PPI ScaneX Programmable Multi Channel Temperature Scanner
CONFIGURATION PARAMETERS
Parameters
| Settings (Default Value)
---|---
Actual Numbers of Channels to Scan
|
1 to Max. Available (Default : 4/8/12/16)
Sensor-break PV Status
|
Up Scale
Down Scale
(Default : Up Scale)
Common Input
Configurations
|
No
Yes
(Default : Yes)
Select Channel for
Input Configuration
|
1 to Actual no. of
channels to scan
(Default : NA)
Input Type
|
Refer Table 1
(Default : Type K)
Resolution
|
1 or 0.1
(Default : 1)
Temperature Units
|
ºC
ºF
(Default : ºC)
Offset
|
1999 / 3000 or
-1999.9 / 3000.0
(Default : 0)
ALARM CONFIGURATION PARAMETERS
Parameters|
Settings (Default Value)
---|---
Number of Alarms Per Channel
|
For COMMON Relay O/P 1 to No. of Alarms/channel (Max. 4)
For INDIVIDUAL Relay O/P 1 to No. of Channels (Max. 16) (Default : NA)
Select Output Relay Number
|
Normal
Reverse
(Default : Normal)
Relay Latch
|
No
Yes
(Default : No)
ALARM SETTING PARAMETERS
Parameters | Settings (Default Value) |
---|
**Channel Number
| 1 to Max. Channels (Default : NA)
Alarm Number
| 1 to User Selected Alarm (Default : NA)
Alarm Type
**| None
Process Low
Process High
(Default : None)
**Alarm Setpoint
**| Min. to Max. of selected input type range (Default : 0)
Alarm Hysteresis
| 1 to 3000 or
0.1 to 3000.0
(Default : 2 or 2.0)
**Alarm Inhibit
**|
No
__
Yes (Default : No)
UTILITY PARAMETERS
Parameters | Settings (Default Value) |
---|
**Enable Min/max Monitoring
**|
** No
__**
Yes (Default : No)
**Password For Resetting Min/max Values
| ** 0 to 250
(Default : 0)
**Baud Rate
**| 4800
9600
19200
38400
57600
(Default : 9600)
Parity
| None
Even Odd
Default : Even
Serial Id
|
1 to 127
(Default : 1)
**Serial Write Permission
**| No
Yes (Default : No)
OPERATOR PARAMETERS
Parameters | Settings (Default Value) |
---|
Alarm Acknowledge
| No
Yes
(Default : NA)
Scan Rate
| 1 Sec. to 99 Sec. (Default : 3 Sec.)
Maximum PV
| View Only (Default : NA)
Minimum PV
| View Only (Default : NA)
Reset Command
| No
Yes
(Default : NA)
Reset Command
|
0 to 250 (Default : 0)
TABLE- 1
Option
|
What it means
|
Range (Min. to Max.)
---|---|---
****|
Type J Thermocouple
|
0.0 to + 960.0ºC /
32.0 to +1760.0ºF
****|
Type K Thermocouple
|
-200.0 to + 1376.0ºC /
-328.0 to + 2508.0ºF
|
Type T Thermocouple
|
-200.0 to + 387.0ºC /
-328.0 to + 728.6ºF
|
Type R Thermocouple
|
0.0 to + 1771.0ºC /
32.0 to + 3219.0ºF
|
Type S Thermocouple
|
0.0 to + 1768.0ºC /
32.0 to + 3214.0ºF
|
Type B Thermocouple
|
0.0 to + 1826.0ºC /
32.0 to +3218.0ºF
|
Type N Thermocouple
|
0.0 to + 1314.0ºC /
32.0 to +2397.0ºF
| Reserved for custom use (Default Type J)| Reserved for custom use
|
3-wire, RTD Pt100
|
-200.0 to + 600.0ºC /
-328.0 to +1112.0ºF
FRONT PANEL LAYOUT
Front Panel
Keys Operation
Symbol
| Key|
Function
---|---|---
|
PAGE
|
Press to enter / exit Set-up Mode
|
DOWN
|
Press to decrease the parameter value. Pressing once decreases the value by one count; holding the key pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the value
by one count; holding the key pressed speeds up the change.
|
ENTER
|
Press to store the set parameter value and to scroll to the next parameter.
|
ALARM ACK
|
Press to Acknowledge any pending Alarm(s)
|
AUTO / MANUAL
|
Press to toggle between Auto and Manual Scan Mode. In Manual Scan Mode, Use UP / DOWN keys to the desired channel.
PV Error Indications
Message
|
PV Error Type
---|---
|
Over-range
(PV above Max. Range)
|
Under-range
(PV above Min. Range)
|
Open
(Sensor open / broken)
ELECTRICAL CONNECTIONS
Old Connections Version
New Connections Version
101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar – 401 210.
Sales : 8208199048 / 8208141446
Support : 07498799226 / 08767395333
E: sales@ppiindia.net,
support@ppiindia.net
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>