PPI HumiTherm GD Temperature and Humidity Controller with Graphic Display Instruction Manual

June 11, 2024
PPI

PPI HumiTherm GD Temperature and Humidity Controller with Graphic Display

Operation

OPERATOR PAGE PARAMETERS

Parameters| Settings (Default Value)
Temp.

Set Value >>

| SP Low Limit to SP High Limit for Temperature (Default : 25.0)
RH

Set Value >>

| SP Low Limit to    SP High Limit for RH (Default : 60.0)
Temp.

LO Deviation >> (Available only if Temp. Low Deviation Alarm is Enabled)

| 0.2 to 99.9

(Default : 2.0)

Temp.

HI Deviation >> (Available only if Temp. High Deviation Alarm is Enabled)

| 0.2 to 99.9 (Default : 2.0)
RH
LO Deviation >> (Available only if RH Low Deviation Alarm is Enabled)| 0.2 to 99.9

(Default : 2.0)

RH
HI Deviation >> (Available only if RH High Deviation Alarm is Enabled)| 0.2 to 99.9 (Default : 2.0)
Change Password >>| 1 to 100

(Default : 0)

SUPERVISORY > SERIAL PARAMETERS

Parameters| Settings (Default Value)
Device ID >>| 1 to 127

(Default : 1)

Baud Rate >>| 2400

4800

| 9600
| 19200
| 38400
| 57600
| (Default : 9600)
Parity >>| None Even Odd

(Default : Even)

Serial Write >>| No Yes

(Default : No)

SUPERVISORY > PV OFFSET

Parameters| Settings (Default Value)
Temp.
Zero Offset >>| -50.0 to 50.0
(Default : 0.0)
RH Zero Offset >>| -50.0 to 50.0

(Default : 0.0)

SUPERVISORY > TEMPERATURE / RH ALARM ENABLE

Parameters| Settings (Default Value)
Temp Low Alarm >> Temp High Alarm >>| Disable Enable

(Default : Enable)

RH Low Alarm >> RH High Alarm >>| Disable Enable

(Default : Enable)

SUPERVISORY > PASSWORD

Parameters| Settings (Default Value)
Change Password >>| 1000 to 1999 (Default : 123)
SUPERVISORY > EXIT

Parameters| Settings (Default Value)
Exit Setup Mode >>| Yes No

(Default : No)

FACTORY > TEMPERATURE > ALARM

Parameters| Settings (Default Value)
Hysteresis >>| 0.1 to 99.9

(Default : 0.2)

Inhibit >>| No Yes

(Default : No)

FACTORY > TEMPERATURE > CONTROL

Parameters| Settings (Default Value)
Tune >>| No Yes

(Default : No)

Setpoint LO Limit >>| 0.0 to Setpoint HI Limit (Default : 10.0)
Setpoint HI Limit >>| Setpoint LO Limit to 99.9

(Default : 99.9)

CONTROL ZONES : DUAL
Parameters| Settings (Default Value)
CZ Prop Band >>| 0.1 to 999.9

(Default : 50.0)

CZ

Integral Time >>

| 0 to 3600 Sec (Default : 100 Sec)
CZ

Derivative Time >>

| 0 to 600 Sec (Default : 16 Sec)
HZ Prop Band >>| 0.1 to 999.9

(Default : 50.0)

HZ

Integral Time >>

| 0 to 3600 Sec (Default : 100 Sec)
HZ

Derivative Time >>

| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
CONTROL ZONES : SINGLE
Parameters| Settings (Default Value)
Proportional Band >>| 0.1 to 999.9

(Default : 50.0)

Integral Time >>| 0 to 3600 Sec (Default : 100 Sec)
Derivative Time >>| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
FACTORY > TEMPERATURE > SENSOR INPUT

Parameters| Settings (Default Value)
Input Type >>| RTD Pt100 0-20mA

4-20mA

0-5V

0-10V

1-5V

(Default : RTD Pt100

Signal LO >> Signal HI >>| | Input Type| Settings| Default
---|---|---
Oto 20mA| 0.00

to 20.00

| 0.00
4 to 20mA| 4.00

to 20.00

| 4.00
0 to 5V| 0.000

to 5.000

| 0.000
0 to 10V| 0.00

to 10.00

| 0.00
1 to 5V| 1.000

to 5.000

| 1.000

Range LO >>| -199.9 to 999.9 Counts

(Default : 0.0)

Range HI >>| -199.9 to 999.9 Counts
(Default : 100.0)
FACTORY > HUMIDITY (RH) > ALARM

Parameters| Settings (Default Value)
Hysteresis >>| 0.1 to 99.9

(Default : 0.2)

Inhibit >>| No Yes

(Default : No)

FACTORY > HUMIDITY (RH) > CONTROL

Parameters| Settings (Default Value)
Tune >>| No Yes

(Default : No)

Setpoint LO Limit >>| 0.0 to Setpoint HI Limit (Default : 10.0)
Setpoint HI Limit >>| Setpoint LO Limit to 99.9

(Default : 99.9)

CONTROL ZONES : DUAL
Parameters| Settings (Default Value)
CZ Prop Band >>| 0.1 to 999.9

(Default : 50.0)

CZ

Integral Time >>

| 0 to 3600 Sec (Default : 100 Sec)
CZ

Derivative Time >>

| 0 to 600 Sec (Default : 16 Sec)
HZ Prop Band >>| 0.1 to 999.9

(Default : 50.0)

HZ

Integral Time >>

| 0 to 3600 Sec (Default : 100 Sec)
HZ

Derivative Time >>

| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
CONTROL ZONES : SINGLE
Parameters| Settings (Default Value)
Proportional Band >>| 0.1 to 999.9

(Default : 50.0)

Integral Time >>| 0 to 3600 Sec (Default : 100 Sec)
Derivative Time >>| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
FACTORY > HUMIDITY (RH) > SENSOR INPUT

Parameters| Settings (Default Value)
Input Type >>| 0-20mA
4-20mA
0-5V
0-10V
1-5V
(Default : 0-5V)
Signal LO >> Signal HI >>| | Input Type| Settings
---|---
0 to 20 mA| 0.00 to 20.00
4 to 20 mA| 4.00 to 20.00
0 to 5 V| 0.000 to 5.000
0 to 10 V| 0.00 to 10.00
1 to 5 V| 1.000 to 5.000

Default : Signal Low 0.000
Signal High 5.000

Range LO >>| -199.9 to 999.9 Counts

(Default : 0.0)

Range HI >>| -199.9 to 999.9 Counts
(Default:100.0)
FACTORY > COMPRESSOR

Control Strategy : Heat + Cool
COMPRESSOR STRATEGY >>| CONT. OFF CONT. ON SP BASED PV BASED

(Default : CONT. ON)

CONT. ON| SP BASED| PV BASED
Time Delay (sec) >>

0 to 1000 Sec (Default : 200 Sec)

| Boundary Set Value >>

0.0 to 100.0

(Default : 45.0)

| Compressor SP >>

0.0 to 100.0

(Default : 2.0)

| Control Zones >>

SINGLE DUAL

(Default : SINGLE)

| Hysteresis >>

0.1 to 99.9

(Default : 2.0)

Time Delay (sec) >>

0 to 1000 Sec

(Default : 200 Sec)

| Time Delay (sec) >>

0 to 1000 Sec

(Default : 200 Sec)

FACTORY > BOILER WATER LEVEL

Parameters| Settings (Default Value)
Enable >>| No Yes

(Default : No)

Water| Single Switch
Level Startegy >>| Dual Switch LO-HI Dual Switch LO-VLO
| (Default : Single Switch)
Switch-1 Logic >>| Open : Water LO Close : Water LO

(Default : Close : Water LO)

Switch-2 Logic >>| Open : Water HI Close : Water HI

(Default : Close : Water HI)

OR

Open : Water VLO Close : Water VLO

(Default : Close : Water VLO)

FACTORY > DOOR OPEN

Parameters| Settings (Default Value)
Enable >>| No Yes

(Default : No)

Switch Logic >>| Open : Door Open Close : Door Open

(Default : Close : Door Open)

Door

Alrm Dly (sec) >>

| 0 to 1000 Sec (Default : 60 Sec)
FACTORY > FACTORY DEFAULT

Parameters| Settings (Default Value)
Set To Default >>| No Yes

(Default : No)

FACTORY > PASSWORD

Parameters| Settings (Default Value)
Change Password >>| 2000 to 2999

(Default : 321)

FACTORY > EXIT

Parameters| Settings (Default Value)
Exit Setup Mode >>| No Yes

(Default : No)

FRONT PANEL KEY

KEYS OPERATION
Symbol Key Function
Scroll Press to scroll through various Process Information Screens in

Normal Operation Mode.
| Alarm Acknowledge| Press to acknowledge and mute (if active) alarm output.
| DOWN| Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.
| SET-UP| Press to enter or exit set-up mode.
| ENTER| Press to store the set parameter value and to scroll to the next parameter.

PV ERROR INDICATIONS
Message Error Type Cause

**OPEN**

| Sensor Open| Sensor (RTD Pt100) Broken / Open

**OVR**

| Over-range| Temperature above Max. Specified Range

UNR

| Under-range| Temperature below Min. Specified Range

ELECTRICAL CONNECTIONS

Documents / Resources

| PPI HumiTherm GD Temperature and Humidity Controller with Graphic Display [pdf] Instruction Manual
HumiTherm GD Temperature and Humidity Controller with Graphic Display, HumiTherm GD, Temperature and Humidity Controller with Graphic Display, Controller with Graphic Display, Graphic Display
---|---