| Sensor Open| Sensor (RTD Pt100) Broken / Open
**OVR**
| Over-range| Temperature above Max. Specified Range
UNR
| Under-range| Temperature below Min. Specified Range
ELECTRICAL CONNECTIONS
Documents / Resources
| PPI
HumiTherm GD Temperature and Humidity Controller with Graphic
Display
[pdf] Instruction Manual
HumiTherm GD Temperature and Humidity Controller with Graphic Display,
HumiTherm GD, Temperature and Humidity Controller with Graphic Display,
Controller with Graphic Display, Graphic Display
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>